PMT17-03811 City of Menifee Permit No.: PMT17-03811
29714 HAUN RD.
'/ACCEL/47 MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 10/26/2017
PERMIT
Site Address: 29623 EDGEMERE WAY, MENIFEE, CA Parcel Number: 364-360-008
92584 Construction Cost: $6,328.72
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 MARIPOSA
Work: 9 MODULES, 1 INVERTER,2.39 kW
LOT 28
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description Qtv Amount fSl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Templale.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
,4
r=Menifee
DATE:10/18/2017 PERMIT/PLAN CHECK NUMBER ?Mt- 05m
TYPE: O COMMERCIAL FSIDENTIAL O MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: t�VVITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
O NEW O PLUMBING O RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit- Plan 1769 -2.39 KW/9 PCS
Master Solar Permit No. PMT16-00910
PROJECTADDRESS 29623 Edgemere Way ZIP 92584
ASSESSOR'S PARCEL NUMBER 364-360-008 LOT 28 TRACT30422-3
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? O YES ONO
BUSINESS NAME 980 Montecito Dr.,Suite 302,Corona CA 92879
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL Jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ SQ FT L SQ FT
APPLICANT'S SIGNATURE DATE 10/18/2017
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BURRING PLANNING ENGINEERING FIRE ACCEPTED BY:
PERMIT FEE I a Leo SMIP GREEN
PLAN CHECK FEE INVOICE TOTAL 3,LOU
OWNER BUILDER VERIFIED O YES G NO DRIVERS LICENSE tl NOTARIZED LETTER 0 YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityqfmenifee.us
SYSTEM INFORMATION ^
✓�y J BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM CITY MFR. MODEL Mike Duhult ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 1Z385KW Sr VPOReray., LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 9 PCS.1 HYUNDAI I HIS-S265RG(265W) Ud 2001133 [IassB BUYER;
INVERTER 1 9 PCS.1 ENPHASE I M215-60-2LL-S22-IG
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 !ARRAY#3 CITY OF MENI EE
MOD OTY 9 NA NA BUYER:
TILT 23• 1 NA* I NA' DATE: N SA
AZIMUTH 175• NA- NA•
PLAN APPRO AL
City of Menitee
Building Dept. REVIEWED BY
4
OCT 2 5 2017
`Approval of these plan shall o
Received approval of,any violatio of any
regulations andordina es. Thi
jobsite until completion
-------------------
t
29'-B'ARRAY
30'-6'FLASHING II'-2'
WIRE
TRRANSITIOANSITIO N BOX
(UNDER ARRAY) GIIIIIIIAD
NIIIIIMI&
PV AC DISCONNECT
EXTERIOR-GARAGE
I
UTILITY METER e
MAIN SERVICE PANEL
(VERIFIED BY BUILDER) I I
L--------�
L---
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 1769 ELEVATION B LEFT
ORIENTATION
NON 3 LOT#28 1
ORIGINAL BY: JIM PARKS DATE:17.05.04
MARIPOSA LENNAR:
980 REVIEWED BY:KIM ASCOUWER DATE:17.05.05
AT THE LAKES
CORONNA.A,C CA A 92879 DRIVE,#302 REV.# I BY DATE I DESCRIPTION •,
namas.�
sauv
DWG TITLE: PAGE AH SCALE: SITE LOCATION: 4571 Broadway SBeN
INDIVIDUAL 29623 EDGEMERE WAY B.Ider,CO 80304
PLOT PLAN I 1/16'= 1'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP.AMBIENT HIGH(TMA%) ASHRAE 2% 'C 37 INV-MODEL INVERTER SPEC M215-6D-2LL-S22-IG
TEMP.AMBIENT LOW(THIN) ASHRAE EXTR.MIN •C -2 INV. MAX POWER,(WAC MAX) INVERTER SPEC WATTS(AG) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC •C 25 INV. INPUT V.Noe MAX) INVERTER SPEC VOLTS IN) 48
TEMP,DELTA LOW(TOELTA) THIN-TTEST •C -27 INV.OUTPUT V.(VAc NON) INVERTER SPEC VOLTS(Ac) 240
MOD-MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT, IAC INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(ID0 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(00 258 COMPLIANCE INVERTER SPEC UL17411 EEE1547 DI
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(9U 31.30 INV.GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT.VOLTAGE(VOC) MODULE SPEC VOLTS(oc) 38.10 INV.QTY.MAX/BRANCH CCT. INV.GTYBc OTY 9
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/•C -0.114 BRANCH CCT.OUTPUT,IMAXBC (IAC•INV.QTYBC) AMPS(Ad 8.10
MOD.MAX VOLTAGE(VMA%MGD) (VOC+(TO•COEF)) VOLTS(OC) 41.18 INV. QUANTITY,TOTAL INV.OTYT OTY 9
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS(OC) 8.50 TOTAL SYSTEM OUTPUT.IMAXT$ I(IAC'INV.QTYT) IAMPS(A[) 8.10
MOD.SHORT CCT. CURRENT(Isc) MODULE SPEC AMPS(OW 9.00
MOD. MAXIMUM CURRENT(IMAX) (Isc• 1.25) AMPS(oc) 11.25
MIN.AMPACITY REO'D,PER NEC (IMAX•1.25) AMPS(oU 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(OC) 15
ELECTRICAL EQUIPMENT SCHEDULE
KEY QTY MANUFACTURER MODEL NOTES TRADE
1 9 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR constru
2 9 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0796-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR V$ions 01
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R,240V,30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR It f appra
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I%I5A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL,MIN. 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER,I-H.120/24OV,200A BLDR.ELEC.
12 TBD TBD GROUNDING ELECTRODE UFER BLDR.ELEC.
13 1 TBD TBD GROUNDING ELECTRODE.690.47(D) SOLAR
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
Q CONDITION OF USE CCOU): I(AMPACITY•TEMP.DERATE•FILL DEBATE)vs.REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): I AMPACITY AT TERMINALS.M REQ'D,(IMAX• 1.25) PANEL MFR- CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REWD OCD BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 0.76 1.0 22.80 8.10 ALLOWED PV PER NEC AMPS 40
TERM 30 25 25 10.13 20 PV OCPD DEVICE USED AMPS 20
B #10 LU NM-B COU LO 0.91 L0 36.40 8,10
TERM 35 35 10.13 20 \
L #10 1 CU I NM-B COU 1 40 0.91 1.0 36.40 8.10
TERM 135 35 10.13 1 20 I Mike Ouhult
5r VPOpemtIGns
CONDUCTOR SCHEDULE U01MI133 ClassB
KEY .CONDUCTORS I CU/AL TYPE I LOCATION I TRADE
A 1-#12 ENGAGE CABLE,1-#6G,FREE AIR 1 CU TC-ER ARRAY SOLAR
B 3-#10, 1-#10 EGC CU NM-B(ROMEX) INTERIOR SOLAR
C 3-#10, 1-#10 EGC I CU I NM-B(ROMEX) I INTERIOR SOLAR
D CAT5E.ETHERNET CABLE I CU I CATSE I INTERIOR I SOLAR
E I-#SGEC.2010 CEC 690.47C) I CU I BARE I EXTERIOR I SOLAR
5 6 II
SEE NOTE 15 10
8
O ISOp
2 O
O O O 20AIff
}
L
G G JM�
13= E A B C =12
I
I Atl6F EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.385%W
LOT#28
ORIGINAL BY: JIM PARKS DATE:17.05.0E
MARIPOSA LENNAR:
980 MONTELITO DRIVE.#302 REVIEWED 8Y:KIM ABCOUWER I DATE:17.05.05
it
AT THE LAKES CORONA,CA 92979 REV.# BY DATE I DESCRIPTION stA
•�
n io'AR
DWG TITLE: PAGE#: SCALE: Street
SITE LOCATION: 4577 Broadway CO8 Street
INDIVIDUAL MENIF EDGEMERE WAY Boulder,C080309
PLOT PLAN 2 NTS
ELECTRICAL MENIFEE,CA 303.44Z0"AO
STRUCTURAL NOTES: Mike Default
SOLAR CONTRACTOR- Sr VP OPeraHons
D ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C. Utl11001133 ❑assB
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC.SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL.VERSION 227.3,PUB 140113-ICC.JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(27 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY. RTM
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
U DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(I')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION. II�1
be a per
federal,i
i 31anilnu
ELECTRICAL NOTES:
GENERAL-
D ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A MATIO14ALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD,
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE U1_1703, IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W7 ENPHASE MICRO-INVERTER SYSTEM.
II)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS. WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIG14AGE-
I6)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT pt'.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED*PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY: JIM PARKS DATE:I .
LENNAR: 05.04
MARIPOSA REVIEWED BY:KIM ASCOUWER I DATE:17.05.05
AT THE LAKES 980 I DRIVE,9302
CORONA.NA.CA CA 92 92879 REV.# BY DATE DESCRIPTION •�
namast�
scree
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 4671 Broadway Street
PLOT PLAN 3 NTS 296E3 EDGEMERE WAY Boulder,C0304 03
NOTES
MENIFEE.CA 303.447.0300
����
Mlke OeFael[
Sr VP Operz[ions
Ucp 1001133 Class B
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS 1T
ARE LOCATED AS SHOWN.
6�—wo
`or,or an
or city
e kept on the
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 6
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 8.1 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: JIM PARKS DATE:17.05.04
MARIPOSA LENNAR:
980 MONTECITO DRIVE.$302 REVIEWED BY:KIM ABCOUWER I DATE:17.05.05
AT THE LAKES CORONA,CA 92879 REV.# BY DATE I DESCRIPTION •�
namast;A.
DWG TITLE: PAG111SCALE: some
SITE LOCATION: 4B Idw,BroadmyBSOeet
INDIVIDUAL 29623 EDGEMERE WAY Bwlder,CO B0304
PLOT PLAN 4TS
PLACARDS MENIFEE.CA
303.447.0300