PMT18-03057 City of Menifee Permit No.: PMT18-03057
29714 HAUN RD.
MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE MENIFEE Date Issued: 08/07/2018
PERMIT
Site Address: 28564 WEDELIA ST, MENIFEE, CA 92584 Parcel Number: 333-650-008
Construction Cost: $5,613.76
Existing Use: Proposed Use:
Description of SOLAR TR 31582-HERITAGE HEIGHTS
Work: 8 MODULES,8 INVERTERS,2.56 KVV
LOT 17 PLAN 2131
Owner Contractor
LENNAR HOMES OF CALIFORNIA, INC LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE SUITE 302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant License Number:728102
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Phone:9518173539
Fee Description QtV Amount(Sl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
spectfications or from preventing builiding operations being carded on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg Permit Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION EE
DATE: 6/12/2018 PERMIT/PLAN CHECK NUMBER V I (
PLANNING CASE NUMBER
TYPE: O COMMERCIAL O RESIDENTIAL O MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: O ADDITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
O NEW O PLUMBING O RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Heritage Heights Master Permit#-PMT17-00129
Kw: PCS: Plan: 03
PROJECT ADDRESS &y l,k-r—&ir &I" ZIP 92584
ASSESSOR'S PARCEL NUMBER -533- y5c 'c:)o8 LOT (-7 TRACT 31582
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? O YES ONO
BUSINESS NAME
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL. samantha.mazella@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 5613.76 SQ FT L SQ FT
APPLICANT'S SIGNATURE DATE
CITYSTAFF USE ONLY
DEPARTMENT DISTRIBUTION ACCEPTED BY' CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE
INVOICETOTAL TO_� GREEN SMIP
OWNER BUILDER VERIFIED OYES O NO DRIVERS LICENSE t1 NOTARIZED LETTER O YES O NO
City of Menifee Building &Safety Department 129714 Haun Rd., Menifee, CA 92586 (951)672-6777
www.cityofinen ifee.us
NI
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR.MODULES TO BE INSTALLED
ITEM OTY 1 MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.560 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE I PCS.j LG I LG320EIK-A5(32OW)
INVERTER BPCS. ENPHASE IO6PLUS-72-ACM-US BUYER:
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3 ARRAY#4
MOD OTY 8 NA NA NA BUYER:
TILT I8° NA' I NA- I NA°
AZIMUTH IBO• NA' NA' NA DATE:
OEM
Q a
� '2
Lu
.12
od
o
W -
a
LL C T yr N N
W J R N r
Q N
LL Q / O
C
W Q f1� 0 d v ♦�
(� a LLJ
LL. z A
O SOLAOECX WIRE
z A TRANSITION BOX
A O
J > o > (UNDER ARRAY)
q r
V m Q,° �[ a PV AC DISCONNECT
j EXTERIOR-GARAGE
UTILITY METER A
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
dp AC COMBINER BOX
�4T
NOTE:.DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2131 ELEVATION A-R ENH Z
ORIENTATION 2 LOT#17
ORIGINAL BY:ARTHUR HICKS DATE:I8.OL.24
HERITAGE HEIGHTS LENNAR: 92879 REVIEWED BY:DUSTIN LANNING DATE:I8.04.24
CORONA,LA
980 MONTEC 21 DRIVE.#302 REV.# BY DATE I DESCRIPTION
namast8
DWG TITLE: PAGE#: SCALE: SITE LOCATION: soul
INDIVIDUAL 28564 WEDELIA STREET 8707 VSuite700 Circle
PLOT PLAN I 1116"= I'-0' der, O8
SYSTEM LAYOUT MENIFEE.LA Boulder,C080307
303.447.0300
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY I MANUFACTURER MODEL NOTES JR.
ADE
I B LG LG3ZOEIK-A5(32OW) ACPV MODULE W/ INTEGRATED ENPHASE 106PLUS-72-ACM-US MICROINVERTER AR
2 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R AR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT, NEMA 3R,240V.30A AR
4 1 ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR.240V AR
5 1 ENPHASE X-IQ-AMI-240-B AC COMBINER BOX AR
6 1 ENPHASE TBD PV BREAKER. I X 2OA-ZP.1 X 5A-2P AR
7 1 CUTLER-HAMMER TBD PV BREAKER. I X 20A-2P.RATING MAY VARY AR
B I TBD. TBD SERVICE PANEL,ZOOA BUS ELEC.
9 1 TBD TBD UTILITY METER, IPH, 120/24OV,200A R. ELEC.
10 1 TBD TBD GROUNDING ELECTRODE.UFER R. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL MFR. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% •C 37 BUS RATING AMPS 200
TEMP.AMBIENT LOW(TMiN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP.MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TEELTA) THIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD. PART NUMBER AL MODULE SPEC LG320EIK-A5(320W) I.VA X 8(1013S)= 9.36A OF CURRENT
MOD. POWER STC(P) AC MODULE SPEC WATTS(DC) 320 9.36A X 1.25= IIJDA
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A 20Al2P 2 SPACE PV BACKFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AU 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HZ(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AL MODULE SPEC UL1741/IEEE1547
GROUNDING. AL MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD.OTY BC QTY 8
BRANCH CIRCUIT OUTPUT,IMAX8C (IAC°MOD.QTY 80 AMPS(AC) 9.36
AC MODULE QUANTITY,TOTAL MOD. CITY T QTY B
TOTAL SYSTEM OUTPUT IMAXTS (IAC•MOD.QTY T) AMPS(AC) 9.36
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY°TEMP.DEBATE ° FILL DERATE)_VG. REQ'D([MAX)
2)TERMINALS(TERM); AMPACITY AT TERMINALS. VS. REQ'D,(IMAX° 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP, IFILLRESULTREO'D OCD
TYPE DERATES DERATE (A) USED(A)
A #12 CU THWN-2 COU 30 .76 9.3fiTERM 25 1176 2D
NM-B COU 40 .91 9.36
TERM 35 11.7D 20
C #10 CU NM-B COU LO .91 9.36
TERM 35 11.70 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE
A LOI ENPHASE 0 CABLE,I-#6G,FREE AIR CU UL3003,DG CABLE ARRAY SOLAR
B 3-#10•,1-#10 EGC CU NM-B(ROMEX7 INTERIOR I SOLAR 9
C 34I0.I-#ID EGL I CU I NM-B(ROMEX) I INTERIOR I SOLAR _
-NEUTRAL CAPPED AND NOT USED M
B
0
O
O 52W2
'
1414141414141FO �O
IN
G G G�
A B C C IO
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.56OKW
LOT# 17
ORIGINAL BY:ARTHUR HICKS DATE:IB.04.24
HERITAGE HEIGHTS LENNAR: REVIEWED BY:DUSTIN LANNING DATE:18.04.24
CO NA.CA I92 DRIVE.#302 REV.# BY DATE DESCRIPTION
CORONA,CA 92879
namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707VAnchesler Cirde
INDIVIDUAL 28564 WEDELIA STREET Suite TOO
PLOT PLAN 2 NTS MENIFEE.CA Boulder,GO 80301
ELECTRICAL 303.447.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
1)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 40'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURERS.INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION,
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH Q')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(29 BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
B)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SMALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
ID 26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TD BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 00 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS,
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TD BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646,IEC61730.
B)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
ID MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SMALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMANLIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,DR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SMALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 69D AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t..
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:ARTHUR HICKS DATEIB.04.2L
HERITAGE HEIGHTS LENNAR: REVIEWED BY:DUSTIN CANNING I DATE18.04.24
980 MONTECITO DRIVE.#302
CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namasbL
tone
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707 Winchester Circle
INDIVIDUAL 28564 WEDELIA STREET Suite 700
PLOT PLAN 3 NTS MENIFEE,CA Boulder,CO 80301
NOTES 303.447.13MO
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECA WIRE
TRFNSITIDN BOX
(DWER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY PETER 0
MIN SERVICE PANEL
(VERIFIED BY BIRLDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 9.36A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:ARTHUR HICKS I DATE18.04.24
HERITAGE HEIGHTS LENNAR: REVIEWED BY:DUSTIN ANNING I DATE18.04.24
980 CA 92879 I DRIVE.#302
CORONA,NA.CA REV.# BY DATE I DESCRIPTION
namasbe
DWG TITLE: PAGE#: SCALE: �D�A•
SITE LOCATION: 8707 Winchester 700 Circe
INDIVIDUAL MENIF WEDELIA STREET der, O8
PLOT PLAN 4 NTS MENIFEE,CA BODIGer,C080301
PLACARDS 303.447.0300