PMT18-01948 City of Menifee Permit No.: PMT18-01948
29714 HAUN RD. T Residential Electrical
�J-ICa CELA-�. MENIFEE,CA 92586 yam'
MENIFEE Date Issued:
05/01/2018
PERMIT
Site Address: 24546 HIDDEN HILLS DR, MENIFEE, CA Parcel Number: 358-661-010
92584 Construction Cost: $7,626.00
Existing Use: Proposed Use:
Description of INSTALL ROOF MOUNTED SOLAR, 9 PANELS,9 MICROINVERTERS,2.880 KW
Work: DAKOTA TR 32025
LOT 35
Owner Contractor
WOODSIDE HOMES SUNSTREET ENERGY GROUP LLC
11870 PIERCE STREET, STE 250 760 NORTHWEST 107 AVENUE
RIVERSIDE, CA 92505 MIAMI, FL 33172
Applicant Phone: 3054854110
KRISTEN MURRAY License Number. 1001133
SUNSTREET ENERGY GROUP LLC
760 NORTHWEST 107 AVENUE
MIAMI,CA 33172
Fee Description Qtv Amount i$1
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permk_Template.rpt Page 1 of 1
& SAFETY PERM IT/PLAN CHECK APPLICATION
,_ Vlenifee too- kqLA%
DATE 04/19/2018 PERMIT/PLAN CHECK NUMBER PWfft -02Y05
TYPE: []COMMERCIAL ❑✓ RESIDENTIAL MULTI-FAMILY ❑MOBILE HQ []SIGN
SUBTYPE: ❑ADDITION []ALTERATION ❑DEMOLITION QELECTRKBII Ifl BRANICAL
[-]NEW [-]PLUMBING ❑RE-ROOF-NUMBEROFSQUARES
DESCRIPTION OF WORK INSTALL 2.880kW ROOF MOUNTED PV SYSTEM APR
Received
PROJECTADDRESS 24546 HIDDEN HILLS DRIVE,MENIFEE, CA
ASSESSOR'S PARCEL NUMBER 358-661-010 LOT 35 TRACT 32025
PROPERTY OWNER'S NAME WOODSIDE HOMES
ADDRESS 11870 PIERCE STREET SUITE 250
PHONE (949)939-9564 EMAIL MIKEJ@WOODSIDEHOMES.COM
APPLICANT NAME KRISTEN MURRAY
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S NAME SUNSTREET ENERGY GROUP LLC OWNER BUILDER? ❑YES ✓❑NO
BUSINESS NAME SUNSTREET ENERGY GROUP LLC
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S STATE LIC NUMBER 1001133 LICENSE CLASSIFICATION B
VALUATION $ $7,626.00 SQ FT L SO FT
APPLICANT'S SIGNATURE I t'q'tM DATE 04/19/2018
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP I
AMOUNT .IQO OICE PAID AMOUNT (00
O CASH OCHECKq OCREDIT CARD VISA/MC
PLAN CHECK FEES PAIDAMOUNT 0CASH 0CHECK# 0 CREDIT CARD VISA/MC
LOWNERBUILDERVERIIFIED 0 YES O NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM QTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.88OKW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 9PCS. LG I LG320EIK-A5(3207 BUYER:
INVERTER 9 PCS.1 ENPHASE I 106PLUS-72-ACM-US
ROOF TYPE I CONIC.TILE DATE:
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3 ARRAY#4
Mot)QTY 9 NA NA NA BUYER:
TILT 18° 1 NA' I NA' NA• DATE:
AZIMUTH I80° 1 NA• NA' NA°
City of Menifee
Building Dept.
APR 2 4 20%
Received OC
12'-7y' 16'-9'ARRAY
NEMA 3R JUNCTION BOX
0'OUTSIDE ARRAY)
PV AC DISCONNECT CITY®F ME
EXTERIOR-GARAGE
` BUILDIN A
UTILITY METER 8
MAIN SERVICE PANEL
I (VERIFIED BY BUILDER) PLAN A PR
(_
{j` ' AC COMBINER BOX
REVIEWED E
'Approval of th se pli
approval of,an viola
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF re9vf iOns and (dine
�DI,vV ntil co pletil
PLAN 4 ELEVATION B-RIGHT
ORIENTATION I LOT#35
DAKOTA AT WOODSIDE HOMES: ORIGINAL BY:DAN BOWLING DATE:18.04.I7
11870 PIERCE STREET,SUITE#100 REVIEWED BY:T.HAMMERBACHER I DATE:18.04.18
AUDIE MURPHY RIVERSIDE,CA 92505 REV.# BY I DATE I DESCRIPTION
• - namaSGB
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6707 Wndwster Circle
HE 24546 HIDDEN HILLS DRIVE Suite 700
PLOT PLAN I I/16'=V-0- MENIFEE.CA 30 Boulder,GO B01
SYSTEM LAYOUT 303.447.D300
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY I MANUFACTURER MODEL NOTES TRADE
1 9 LG LG320EIK-A5(320W) ACPV MODULE W/INTEGRATED ENPRASE 106PLUS-72-ACM-US MICROINVERTER SOLAR
2 1 TBD TBD PV ROOF JUNCTION BOX.NEMA 3R SOLAR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V,30A SOLAR
4 1 ENPHASE 10 ENVOY ENV-IQAMI-240 PV DATA MONITOR,240V SOLAR
5 1 ENPHASE X-IG-AMI-240-B AC COMBINER BOX SOLAR
6 1 ENPHASE TBD PV BREAKER. I X 2OA-2P,I X 5A-2P SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER, I X 2OA-2P,RATING MAY VARY SOLAR
8 1 TBD TBD SERVICE PANEL,200A BUS BLDR.ELEC.
9 1 TBD TBD UTILITY METER. IPH,120/24OV,200A BLDR.ELEC.
10 I TBD I TBD I GROUNDING ELECTRODE,UFER I BLDR.ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT I PANEL
LOCATION MENIFEE,CA PANEL MFR. CUTLER-HAMMER
TEMP.AMBIENT HIGH(TMAx) ASHRAE 2% •C 38 BUS RATING AMPS 200
TEMP.AMBIENT LOW(THIN) ASHRAE EXTR.MIN •C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC •C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TELLTA) THIN-TTEST 'C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALCS:
MOD.PART NUMBER AC MODULE SPEC LG320EIK-AS(32OW) I.DA x 9(MODS)= 10.53A OF CURRENT
MOD. POWER STC(P) AC MODULE SPEC WATTS(OC) 320 10.53A K 1.25= 13.16A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-1N WITH A 20A/2P 2 SPACE PV MCKFEEU BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC I WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(LAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HZ(AC) 60 r 59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741 /IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER 13RANCH CIRCUIT MOD. CITY BC CITY 9
BRANCH CIRCUIT OUTPUT. IMAXBC (IAC•MOD.QTY et) AMPS(AC) 10.53
AC MODULE QUANTITY, TOTAL MOD. CITY T CITY 9
TOTAL SYSTEM OUTPUT IMAXTS (IAC'MOD.QTY T) AMPS(AC) 10.53
CONDUCTOR SIZING CALCULATIONS
D CONDITION OF USE(COU): I (AMPACITY'TEMP.DERATE ' FILL DERATE)vs.REO'D(IMAX)
2)TERMINALS(TERM): AMPACITY AT TERMINALS.vs. REO'O.(IMAX' 1.25)
KEY SIZE CU/AL INSULATION CALL. AMPACITY W/0 TEMP. FILL RESULT REO'D OCD
TYPE OERATES DERATE DERATE (A) (A) USED(A)
A #12 CU THWN-2 LOU 30 0.76 1.0 22.80 10.53
TERM 25 25 13.16 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 10.53
TERM 35 35 13.16 20
C #10 CU NM-S COU 40 0.91 1.0 36.40 10.53
TERM 35 35 13.16 20
CONDUCTOR SCHEDULE FEE
KEY CONDUCTORS 1 CU/AL 1 TYPE LOCATION 1 TRADE
A I-#12 ENPHASE Q CABLE,1-#6G,FREE AIR CU UL30U,DG CABLE ARRAY SOLAR T
B3-#10',I-#10 EGC LU NM-B(ROMEX) INTERIOR SOLAR AFE U
C 3-#10,1-#10 EGC CU NM-B(ROMEX) INTERIOR SOLAR
'NEUTRAL CAPPED AND NOT USED
4SA/2POO6
z
20A/2T- 111
_ N
G G G Sall not 6e cc nstru(
A B c Lof any provisi Ins of
10 s, This set of pprov
i
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.88o KW
LOT#35
ORIGINAL BY:DAN BOWLING DATE:18.04.17
WOODSIDE HOMES:
DAKOTA AT REVIEWED BY:T.HAMMERBACHER I DATE:18.04.18
11870 PIERCE STREET,SUITE#100
AUDIE MURPHY RIVERSIDE.CA 92505 REV.# BY DATE DESCRIPTION •�
namasrd
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 6707 WiRe Circle
24546 HIDDEN HILLS DRIVE de ur700
PLOT PLAN 2 NTS O8
MENIFEE.CA Boulder,C0301
ELECTRICAL
303.447.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW.TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)WIRE TRANSITION JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)THE RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION MANUAL,
APRIL 2016 EDITION
6)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(}')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(29 BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
7)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
W PV PANEL HAS BEEN TESTED BASED ON ILL 1705.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)BASE ATTACHMENT AND FLASHING TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
ID ALL ROOF ATTACHMENTS TO BE FLASHED AND SEALED PER MANUFACTURER'S SPECIFICATIONS.
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646.IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
II)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES. CART EN
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
)bea pe 70tor
federal, itatem
plans tbekl
ORIGINAL BY:DAN BOWLING DATEI8.04.17
DAKOTA AT WOODSIDE HOMES: REVIEWED BY:T.HAMMERBACHER DATEIS.04.18
11870 PIERCE STREET,SUITE#100
AUDIE MURPHY RIVERSIDE.CA 92505 REV.# BY DATE DESCRIPTION
t2amI,
SOIAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 6707 Wince 700 Cirda
PLOT PLAN 3 TUTS 24546 HIDDEN HILLS DRIVE der.CO
NOTES MENIFEE,CA Boulder. O Bo301
303.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
NEMA 3R JUNCTION BOX
0' OUTSIDE ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER B
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE — AC SPECS ATE
AC OPERATING VOLTAGE: 240 V PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING CURRENT: 10.53A WITH RAPID SHUTDOWN an
Y
OnUT
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:DAN BOWLING DATEi6.04.17
DAKOTA AT WOODSIDE HOMES: REVIEWED SY:T.HAMMERBACHER I DATEi8.04.18
11870 PIERCE STREET.SUITE*100
AUDIE MURPHY RIVERSIDE,CA 92505 REV.R BY DATE I DESCRIPTION
namaste
iOMP
DWG TITLE: PAGE S: I SCALE: SITE LOCATION:
INDIVIDt1AL 6707 W uke 7aer Circe
PLOT PLAN 4 NTS 24546 E.CA HILLS DRIVE Boulder,
CO
MENIFEE.CA Bo3MA O 80307
PLACARDS 303.447.0300