PMT18-04222 City of Menifee Permit No.: PMT18-04222
AM Ar 29714 HAUN RD.
Type: Residential Electrical
-0 MENIFEE, CA 92586
MENIFEE MENIFEE Datelssued: 08128/2018
PERMIT
Site Address: 25479 KAMRAN CIR, MENIFEE, CA Parcel Number:
92584 Construction Cost: $7,626.00
Existing Use: Proposed Use:
Description of ROOF MOUNTED SOLAR SYSTEM,9 PANELS, 9 MICROINVERTERS,2.880 KW
Work: OAK HILL II TR 37102
LOT 11
Owner Contractor
JCA HOMES SUNSTREET ENERGY GROUP LLC
26040 ACERO 760 NORTHWEST 107 AVENUE
MISSION VIEJO, CA 92691 MIAMI, FL 33172
Applicant Phone: 3054854110
KRISTEN MURRAY License Number: 1001133
SUNSTREET ENERGY GROUP LLC
760 NORTHWEST 107 AVENUE
MIAMI, CA 33172
Fee Description ,OQt Amount I51
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise slated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Pemrit_Template.rpt Page 1 of 1
IT/PLAN& SAFETY PERM APPLICATION
Menifee
DATE 08/23/2018 PERMIT/PLAN CHECK NUMBER - 8
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑P00 A IG
SUBTYPE: ]ADDITION ❑ALTERATION ❑DEMOLITION [Z]ELECTRICAL ❑MEC@W1QgDgPt,
❑NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK INSTALL 2.880kW ROOF MOUNTED PV SYSTEM AUG Z 2018
Reeeiv6
PROJECTADDRESS 25479 KAMRAN CIRCLE, MENIFEE, CA92586 a
ASSESSOR'S PARCEL NUMBER LOT 11 TRACT 37102
PROPERTY OWNER'S NAME JCA HOMES
ADDRESS 26040 ACERO,MISSION VIEJO, CA 92691
PHONE (949)614-1434 EMAIL AMANDA.KASHANI@JCAHOMES.COM
APPLICANTNAME KRISTENMURRAY
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S NAME SUNSTREET ENERGY GROUP LLC OWNER BUILDER? ❑YES❑✓NO
BUSINESS NAME SUNSTREET ENERGY GROUP LLC
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S STATE LIC NUMBER 1001133 LICENSE CLASSIFICATION B
VALUATION$ $7,626.00 SQ FT L SQ FT
APPLICANT'S SIGNATURE " DATE 08/23/2018
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN 1 7 SMIP
INVOICE PAID AMOUNT O
AMOUNT • LOb O CASH JCHECK# CREDIT CARD VISA/MC
PLAN CHECK FEES PAIDAMOUNT 0CASH 0 CHECK# 0 CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department29714 Haun Rd. Menifee, CA 92586951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.880 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 9 PCS.1 LG 1 LG320NIK-A5(320) BUYER: —— _—_--_—_—_
INVERTER 1 9 PCS.1 ENPHASE I Q6PLUS-72-ACM-US
ROOF TYPE I CONIC. TILE DATE:
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3 ARRAY#4
MOD QTY 9 NA NA NA BUYER:
TILT 23' NA' NA' NA'
DATE: ____
AZIMUTH I80° NA' NA' NA'
City of Menitee
Building Dept
AUG 2 7 2018
10'-I'ARRAY Received
10'-11-FLASHING 21'
r
0
in
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY) cir a
BUI DII
PV AC DISCONNECT PUN A
EXTERIOR-GARAGE
UTILITY METER ) --
MAIN SERVICE PANEL �- REMIC11
(VERIFIED BY BUILDER) Gr
AC COMBINER BOX
(EXTERIOR-GARAGE) ,
ap val o
appr al of,
regull tons
jobsi e and
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN[ ELEVATION A-LEFT
ORIENTATION 3 LOT# II
ORIGINAL BY:DUSTIN LANNING DATE:17.07.12
OAK HILLS JCA HOMES REVIEWED BY:JIM PARKS DATE:17.07.13
26040 ACERO MISSION VIEJO,CA 92691 REV.# BY DATE DESCRIPTION
namasb6
301At
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 25479 KAMRAN CIRCLE Boulder,DO 803D4
PLOT PLAN 1/I6"=V-0, MENIFEE.CA 303.447.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY I MANUFACTURER MODEL NOTES TRADE
1 9 LG LG320NIK-A5(32OW) PV MODULE SOLAR
2 9 ENPHASE 106PLUS-72-ACM-US PV INVERTER SOLAR
3 1 RSTC /SOLADECK 0786-3R5 PV ROOF JUNCTION BOX.NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.24OV,30A SOLAR
5 1 ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR,120V SOLAR
6 1 ENPHASE X-I0-AMI-240-8 AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER, I X 20A-2P.I X 5A-IP SOLAR
8 1 CUTLER-HAMMER TBD PV BREAKER, I X 20A-2P.RATING MAY VARY SOLAR
9 1 TBD TBD SERVICE PANEL,200A BUS BLDR. ELEC.
10 1 TBD TBD UTILITY METER.IPH.120/240V.200A BLDR. ELEC.
II TBD TBD GROUNDING ELECTRODE,LIFER BLDR. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM I UNIT IPANEL
LOCATION MENIFEE,CA PANEL MFR. 1 CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT I AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC I AMPS 40
TEMP,DELTA LOW(TDELTA) TmIN-TTEST °C -27 PV OCPD DEVICE USED I AMPS 20
MOD.MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD. PART NUMBER AC MODULE SPEC LG320NIK-AS(320W) I.17A.9(MODS)=ID.53A OF CMRENT
MOD. POWER STC(P) AC MODULE SPEC WATTS(00 320 10.53A x 1.25-13.16 A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A 20A/2P 2 SPACE PV BAMFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC I WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT OAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC H2(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC W741 /IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 9
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD.OTY BC OTY 9
BRANCH CIRCUIT OUTPUT,IMAXBC (IAC•MOD.OTY BC) AMPS(AC) 10.53
AC MODULE QUANTITY.TOTAL MOD.OTY T OTY 9
TOTAL SYSTEM OUTPUT MARTS gWMOD.QTY T) AMPS(AC) 10.53
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COLD: (AMPACITY°TEMP.DERATE °FILL DERATE)vs.REQ'D(IMAX)
2)TERMINALS(TERM): AMPACITY AT TERMINALS. vs. REQ'D,(IMAX` 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL RESULT REQ'D OCD
TYPE DERATES DERATE OERATE (A) (A) USED �I A #12 CU THWN-2 COU 30 0.76 1.0 22.80 10.53 {'ENIFEE
TERM 25 25 13.16 20
B #10 CU NM-B COU 40 53
TERM 35 0.91 I.0 35 40 13.16 20 ; AND SA a
( #10 CU NM-B COU 40 0.91 1.0 36.40 10.53 `I
TERM 35 35 13.16 20 :PROVAL
CONDUCTOR SCHEDULE o
KEY TCONDUCTORS 1 CU/AL 1 TYPE lLOCATION 4 TRADE
A I-#12 ENGAGE CABLE,1-#6G.FREE AIR Cu TC-ER ARRAY SOLAR 41 _9�
B 3-#10, -#10 EGC CU NM-B(ROMEX) INTERIOR SOLAR C 3-#10. I-#10 EGC CU NM-B(ROMEX) INTERIOR SOLARe conO
isions
OI 02 p7 of app
2G
A g C
I I I
r ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.88OKW
LOT#II
ORIGINAL BY:DUSTIN LANNING DATE:17.07.12
OAK HILLS JCA HOMES REVIEWED BY:JIM PARKS I DATE:17.07.13
ERO
MISSION
N VIEJ REV.# BY DATE DESCRIPTION •,
MISSION VIEJO,CA 92691
- b namasGd
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4571 Broadway GO Street
INDIVIDUAL 25479 E.CA
CIRCLE BO303.4CO80304
PLOT PLAN 2 NTS MENIFEE,CA 303.447.Q30D
ELECTRICAL
INSTALLATION NOTES,
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
6)THE RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION MANUAL.
APRIL 2016 EDITION
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(V)SPACE BETWEEN PV MODULES.SOLARMOUM RAILS MUST EXTEND A MINIMUM OF TWO INCHES.(2')BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 401.
9)PV PANEL HAS BEEN TESTED BASED ON UL 1703.
10)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
IO BASE ATTACHMENT AND FLASHING TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
12)ALL ROOF ATTACHMENTS TO BE FLASHED AND SEALED PER MANUFACTURER'S SPECIFICATIONS.
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
IU MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER. 3A
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING /PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING
MINIMUM HEIGHT yH.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRINGIRACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER. l0 be a lInd`(.,"
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
.ne federa stated
edplans stt)eln
ORIGINAL BY:DUSTIN LANNING DATEi7.
JCA HOMES 07.12
OAK HILLS REVIEWED BY:JIM PARKS DATE17.07.13
26040 ACERO REV.# BY DATE DESCRIPTION
MISSION VIEJO.CA 92691
ti namasC6
0 SOLAR
DWG TITLE: PAGER: SCALE: SITE LOCATION: 4571 Broaeway Street
INDIVIDUAL 25479 KAMRAN CIRCLE BONtler,CO 80304
PLOT PLAN 3 NTS MENIFEE,CA 303.447.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UDDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
�I
UTILITY METER A i
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX.
(EXTERIOR-GARAGE)
SERVICE BY QUALIFIED PERSONNEL ONLY I�
CONTACT: SUNSTREET ENERGY GROUP ATE
1-877-SLR-POWR
r an
'tY
on the
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 10.53A
I PC.,NEC e90.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:DUSTIN LAMMING DAT197.07.12
JCA HOMES
OAK HILLS REVIEWED BY:JIM PARK I DATE:17.07.15
ERO
MISSION
N VIED REV.# BY DATE DESCRIPTION
MISSION VIEJO,CA 92691 to namaste
It. mue
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
INDIVIDUAL 4571uldw.DO
a8 Street
PLOT PLAN 4 NTS MENIF E,C AN CIRCLE Ba303."703M
PLACARDS MENIFEE.CA 303.447.03Do