PMT18-03554 City of Menifee Permit No.: PMT18-03554
29714 HAUN RD.
f MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE MENIFEE Date Issued: 07/19/2018
PERMIT
Site Address: 30429 VILLAGE KNOLL DR, MENIFEE, Parcel Number:
CA 92584 Construction Cost: $5,931.52
Existing Use: Proposed Use:
Description of ROOF MOUNTED SOLAR SYSTEM,7 PANELS,2.24 KW
Work: THE VILLAGE TR 37179
LOT 63
Owner Contractor
LENNAR HOMES OF CALIFORNIA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE,STE 302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
SAMANTHA MAZELLA License Number:728102
LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE,#302
CORONA,CA 92879
Fee Description Qtv Amount ISI
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Pennit Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION MENIFEE
DATE: 7/16/2018 PERMIT/PLAN CHECK NUMBER - Q
PLANNING CASE NUMBER
City O enl ee
TYPE: G COMMERCIAL C, RESIDENTIAL 0 MULTI-FAMILY O MOBILE HOME O FM N
SUBTYPE: O ADDITION C,ALTERATION 0 DEMOLITION O ELECTRICAL G INH 1 I�O,$
ONEW PLUMBING RE-ROOF NUMBER OFSQUARES ,,J)
DESCRIPTION OF WORK Solar Permit-,T.he Villacie Received
Plan Type: -1 3__1 KW: •aJ -I PCS: -1 Master Solar Permit#: PMT17-04339
PROJECT ADDRESS Vl114? 1;)Io l l ZIP 92584
ASSESSOR'S PARCEL NUMBER LOT (Q � TRACT 37179
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella lennar.com
APPLICANT NAME Lennar Homes of California Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S NAME Lennar Homes of California Inc. OWNER BUILDER? OYES ONO
BUSINESS NAME
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S STATE LIIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 5 , 3 I' 5 a So FT L SQ FT
APPLICANT'S SIGNATURE C� DATE I Its I
CITYSTAFF USE ONLY
DEPARTMENT DISTRIBUTION ACCEPTED BY: CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE MI'�
INVOICE TOTAL �0 GREEN — SMIP I
OWNER BUILDER VERIFIED OYES 0 NO DRIVERS LICENSE# NOTARIZED LETTER O YES NO
City of Menifee Building &Safety Department 129714 Haun Rd., Menifee, CA 92586 (951)672-6777
www.cityofmenifee.us
ENIF
a
i
SYSTEM INFORMATION City of Menifee BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY 1 MFR. MODEL Building p De t. ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.240 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
OD MULE 7 PCS.1 LG L6320EIK-AS(5207) JUL 17 2018 BUYER: _
INVERTER 7PCS. ENPHASE 106FLUS-72-ACM-US
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY NI ARRAY#2 ARRAY#3 ARRAY 04 a ce ive d BUYER:MOD OTY 7 NA NA NA
TILT 18° NA' NA. NA'
AZIMUTH I80° I NA' I NA' NA' DATE:
CITY OF MENIFEE
BUILDING AND SAFETY DEPARTMENT
PLAN APPROVAL
REVIEWED BY '7
1 ARRAY DA E
10'-2' 17'.7'-7'F FLASHING
theseplansshallnotbeconsh WiDbesperm@for,ors
7regpurioa
jiaoI9
any valationofany provisions ofthe federal,state or city
nd ordinsrleee. TW at of approved phm must be kept on he
completlon,
SOLADECK WIRE
TRANSITION BOX t
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER,a
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX
1
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 1937 ELEVATION B-LEFT
ORIENTATION 3 LOT#63
ORIGINAL BY-DAN BOWLING OATE:I8.07.10
MENIFEE TOWN CENTER LENNAR: REVIEWED BY:JIM PARKS DATE:18.07.11
CORONNA,A,C CAA
DA4 980 I 2 DRIVE,#302
92879 REV.# BY DATE DESCRIPTION
namastAW
via
SOIAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 6707 wbueh er Circle
INDIVIDUAL 30429 VILLAGE KNOLL DRIVE Suite 700
PLOT PLAN 1 1116'-V-O' MENIFEE,CA Boulder,CO 80MI
SYSTEM LAYOUT 1 303.447.0300
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 7 LG LG320EIK-AS(320W) ACPV MODULE W/INTEGRATED ENPHASE 106PLUS-72-ACM-US MICROINVERTER SOLAR
2 I RSTC/SOLADECK 0786.3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.Z4OV,30A SOLAR
4 1 ENPHASE 10 ENVOY ENV-IQAMI-240 PV DATA MONITOR,240V SOLAR
5 1 ENPHASE X-10-AMI-240-B AC COMBINER BOX SOLAR
6 1 ENPHASE TBD PV BREAKER,I X ZOA-2P, IX 5A-2P SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER,I X 2OA-2P,RATING MAY VARY SOLAR
8 1 TED TBD SERVICE PANEL.200A BUS BLDR.ELEC.
I TBD TBD UTILITY METER, IPH,120/24OV,200A BLDR,ELEC.
10 1 TBD TBD I GROUNDING ELECTRODE,UFER BLDR.ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT IPANEL
LOCATION MENIFEE,CA PANEL MFR. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40
TEMP.DELTA LOW(TOELTA) THIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD.MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALCS:
MOD.PART NUMBER AC MODULE SPEC LG320EIK-A5(320W) I.I7A X 7(MODS): 8.19A OF CURREW
MOD.POWER STC(P) AC MODULE SPEC WATTS IN) 320 8.19A a 1.26= I0.24A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIEAN WITH A 20A/2P 2 BPACE PV W FEED 8RE"ER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC I WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS (AC) 240/211-264
NOMINAL OUTPUT CURRENT QA0 AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HZ(AC) 60 159.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC LIL1741/IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AU 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD.OTY SC OTY 7
BRANCH CIRCUIT OUTPUT,IMAX8C (IAC'MOD.OTY fit) AMPS(AC) 8.19
AC MODLLE QUANTITY, TOTAL MOD.OTY T OTY 7
TOTAL SYSTEM OUTPUT IMAXTB (IAC'MOD.CITY T) AMPS(AC) 1 8.19
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY-TEMP.DERATE- FILL DERATE) REO'D DMAX)
2)TERMINALS(TERM): AMPACITY AT TERMINALS. VS. REO'D,(IMAX-1.25)
HEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REO'D OCD
TYPE DERATES DERATE DERATE (A) (A) USED(A)
A #12 CU THWN-2 COU 30 J6 1.0 LSO 8.19
TERM 25 25 10.24 20
B #10 Cu NM-B COU 40 .91 1.0 36.40 8.19
TERM 35 35 10.24 20
C #10 CU NM-S COU 40 .91 L0 36.40 8.19
TERM 35 35 110.24 20
CONDUCTOR SCHEDULE
KEY ICONOUCTORS I CU/AL I TYPE 1 LOCATION 1
TRADE °
p I-#12 ENPHASE 0 CABLE, I-06G,FREE AIR CU UL3003,DG CABLE ARRAY SOLAR
B 3-#10•,1-#10 EGC CU NM-B(ROMEX) INTERIOR SGLAR 9
C 3-#10.I-MID EGC CU NM-B(ROMEX) INTERIOR SOLAR
°NEUTRAL CAPPED AND NOT USED O
M
O � O
4 O3
O 5A72P O
O
O6 10A/
2
20A 2 4
N
G
G
A B C C — 10
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.240 NW
LOT#63
ORIGINAL BY:DAN BOWLING I DATE:18.07.
LENNAR. 10
MENIFEE TOWN CENTER 980 MQNTEDITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:18.07.11
DA4 CORONA,CA 92879 REV.# BY DATE DESCRIPTION
Gd nomasGe
•CbX
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707 WIn&ester CU91e
INDIVIDUAL 30429 VILLAGE KNOLL DRIVE Suite 700
PLOT PLAN 2 NTS MENIFEE,CA Boulder,CO 80301
ELECTRICAL 303.4470300
INSTALLATION NOTES:
SOLAR CONTRACTOR
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(y)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES M)BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING (COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
10 26 GAUGE INTERLOCKING FLASHING'9IDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 00 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY I$SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
S)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUOE UL1703, IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)OC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
II)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT�,
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
I9)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26,
ORIGINAL BY:DAN BOWLING DATEIS.07.10
MENIFEE TOWN CENTER q80 MON ECITO DRIVE,#302 ENNAR REVIEWED BY:JIM PARKS DATEIS.07.11
DA4 CORONA,CA 92879 REV.#. BY DATE DESCRIPTION �f
QO namasGC
wux
DWG TITLE: PAGE#.: SCALE: SITE LOCATION: 907 WinMeskr Circle
INDIVIDUAL 30429 VILLAGE KNOLL DRIVE SWIe no
PLOT PLAN 3 NTS MENIFEE,CA Boulder,CO 60301
NOTES 303."7.03DO
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR - GARAGE
UTILITY METER &
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 8. 19A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:DAN BOWLING DATEJB.07.10
MENIFEE TOWN CENTER LENNAR:980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:I8.07.11
DA4 CORONA,CA 92879 REV.# BY DATE DESCRIPTION .:
via namast6
oue
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707 Wi n.ster Circle
INDIVIDUAL 30429 VILLAGE NNOLL DRIVE Suite 700
PLOT PLAN 4 NTS MENIFEE.CA Boulder,C080301
PLACARDS 303"7.0300