PMT18-00612 City of Menifee Permit No.: PMT18-00612
29714 HAUN RD.
'ACCEt_A? MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 0 3/1 61201 8
PERMIT
Site Address: 28542 FIELDGRASS ST, MENIFEE, CA Parcel Number:
92584 Construction Cost: $5,613.76
Existing Use: Proposed Use:
Description of SOLAR TR 31582 HERITAGE HEIGHTS
Work: 7 MODULES,7 MICROINVERTERS,2.24kW
LOT 91
Owner Contractor
LENNAR HOMES OF CA, INC LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
SAMANTHA MAZELLA License Number: 728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description Q�t Amount!$)
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpt Page 1 of 1
IT/PLAN CHECK APPLICATION
41,
5
Menifee
DATE:2/5/2018 PERMIT/PLAN CHECK NUMBER
TYPE: O COMMERCIAL O RESIDENTIAL O MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: O ADDITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
O NEW O PLUMBING O RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit -2.24 kW, 7 pcs, Master Solar Permit No: PMT 17-00129
Plan No: 1874
PROJECTADDRESS 28542 Fieldgrass St ZIP 92584
ASSESSOR'S PARCEL NUMBER LOT 91 TRACT31582
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
APPLICANTNAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? OYES ONO
BUSINESS NAME Lennar Homes of California
ADDRESS 980 Montecito Dr.,Suite 302, Carona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 5,613.76 SQ FT L SQ FT
APPLICANT'S SIGNATURE D I / '' 6 DATE 2/5/2018
SE ONL: _
DEPARTMENT DISTRIBUTION �y� CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE ACCEPTED BY: /f«
PERMIT FEE Ot�3• SMIP I GREEN
PLAN CHECK FEE INVOICE TOTAL
OWNER BUILDER VERIFIED O YES O NO DRIVERS LICENSE# NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityafinenifee.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.240 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 7 PCS.1 LG I LG320EIK-A5(320W) BUYER:
INVERTER 1 7 PCS.j ENPHASE I IO6PLUS-72-ACM-US
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3 ARRAY#4
MOD OTY 7 NA NA NA BUYER:
TILT I8° NA' NA° NW
AZIMUTH 1 180- 1 NA' I NA- I NA- DATE: ENII
City of Mendee j
Building Dept. BUILDING ANI
FEB 1 ' 2018 PLAN APF R01
Recei��b REVIEWE
'Approval of then plans
approval of,any i olatip
regulations and oi km
johsite until coq left
rz
SOLADECK WIRE .- Or a
TRANSITION BOX
(UNDER ARRAY)
PV DISCONNECT
EXTERIOR-GARAGE
UTIL
(VERIFIED
METER I
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX 1
41
b.
F
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 1874 ELEVATION A-RIGHT Z
ORIENTATION 2 LOT#91
ORIGINAL BY-AARON FRIEDLANDE DATE:I7.II.22
HERITAGE HEIGHTS LENNAR: 92879 REVIEWED BY:JIM PARKS DATEA7.11.22
CORONA,CA
980 MONTECI DRIVE,#302 REV.# BY DATE I DESCRIPTION
;PmamasW
SOLAR
DWG TITLE: PAGE #: SCALE:
SITE LOCATION: 4B &u.GOO 304
INDIVIDUAL 28542 FILEDGRASS ST BaWtle4 7030004
PLOT PLAN I I/Ifi'=I'-0' MENIFEE,CA 303.4A7.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY I MANUFACTURER MODEL NOTES I TRADE
1 7 1 LG LG320EIK-A5(32OW) ACPV MODULE W/INTEGRATED ENPHASE IQ6PLU5-72-ACM-US MICROINVERTER SOLAR
2 1 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
3 I CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R,240V.30A SOLAR
4 I ENPHASE IQ ENVOY ENVACAMI-240 PV DATA MONITOR,240V SOLAR
5 1 ENPHASE X-IQ-AMI-240-B AC COMBINER BOX SOLAR
6 I ENPHASE TBD PV BREAKER.I X 20A-2P.I X SA-2P SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER.I X 20A-2P.RATING MAY VARY SOLAR
8 1 TBD TBO SERVICE PANEL,200A BUS BLDR.ELE .
9 1 TBD TBD UTILITY METER, IPH,120/24OV,200A I BLDR.ELE .
10 I TBD TBD GROUNDING ELECTRODE,LIFER BLDR.ELEC. DE S
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL MFR. CUTLER- 'MER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% •C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP.MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40 lail
TEMP.DELTA LOW(TOELTA) THIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD. PART NUMBER AC MODULE SPEC LG320EIK-A5(320W) IAA x 7(MOBS)= BJ19 OF CORBENT
MOD. POWER STC(P) AC MODULE SPEC WATTS(GG) 320 8.19A x 1.25= I0.24A
stnm
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A 20A/2P 2 SPACE PV BACKFEEO BREAKE n
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 280 �lot be
ON
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264 ny provi$ n$of l
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HI(AC) 60/59.3-60.5 Fnls set of iMm
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741/IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD, OTY BC OTY 7
BRANCH CIRCUIT OUTPUT, IMAXBC (IAC-MOD.GTY ea) AMPS(AC) 8.19
AC MODULE QUANTITY,TOTAL MOD. OTY T QTY 7
TOTAL SYSTEM OUTPUT IMAXTS (IAC•MOD. OTY T) AMPS(AC) 1 8.19
CONDUCTOR SIZING CALCULATIONS
I)CONDITION OF USE(COU): (AMPACITY`TEMP.DERATE` FILL DERATE)vs.REO'D(MAX)
2)TERMINALS(TERM); AMPACITY AT TERMINALS. vs.REG-D.(TMAX - 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITYW/0 TEMP. FILL RESULT REO'0 OCO
TYPE DERATES DERATE DERATE (A) (A) USED(A)
A #12 ICU THWN-2 COU 30 g16110 22.80 8.19
TERM 25 25 10.24 20
B #10 CU NM-B COU 40 036.40 8.19
TERM 35 35 10.24 20
C #10 LU NM-B COU 40 0 36.40 8.19
TERM 35 35 10.24 1 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS 1 CU/AL 1 TYPE LOCATION TRADE
A I-#12 ENPHASE Q CABLE.I-#6G,FREE AIR CU UL3003,DG CABLE ARRAV SOLAR
B 3-#10`.I-#10 EGC CU NM-B(ROMEX) INTERIOR I SOLAR
C 3-#10,1-#10 EGC I CU I NM-B(ROMEX) I INTERIOR I SOLAR 9
'NEUTRAL CAPPED AND NOT USED _
O
O8 �
5
4 e
O 5A/2P O
O
O6 tOAI
2
20AR
N
G
A e c c =m
I I I
( ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.24OKW
LOT#91
HERITAGE HEIGHTS LENNAR: ORIGINAL BY:AARON FRIEDLANDE DATE:I I.II.22 980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:17.11.22
CORONA,CA 92879 REV.# BY DATE DESCRIPTION •,
namasb8
xo4Ae
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4577 lder,C 8 304
net
INDIVIDUAL 28542 FILEDGRASS ST B9WHe4 C03030A
PLOT PLAN 2 NTS MENIFEE,CA 303.447.0300
ELECTRICAL
INSTALLATION NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS.TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(}')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED.FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'. ���
IU 26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(1')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION. /N
I
e a pem9
eral,sta
ELECTRICAL NOTES: iz Its must
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
IU MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT}.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:AARON FRIEDLANDE DATE17.11.22
HERITAGE HEIGHTS LENNAR: REVIEWED BY:JIM PARKS DATEi7.11.22
980 MONTECITO DRIVE.#302
CORONA,CA 92879 REV.# BY DATE DESCRIPTION •,
namas so".
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
INDIVIDUAL 457t Ber,CO 8 Sheet
PLOT PLAN 3 KITS28542 FILEDGRASS ST Boulder, 7030304
NOTES
MENIFEE.CA 03.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE _
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
T
top
WO ECX WWE '.Or an
1a0K4T10N 00X
MCEq dggaYl
city
apt on tho
1
JI�AcevXmrecT
AN SERVICE PYIEL
RIFIM ev WILMR)
L[[CM01 YR 00%
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 8. 19A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:AARON FR EDLANDEq DATE17.11.22
HERITAGE HEIGHTS LENNAR:
900 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:17.11.22
CORONA.CA 92879 REV.# BY DATE DESCRIPTION
namasb6
soLev
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 9571l or,CO8 Street
PLOT PLAN 4 NTS MENIF FILEDGRASS ST BoW3. C08030q
PLACARDS MENIFEE,LA 303.4g7.0300