PMT17-04410 City of Menifee Permit No.: PMT17-04410
29714 HAUN RD. Type: Residential Electrical
'5A—CCELAk� MENIFEE,CA 92586
MENIFEE Date Issued:
12115/2017
PERMIT
Site Address: 30477 BRISTOL GATE LN,MENIFEE, CA Parcel Number: 364350-021
92584 Construction Cost: $6,328.72
Existing Use: Proposed Use:
Description of INSTALL SOLAR PV SYSTEM,2.560 KW,8 MODULES, 8 INVERTERS
Work: TR 30422 LOT 40
Owner Contractor
LENNAR HOMES LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DRIVE SUITE 302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
LENNAR HOMES OF CALIFORNIA INC License Number.728102
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Phone:9493498269
Fee Description QtV Amount($1
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00 -
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carded on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfefted.
AA_8ldg_Permft_Terrplate.rpt Page 1 of 1
PERMIT/PLANBUILDING & SAFETY APPLICATION
�'PMenifee `'
DATE: 12/12/2017 PERMIT/PLAN CHECK NUM t" 1IBER — D
TYPE: O COMMERCIAL O RESIDENTIAL O MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: O ADDITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
O NEW O PLUMBING O RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit- 2.560 kW, 8 pcs, Master Solar Permit No: PMT 16-00910
Plan No: 1924
PROJECTADDRESS 30477 Bristol Gate Lane ZIP 92584
ASSESSOR'S PARCEL NUMBER 364-350-021 LOT 40 TRACT30422-3
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? O YES ONO
BUSINESS NAME Lennar Homes of California
ADDRESS 980 Montecito Dr., Suite 302, Corona,CA 92879
PHONE 951-817-3539 EMAIL samantha.mazella@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 6328.72 SQ FT L SQ FT
APPLICANT'S SIGNATURE DATE 12/12/2017
CITY STAFF USE ONLY
DEPARTMENT DISTRIBUTION CITY OF MEN IEEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE ACCEPTED BY:
PERMIT FEE a �(� SMIP GREEN
PLAN CHECK FEE INVOICETOTAL
OWNER BUILDER VERIFIED OYES O NO DRIVERS LICENSE# NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityeftenifee.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY 1 MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.560 KW Mike Dufa01[ LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 8 PCS.1 LG LG320EIK-A5(320W) Sf VP OPefaLIODS
INVERTER 1 8 PCS.1 ENPHABE I I06PLU5-72-AGM-US
❑c#1001133 Class a BUYER:
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3 ARRAY#4
MOD OTY 8 NA NA NA BUYER:
TILT 23- NA° NA• NA°
AZIMUTH 270° NA° NA• NA'
DATE:
———————l
r
I
I � I
I I
i I
I
13'-S ARRAY
12'-9J4' IL'-3°FLASHING
SOLADECK WIRE
^ TRANSITION BOX
am ` (UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
—_
m UTILITY METER 8
pr I MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BOX
W a >^H
IWL Q Q
Z O o d
u a aLL co
o
C Z
r Z A
iV VE:DlI'IENSIONS AWSHOWN IN INIFIC,
' Z
PLAN1924 ELEVATION A-RIGHT
ORIENTATION 2 LOT#40
LENNAR: ORIGINAL BY:DESIREE WILLIAMS DATE:17.9.29
MARIPOSA AT 980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:17.9.29
THE LAKES CORONA.CA 92879 REV.# BY DATE DESCRIPTION
Omamasri§
Souv
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Breedw yStreet
INDIVIDUAL 30477 BRISTOL GATE LANE Boulder,CO 803D4
PLOT PLAN I/Ifi'=I'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY CITY I MANUFACTURER MODEL NOTES TRADE
1 8 LG LG326EIK-A5(32OW) ACPV MODULE W/INTEGRATED ENPHASE IG6PLUS-72-ACM-US MICROINVERTER SOLAR
2 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
3 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.240V.30A SOLAR
4 1 ENPHASE 10 ENVOY ENV-IGAMI-240 PV DATA MONITOR,120V SOLAR
5 1 ENPHASE X-10-AMI-240-B AC COMBINER BOX SOLAR
6 1 ENPHASE TBD PV BREAKER.I X 20A-2P.I X 5A-2P SOLAR
7 1 CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P.RATING MAY VARY SOLAR
8 I TBD TBD SERVICE PANEL,200A BUS BLDR.ELEC.
9 1 TBD TBD UTILITY METER, IPH,120/24OV,200A BLDR.ELEC.
10 1 TBD TBD GROUNDING ELECTRODE.UFER BLDR.ELEC.
II 1 TBD TBD GROUNDING ELECTRODE. 690.47(D) SOLAR
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT I PANEL
LOCATION MENIFEE,CA PANEL MFR. CUTLER-HAMMER
TEMP.AMBIENT HIGH(TMAX) ASHRAE 2% °C. 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TDELTA) THIN-TTEST °C -27 PV OCPO DEVICE USED AMPS 20
MOD.MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD.PART NUMBER AC MODULE SPEC LG320EIK-A5(320W) 1.17A X B(MODS)= 9.36A OF CURRENT
MOD.POWER STC(P) AC MODULE SPEC WATTS(Dc) 620 9.36A X Lzs= II.70A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN w1TH A EDArzP x SPACE PV BACXFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264 ��
NOMINAL OUTPUT CURRENT OAC) AC MODULE SPEC AMPS(AC) 1.17 0ufauit
NOMINAL FREQUENCY/RANGE AC MODULE SPEC H2(AC) 60/59.3-60.5 Sr Mike ke Operations
PHASE QUANTITY AC MODULE SPEC PHASE
COMPLIANCE AC MODULE SPEC UL1741/ IEEE1547 Uc#1001133 Class B
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD.OTY Be CITY 8
BRANCH CIRCUIT OUTPUT, IMAXBC (IAC'MOD.QTY BC) AMPS(AC) 9.36
AC MODULE QUANTITY,TOTAL MOD.OTY T AMPS
8
TOTAL SYSTEM OUTPUT IMAXTB (IAD'MOD.OTY T) AMPS(AC) 9.36
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY-TEMP.DEBATE'FILL DEBATE)VS.REG'D(IMAX)
2)TERMINALS(TERM): AMPACITY AT TERMINALS.M.REQ'D,(IMAX° 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT READ OLD
TYPE DERATES DERATE DERATE (A) (A) USED(A)
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 9.36
TERM 25 25 11.70 20
B #10 LU NM-B COU 40 0.91 1.0 36.40 9.36
TERM 35 35 11.70 20
C #10 CU NM-B COU 40 0.91 1.0 36.40 9.36
TERM 35 35 II.70 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE
p L#12 ENPHASE Q CABLE.I-#6G,FREE AIR CU UL3003.DG CABLE ARRAY SOLAR
B 3-#IO.1410 EGC CU NM-B(ROMEX) INTERIOR I SOLAR
C 13410.1410 EGG CU NM-B(ROMEX) INTERIOR I SOLAR 9
D 1-#6 GEC. 2016 CEC 690.47(3) CU BARE TNT/EXT I SOLAR O
NOTE:NEUTRAL CAPPED AND NOT USED
B
O
O SUOP O
D<,
,N
G
— u
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.56OKW
LOT#40
ORIGINAL BY:DESIREE WILLIAMS DATE97.9.29
MARIPOSA AT LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:17.9.29
THE LAKES CORONA,CA 92879 REV.* BY DATE I DESCRIPTION
Onamastili
Po!�Av
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 30477 BRISTOL GATE LANE Boulder,CO 80304
PLOT PLAN 2 NTS MENIFEE,LA 303.447.0300
ELECTRICAL
INSTALLATION NOTES: Mike Dufault
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C. Sr VP Operations
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE. Uc#1001133 Class 8
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(e)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(T)BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY,
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
IU 26 GAUGE INTERLOCKING FLASHING'SIOEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(1')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SMALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703.IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING.OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT k.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110-26.
ORIGINAL BY:DESIREE WILLIAMS DATE17.9.29
MARIPOSA AT LENNAR: REVIEWED BY:JIM PARKS DATE17.9.29
980 MONTECITO DRIVE.#302
THE LAKES CORONA.CA 92879 REV.# BY DATE DESCRIPTION t1mast6
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
teel
INDIVIDUAL 4571lder.0 B 304
PLOT PLAN 3 NTS 30477 BRISTOL GATE LANE Boulder. 7080304
NOTES MENIFEE,CA 303.447.0300
Mike Dufaul[
Sr VP Operations
❑C#1001133 Class 8
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER&
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AL COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 9.36A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:DESIREE WILLIAMS DATEJ7.9.29
980
MARIPOSA AT 80 MO:NTECITD DRIVE,#302 REVIEWED BY:JIM PARKS DATE17.9.Z9
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION •,
namasb6
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 4871 Broadway 304
PLOT PLAN 4 NTS 30477 BRISTOL GATE LANE Boulder. 7030004
PLACARDS MENIFEE,CA 303.447.0300