PMT18-01942 City of Menifee Permit No.: PMT18-01942
29714 HAUN RD.
'f-,CCEL/-> MENIFEE, CA 92586 Type: Residential Electrical
W.- MENIFEE Date Issued: 0 510112 01 8
PERMIT
Site Address: 24582 HIDDEN HILLS DR, MENIFEE,CA Parcel Number: 358-661-007
92584 Construction Cost: $6,779,00
Existing Use: Proposed Use:
Description of INSTALL ROOF MOUNTED SOLAR, 8 PANELS,8 MICROINVERTERS,2.560 KW
Work: DAKOTA TR 32025
LOT 32
Owner Contractor
WOODSIDE HOMES SUNSTREET ENERGY GROUP LLC
11870 PIERCE STREET,STE 250 760 NORTHWEST 107 AVENUE
RIVERSIDE,CA 92505 MIAMI, FL 33172
Applicant Phone: 3054854110
KRISTEN MURRAY License Number: 1001133
SUNSTREET ENERGY GROUP LLC
760 NORTHWEST 107 AVENUE
MIAMI, CA 33172
Fee Description ON Amount($l
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA Bldg_Permit_Template.rpt Page 1 of 1
& SAFETY PERMIT/PLAN CHECK APPLICATION
eni ree .o
DATE 04/19/2018 PERMIT/PLAN CHECK NUMBER PWffr" %
TYPE: []COMMERCIAL ❑✓ RESIDENTIAL MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑ADDITION []ALTERATION ❑DEMOLITION ❑✓ ELECTRIC .ME vIInivee CAL
❑NEW [-]PLUMBING ❑RE-ROOF-NUMBER OF SQUARES Ily ����
DESCRIPTION OF WORK INSTALL 2.56OkW ROOF MOUNTED PV SYSTEM APR 2 4 2018
PROJECTADDRESS 24582 HIDDEN HILLS DRIVE, MENIFEE, CA Received
ASSESSOR'S PARCEL NUMBER 358-661-007 LOT 32 TRACT 32025
PROPERTY OWNER'S NAME WOODSIDE HOMES
ADDRESS 11870 PIERCE STREET SUITE 250
PHONE (949)939-9564 EMAIL MIKEJ@WOODSIDEHOMES.COM
APPLICANT NAME KRISTEN MURRAY
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S NAME SUNSTREET ENERGY GROUP LLC OWNER BUILDER? ❑YES ✓❑NO
BUSINESS NAME SUNSTREET ENERGY GROUP LLC
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S STATE LIC NUMBER 1001133 LICENSE CLASSIFICATION B
VALUATION$ $6.779.00 SQ FT L SQ FT
APPLICANT'S SIGNATURE c/1.f.6 Q.YL , l'f"}��- DATE 0 411 9/2 0 1 8
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN I SMIP
INVOICE ' �/ PAIDAMOUNT O
AMOUNT Uo OCASH OCHECK# CREDIT CARD VISA/MC
PLAN CHECK FEES PAIDAMOUNT 0CASH 0CHECK# O CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6 77 7
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM 0TY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE .56OKW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 8PCS. LG LG320EIK-A5(3207) BUYER:
INVERTER 8PCS ENPHASE 106PLUS-72-ACM-US
ROOF TYPE I CONC. TILE DATE: ____
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3 ARRAY#4
MOD 0TY 8 NA NA NA BUYER:
TILT 27° NA' NA' NA'
AZIMUTH 263- NA' NA* NA' O TE:
City of M
Building Dept.
APR 2 4 2018
Received
O
OA
T
Q
K
K
a
_ c
a
NEMA 3R JUNCTION BOX
t 5'-6 3' (I'OUTSIDE ARRAY)
'
PV AC DISCONNECT
4 EXTERIOR-GARAGE CITY OF MENI EE
UTILITY METER 8 BUILDING AN S!
MAIN SERVILE PANEL
(VERIFIED BY BUILDER
PLAN APPRO AL
-� AC COMBINER BOX
REVIEWED B
'Approval of these plan shall
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF approval of,4*violatio i of a
regulations#prdinan s. T
PLAN I ELEVATION B-RIGHT jobsite unbh-Aplelion
ORIENTATION I LOT#32
DAKOTA AT WOODSIDE HOMES: ORIGINAL BY:DAN BOWLING DATE:18.04.16
11870 PIERCE STREET,SUITE#I00 REVIEWED BY:T.HAMMERBACHER DATE:18.04.17
AUDIE MURPHY RIVERSIDE.CA 92505 REV.# BY DATE I DESCRIPTION %.U namasti§
s0ue
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 6707 WSuite 7 ar Circle
2L582 HIDDEN HILLS DRIVE der, O8
PLOT PLAN I I/16'=I'-0' MENIFEE,CA Boulder,C080301
SYSTEM LAYOUT 303.447.0300
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 8 LG LG320EIK-A5(32OW) ACPV MODULE W/INTEGRATED ENPHASE 106PLUS-72-ACM-US MICROINVERTER SOLAR
2 1 TBD TBD PV ROOF JUNCTION BOX,NEMA 3R SOLAR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V,30A SOLAR
4 1 ENPHASE 10 ENVOY ENV-IGAMI-240 PV DATA MONITOR,240V SOLAR
5 1 ENPHASE X-10-AMI-240-B AC COMBINER BOX SOLAR
6 1 ENPHASE TBD PV BREAKER.I X 2OA-2P.I X 5A-2P SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER.I X 2OA-ZP,RATING MAY VARY SOLAR
8 1 TBD TBD SERVICE PANEL,200A BUS BLDR.ELEC.
9 1 TBD TBD UTILITY METER, IPH,120/24OV,200A BLDR.ELEC.
10 1 TBD TBD GROUNDING ELECTRODE,UFER BLDR.ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE.CA PANEL MFR. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 38 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTSST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TDELTA) THIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD, MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD. PART NUMBER AC MODULE SPEC LG320EIK-A5(320W) I.I,A x H(MODS)= 9.36A OF CURRENT
MOD, POWER STC(P) AC MODULE SPEC WATTS(00 320 9.36A x 3.25= II.70A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 1 TIE-IN WITH A 20A/2P 2 SPACE Iry BACKFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC I WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC I VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HZ(AC) 60 159.3-60.5
OUTPUT PHASE OUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741/IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY.MAX PER BRANCH CIRCUIT MOD.QTY BC QTY 8
BRANCH CIRCUIT OUTPUT, IMAMC (IAc•MOD.QTY ac) AMPS(AC) 9.36
AC MODULE QUANTITY.TOTAL MOD.OTY T OTV 8
TOTAL SYSTEM OUTPUT IMAXTS (IAc-MOD. QTY T) AMPS(AC) 9.36
CONDUCTOR SIZING CALCULATIONS
0 CONDITION OF USE(COU): (AMPACITY'TEMP.DERATE'FILL DERATE)vs.REO'D(IMAX)
2)TERMINALS(TERM): AMPACITY AT TERMINALS.vs.REOT.(IMAX• 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL RESULT REQ'D OCD
TYPE DERATES DERATE DERATE (A) W USED(A)
A #12 CU THWN-2 COU 30 0.76 1 1.0 22.80 9.36
TERM 25 25 11.70 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 9.36
TERM 35 35 11.70 20
C #10 CU NM-B COU 40 0.91 L0 36.40 9.36
TERM 35 35 11.70 20
CONDUCTOR SCHEDULE
KEY 1 CONDUCTORS CU/AL TYPE LOCATION TRADE O
A I-#12 ENPHASE 0 CABLE. 1-#6G,FREE AIR CU UL3003,DG CABLE ARRAY SOLAR 9
8 1 3-#10•. 1-#10 EGC I CU I NM-B(ROMEX) INTERIOR I SOLAR
C 3-#10. 1410 EGC CU I NM-B(ROMEX) INTERIOR I SOLAR 41N
•NEUTRAL CAPPED AND NOT USED
7
' E DI
4 =SA/2P
O620A2GG
A B C C = 10
I I 1 i be onstn
ROOF EXTERIOR-GARAGE qi DVI iions(
ELECTRICAL DIAGRAM 2.56o KW set appr(
LOT#32
ORIGINAL BY:DAN BOWLING DATE:18.04.16
DAKOTA AT WOODSIDE HOMES: REVIEWED BY:T.HAMMERBACHER I DATE:18.04.17
11870 PIERCE STREET.SUITE#100
AUDIE MURPHY RIVERSIDE,CA 92505 REV.# BY DATE DESCRIPTION •�
namasbe
SOL/,A
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
6707 Vfi Circle
INDIVIDUAL 24582 HIDDEN HILLS DRIVE Su8e ufte7 70O
PLOT PLAN 2 NTS MENIFEE,CA
Boulder. 00301
303.4
ELECTRICAL 303.447.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)WIRE TRANSITION JUNCTION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)THE RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION MANUAL,
APRIL 2016 EDITION
6)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH EV)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND
THE EDGE OF THE PV ARRAY 7 SUB-ARRAY.
7)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 401.
8)PV PANEL HAS BEEN TESTED BASED ON UL 1703.
9)AN ANIMAL GUARD SHALL BE INSTALLED MOUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS T0.MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)BASE ATTACHMENT AND FLASHING TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS,
II)ALL ROOF ATTACHMENTS TO BE FLASHED AND SEALED PER MANUFACTURER'S SPECIFICATIONS.
ELECTRICAL NOTES-
GENERAL-
0 ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING.NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE,
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703.IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
ID MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED*PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS- 'A THE
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110,26.
1
o he i pomp
a fedi rol,sW
'Plan Must
ORIGINAL BY:DAN BOWLING DATEIB.04.16
DAKOTA AT WOODSIOE HOMES 11870 PIERCE STREET,SUITE#100 REVIEWED BY:T.HAMMERBACHER I DATE18.04.17
AUDIE MURPHY RIVERSIDE,CA 92505 REV.# BY DATE DESCRIPTION •a
b namasGe
MIA'
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 6707 Wrichoster 0 Circle
PLOT PLAN 3 NTS 24582 HIDDEN HILLS DRIVE Suits O8
NOTES MENIFEE,CA Boulder,3D3,4 7.03DO 5
303.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
NEMA 3R JUNCTION BOX
0'OUTSIDE ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER S
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE — AC SPECS
AC OPERATING VOLTAGE: 240 V PHOTOVOLTAIC SYSTEM EQUIPPED DATE
AC OPERATING CURRENT: 9.36A WITH RAPID SHUTDOWN or an
I PC., NEC 690.54 1 PC., NEC 690.12 apt on
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:DAN BOWLING I DATEi8.04.16
DAKOTA AT WOODSIDE HOMES: REVIEWED BY:T.HAMMERBACHER I DATE18.04.17
11370 PIERCE STREET.SUITE#100
AUDIE MURPHY RIVERSIDE.CA 92505 REV# BY DATE DESCRIPTION is
namasb6
SOL/R
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 6707 Vter Cede
PLOT PLAN 4 NITS 24582 HIDDEN HILLS DRIVE Suite Suite 7O8
PLACARDS HENIFEE.CA B 303,4 7030301
303.M7.0300