PMT18-03553 City of Menifee Permit No.: PMT18-03553
29714 HAUN RD.
MENIFEE, CA 9258E Type: Residential Electrical
MENIFEE MENIFEE Date Issued: 0 711 912 01 8
PERMIT
Site Address: 30425 VILLAGE KNOLL DR, MENIFEE, Parcel Number:
CA 92584 Construction Cost: $5,931.52
Existing Use: Proposed Use:
Description of ROOF MOUNTED SOLAR SYSTEM,7 PANELS,2.24 KW
Work: THE VILLAGE TR 37179
LOT 62
Owner Contractor
LENNAR HOMES OF CALIFORNIA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE,STE 302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
SAMANTHA MAZELLA License Number:728102
LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE,#302
CORONA,CA 92879
Fee Description ON Amount 151
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work cemmenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permil_Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION MENIFEE
DATE: 7/16/2018 PERMIT/PLAN CHECK NUMBER
PLANNING CASE NUMBER
TYPE: 0 COMMERCIAL 0 RESIDENTIAL O MULTI-FAMILY 0 MOBILE HOME 0 q I/�G#AM re�PKM
SUBTYPE: 0 ADDITION O ALTERATION O DEMOLITION G ELECTRICAL ::i @T�NHAAFCALept.
O NEW O PLUMBING 0 RE-ROOF NUMBER OF SQUARES 4 -7 onjo
DESCRIPTION OF WORK Solar Permit-The Village Q/-aQ
Plan T e: —105 KW: a-a,/1 PCs: -7 Master Solar Permit#: P T�ce4 'vG
PROJECTADDRESS cDJS UMR!j7. VVIDII lbr. ZIP 92584
ASSESSOR'S PARCEL NUMBER LOT [09, TRACT 37179
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella lennar.com
APPLICANT NAME Lennar Homes of California Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S NAME Lennar Homes of California Inc. OWNER BUILDER? 0 YES ONO
BUSINESS NAME
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S STATEELIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 5 I T,3) 'S a SQ Fr L SQ FT (J
APPLICANT'S SIGNATURE DATE
0
CITYSTAFF USE ONLY
DEPARTMENT DISTRIBUTION ACCEPTED BY: ' 1� CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE I�
INVOICE TOTAL GREEN — SMIP
OWNER BUILDER VERIFIED O YES D NO DRIVERS LICENSE# NOTARIZED LETTER 0 YES C' NO
City of Menifee Building &Safety Department 129714 Haun Rd., Menifee, CA 92586 (951)672-6777
www.cityofmenifee.us
ENIFE
SYSTEM INFORMATION City of Menifee BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR, I MODEL Building Dept. ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.240 KW I I LOCATIONS INDICATED BY THE ILLUSTRATION.
tODULE
NVERTER 7PCS ENPHASE 06PLUS-72-ACM-US' JUL 1 7 2018
BUYER:—---_-----.------------.------------------
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION Received
ARRAY#I ARRAY#2 ARRAY 03 ARRAY#4
MOD OTY 7 NA NA NA BUYER:
TILT I IB° I NA' NA° NA'
AZIMUTH 1 270° 1 NA' NA' NA'
DATE:
CITY OF MENIFEE
BUILDING AND SAFETY DEPARTMENT
PLAN APPROVAL
REVIEWED BY
D WE
41 3 5-6 °Appro Val of these plans shall not be construed lDbea permit for,o an
appro at of,any Violation
Ofany Millions oflhefedaral,state orci
regu#a onsandordinances. This set of approved plans mustbekept Itthe
jobsitc until Completion.
--------------------------------------
« SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER B
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
<Y' AC COMBINER BOX
1
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 1705 ELEVATION C-RIGHT
ORIENTATION 3 LOT#62
LENNAR: ORIGINAL BY:DAN BOWLING DATE:18.07.10
MENIFEE TOWN CENTER REVIEWED BY:JIM PARKS DATEAS.07.11
CORONNA,A,CA
DA4 980 C I DRIVE.#302
A 92879 REV.# BY DATE DESCRIPTION
IV H ama."€
SOUR
DWG TITLE: [PAGET*: SCALE: SITE LOCATION: 6707 Winchester Circle
INDIVIDUAL 30425 VILLAGE KNOLL DRIVE SWI 700PLOT PLAN -P-0' MENIFEE.CA BoulSv,CO 80301
SYSTEM LAYOUT =.447.0300
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 7 LG LG320EIK-A5(32OW) ACPV MODULE W/INTEGRATED ENPHASE IQ6PLUS-72-ACM-US MICROINVERTER SOLAR
2 1 RSTC /SOLADECK 0766-3RS PV ROOF JUNCTION BOX,NEMA 3R SOLAR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V.30A SOLAR
4 1 ENPHASE 10 ENVOY ENV-IOAMI-240 PV DATA MONITOR,240V SOLAR
5 1 ENPHASE X-10-AMI-240-8 AC COMBINER BOX SOLAR
6 1 ENPHASE TBD PV BREAKER,I X 2OA-2P, I X 5A-ZP SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER,I X 20A-ZP,RATING MAY VARY SOLAR
8 1 TED TBO SERVICE PANEL,20OA BUS ELOR.ELEC.
9 1 TBD TBD UTILITY METER.IPH,120/24OV,200A SLOR. ELEC.
10 1 TBD I TBD GROUNDING ELECTRODE,UFER ELDR. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL MFR. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% 'C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN 'C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40
TEMP.DELTA LOW(TOELTA) TMIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD. PART NUMBER AC MODULE SPEC LG320EIK-A5(32OW) I.17A x)(MODS)• 8.19A OF CL NT
MOD. POWER STC(P) AC MODULE SPEC WATTS(UC) 320 S.19A x 1.11= 10.2AA
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TI'E9 WITM A 20A/YP 2 SPACE w ePMFEED BREAXER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MOOLE SPEC I WATTS(AC) 250
NOMINAL VOLTAGE/RANGE AC MODULE SPEC I VOLTS(AC) 240/211-264
NOMINAL OUTPUT CU RENT OAQ AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HZ(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741/IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD, OTY SC OTY 7
BRANCH CIRCUIT OUTPUT.IMAXBC (IAC'MOO.QTY SO AMPS(AC) 8.19
AC MODULE QUANTITY,TOTAL MOD. OTY T CITY 7
TOTAL SYSTEM OUTPUT IMAXTS (IAC°MOD. OTY T) AMPS(AC) 1 F19
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE COU): I(AMPACITY- TEMP.DERATE• FILL DERATE)vs.REO'D(TMAX)
2)TERMINALS(TERM): I AMPACITY AT TERMINALS. vs.REG'D.(TMAX•1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REO'D OCD
TYPE DERATES DERATE DERATE (A) (A) USED(A)
A V1 CCU THWN-2 COO 30 .76 1.0 22,80 8.19
TERM 25 25 10.24 20
8 #10 CU NM-B COU 40 .91 TO 36.40 8.19
TERM 35 35 10.24 20
C 010 CU NM-B COU 40 .91 1.0 36.40 8.19
TERM 35 35 10.24 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE
A 1-#12 ENPHASE 0 CABLE,1-#6G,FREE AIR CU UL3003,DG CABLE ARRAY SOLAR
B 1 3-#10-.I-#10 EGG I CU NMAI(ROMEX) INTERIOR ISOLAR icao
C 3-010,I-#10 EGO CU NM-B(ROMEX) INTERIOR SOLAR
'NEUTRAL CAPPED AND NOT USED 4A -T_
A B
ROOF I EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.240KW
LOT#62
ORIGINAL BY:DAN BOWLING IDATEAB.
LENNAR: 07.10
MENIFEE TOWN CENTER 980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:18.07.11
DA4 CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namasCe
SOLAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 6707 Wmcheeter Circle
INDIVIDUAL 30425 VILLAGE KNOLL DRIVE SVRe 700
PLOT PLAN 2 NTS MENIFEE,CA Boulder,GO 90301
ELECTRICAL 301. 17.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
1)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 40'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS.IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(JI)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 31.
IU 26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION.IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT W)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF SAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIROSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION,
ELECTRICAL NOTES:
GENERAL-
0 ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE U1.1703,IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)OC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS. WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS,
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING /PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING, BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT k.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED*PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT;WIRING/RACEWAYS SMALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:DAN BOWLING DATEfB.OJ.IO
MENIFEE TOWN CENTER 980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS DATEf8.07!1,
DA4 CORONA.CA 92879 REV.# BY DATE DESCRIPTION
S?namasto§
aoue
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707 WlnnnW Circle
INDIVIDUAL 30425 VILLAGE KNOLL DRIVE SWIe 700
PLOT PLAN 3 NTS MENIFEE,CA Bouldw,CO SM01
NOTES 303.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
®EXTERIOR - GARAGE
UTILITY METER d
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 8. 19A
I PC., NEC 690.54 1 PC., NEC 690,12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
LENNAR: ORIGINAL BY:DAN BOWLING DATE18.07.10
MENIFEE TOWN CENTER 980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS DATE18.07.11
DA4 CORONA,CA 92879 REV.,". BY DATE DESCRIPTION •1 }
Qti namaste
f OIA[
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707 Wnd ter Clyde
INDIVIDUAL 30425 VILLAGE KNOLL DRIVE Suite 700
PLOT PLAN 4 NITS MENIFEE,CA Boulder,CO 80301
PLACARDS 303.447.0300