PMT18-03053 City of Menifee Permit No.: PMT18-03053
29714 HAUN RD. Type: Residential Electrical
MENIFEE,CA 92586
MENIFEE MENIFEE Date Issued: 0 710 912 01 8
PERMIT
Site Address: 28539 WEDELIA ST, MENIFEE,CA 92584 Parcel Number: 333-651-014
Construction Cost: $5,613.76
Existing Use: Proposed Use:
Description of SOLAR TR 31582-HERITAGE HEIGHTS
Work: 7 MODULES,7 INVERTERS, 2.24 KW
LOT 92 PLAN 1874
Owner Contractor
LENNAR HOMES OF CALIFORNIA, INC LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE SUITE 302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant License Number:728102
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Phone:9518173539
Fee Description Qtv Amount I$1
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Pernit_Template.rpt Page 1 of 1
BUILDING &SAFETY PERMIT/PLAN CHECK APPLICATION , MENIFEE
. i Milt',
DATE: 6/12/2018 PERMIT/PLAN CHECK NUMBER I`�VI I ����✓/
PLANNING CASE NUMBER
TYPE: O COMMERCIAL O RESIDENTIAL O MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: O ADDITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
O NEW O PLUMBING O RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Heritage Heights Master Permit#-PMT17-00129
Kw: 0005361
), Aq q 1 , 1PCs: `I J Plan: l -7
41
PROJECTADDRESS 0053j..,l�7JAAj� L,L $' /. ZIP 92584
ASSESSOR'S PARCEL NUMBER '✓ -J ✓ 'If V) I - O 14 LOT TRACT 31582
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella lennar.com
APPLICANT NAME Lennar Homes of California Inc.
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S NAME Lennar Homes of California Inc. OWNER BUILDER? O YES ONO
BUSINESS NAME
ADDRESS 980 Montecito Dr. Ste 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 6613.76 SQ FT L SQ FT APPLICANT'S SIGNATURE DATE V I1 a I I Bc
CITY STAFF USE ONLY
DEPARTMENT DISTRIBUTION ACCEPTED B CnYOFMENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE
INVOICETOTAL oC'1�,�1J�_ GREEN SMIP
OWNER BUILDER VERIFIED O YES O NO DRIVERS LICENSE# NOTARIZED LETTER O YES O NO
City of Menifee Building &Safety Department 129714 Haun Rd., Menifee, CA 92586 (951)672-6777
www.c i tyofm en ifee.us
I .
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM 1 QTY 1 MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.240 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 1 7 PCSJ LG LG320EIK-A5(32OW) BUYER:
INVERTER 1 7 PCS.1 ENPHASE IQ6PLUS-72-ACM-US
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 1 ARRAY#3 1 ARRAY#4
MOD OTY 7 NA I NA I NA BUYER:
TILT 1 18` 1 NA' NA' N4° DATE: --
AZIMUTH 180° NA- NA' NA°
cmz
5'-6- 3'
P
UP
SOLADEC
a �3
- y
TRANSITION
WIRE Z ys
TRANSITION BOX W(UNDER ARRAY)
CAD
PV AC DISCONNECT '
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL-1-4C s!S
(VERIFIED BY BUILDER) qq 4ici
�uj[
AC COMBINER BOX a LL.
Q m 6 C
777bbb
T S
C
LU Ix
CL
N Cam}
O G C
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 1874 ELEVATION B ENH-LEFT Z
ORIENTATION 4 LOT#92
LENNAR: ORIGINAL BY:CHRISTINE MARTINI DATE:IB.04.19
HERITAGE HEIGHTS REVIEWED BY:ANGLEA BURKE DATE:IB.04.20
CORONA,CA
980 NA.CA 42879 ITO DRIVE,#302 REV.# BY DATE DESCRIPTION
namast6
DWG TITLE: PAGE#: SCALE: SITE LOCATION: sous
INDIVIDUAL 28539 WEDELIA STREET 4571 Broadway Street
Boulder,CO W304
PLOT PLAN 1 I/Ifi'=I'-0' MENIFEE,CA 303.447,0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY I MANUFACTURER MODEL NOTES TRADE
1 7 LG LG320EIK-A5(320W) ACPV MODULE W/INTEGRATED ENPHASE 106PLUS-72-ACM-US MICROINVERTER SOLAR
2 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R. SOLAR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V,30A SOLAR
4 1 ENPHASE IQ ENVOY ENV-IGAMI-240 PV DATA MONITOR,240V SOLAR
5 I ENPHASE X-IQ-AMI-240-8 AL COMBINER BOX SOLAR
6 1 ENPHASE TBD PV BREAKER,I X 20A-2P.I X 5A-2P SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER.I X 20A-2P,RATING MAY VARY SOLAR
8 1 TBD TBD SERVICE PANEL.20DA BUS BLDR. ELEC.
9 1 TBD TBD UTILITY METER,IPH,1201240V,200A BLDR. ELEC.
10 1 TBD TBD GROUNDING ELECTRODE,LIFER I BLDR. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE.CA PANEL MFR. CUTLER-HAMMER
TEMP.AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 BUS RATING AMPS 2D0
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 2D0
TEMP.MODULE TEST(TTEST) MODULE SPEC 'C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TOELTA) THIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOO.PART NUMBER AC MODULE SPEC LG320EIK-A5(32OW) I.17A x 7(MODS)- 6.19A OF CURRENT
MOO. POWER STC(P) AC MODULE SPEC WATTS(DC) 320 B.19A x 1.25= 10.24A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A 20A/2P 2 SPACE PV BACBFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC IF) AC MODULE SPEC WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC Hz(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741/ IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS.(AC) 20
AC MODULE QUANTITY.MAX PER BRANCH CIRCUIT MOD.QTY Bc QTY 7
BRANCH CIRCUIT OUTPUT,IMAXBC (IAC°MOD.QTY BW AMPS(AC) 8.19
AC MODULE QUANTITY,TOTAL MOD.QTY T QTY 7
TOTAL SYSTEM OUTPUT IMAXTS (IACMOD.QTY T) AMPS(AC) 1 8.19
CDNDUCTOR SIZING CALCULATIONS
O CONDITION OF USE(COU): I(AMPACITY-TEMP.DERATE° FILL DERATE)vs.REQ'D(IMAX)
2)TERMINALS(TERM): I AMPACITY AT TERMINALS. VS. REQ'D,(IMAX• 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. NFILLRESULT REO'D OCD
TYPE DERATES DERATE (A) (A) USED(A)
#12 CU THWN-2 COU 30 .76 22.80 8.19
TERM 25 25 10.24 20
NM-B COU 40 .91 36.40 B.19
TERM 35 35 10.24 20
*10 LU NM-BCOU 40 .91 36.40 8.19
TERM 35 35 10.24 20
CONDUCTOR SCHEDULE
KEY I CONDUCTORS CU/AL TYPE LOCATION TRADE
A -#12 ENPHASE O CABLE, 1-96G.FREE AIR I CU UL30D3,DG CABLE I ARRAY I SOLAR
B 1 3-#10°.I-#10 EGC I CU NM-B(ROMEX) I INTERIOR I SOLAR 9
C 1 3-#10,1-#10 EGL I CU I NM-B(ROMEX) I INTERIOR I SOLAR _
'NEUTRAL CAPPED AND NOT USED M
O 8
5
4 O3
O w2P O
I O
O 6 m
z0az
r- - — R
G G
A B C C TO
I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.240KW
LOT#92
ORIGINAL BY:CHRISTINE MARTINI I DATE:IB.04.19
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ANGLEA BURKE DATE:18.04.20
CORONA.
NA.CA I92 DRIVE.#302
CORONA,LA 92879 REV.# BY DATE I DESCRIPTION
namasb6
DWG TITLE: PAGE#: SCALE: su�A•
INDIVIDUAL SITE LOCATION: 4571 Broadway Street
PLOT PLAN 2 NTS 28539 WEDELIA STREET Boulder.CO SON
ELECTRICAL MENIFEE.CA 303.447.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48-O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH It')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES In BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY,
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
II)Z6 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION, IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(I')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF SAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NDN-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED.ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE,
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED.TO PV ARRAY FOOTPRINT W/ ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS. WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE.'OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:CHRISTINE MARTINI DATE18.04.19
HERITAGE HEIGHTS 980 MOLENNAR: REVIEWED BY:ANGLEA BURKE DATE18.04.20
9B0 NA,CA I92 DRIVE. #302
CORONA,LA 92879 REV.# BY DATE DESCRIPTION •,
namasGe
DWG TITLE: PAGE#: SCALE: •oi�t
SITE LOCATION: 4571 BroaCway Street
INDIVIDUAL 28539 WEDELIA STREET Boulder,CO B0304
PL07 PLAN 3 NTS MENIFEE.CA 303.467.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOR
(UNDER ARRAY)
PV 4C DISCONNECT
EXTERIOR-GARAGE
UTILITY METER B
MAIN SERVICE PANEL
(VERIFIEO BY BUILDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 8. 19A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:CHRISTINE MARTINI DATEl0.04.19
HERITAGE HEIGHTS LENNAR:
900 MONTECITO DRIVE,#302 REVIEWED BY:ANGLEA BURKE DATH0.04.20
CORONA,CA 92079 REV.# BY DATE I DESCRIPTION
Oniamasr,6
DWG TITLE: PAGE#: SCALE: SOLAR
SITE LOCATION:
INDIVIDUAL 20539 WEDELIA STREET 457ulder, O8ay street
PLOT PLAN 4 NTS Boulder,C080304
PLACARDS MENIFEE,CA 303.447.0300