PMT17-03808 City of Menifee Permit No.: PMT17-03808
29714 HAUN RD. Type: Residential Electrical
�!-�CCEL/4? MENIFEE,CA 92586
MENIFEE Date Issued: 10126120117
PERMIT
Site Address: 29671 EDGEMERE WAY, MENIFEE, CA Parcel Number: 364-360-005
92584 Construction Cost: $6,328.72
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 MARIPOSA
Work: 9 MODULES, 1 INVERTER,2.39 kW
LOT 25
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number: 728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description Qtv Amount 4$)
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpt Page 1 of 1
APPLICATIONBUILDIN & SAFETY PERM IT/PLAN CHECK
Menifee
DATE:10/18/2017 PERMIT/PLAN CHECK NUMBER
TYPE: O COMMERCIAL AESIDENTIAL O MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: **CQITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
O NEW O PLUMBING O RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit - Plan 1924- 2.39 KW/9 PCS
Master Solar Permit No. PMT16-00910
PROJECTADDRESS 29671 Edgemere Way ZIP 92584
ASSESSOR'S PARCEL NUMBER 364-360-005 LOT 25 TRACT30422-3
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL Jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? O YES ONO
BUSINESS NAME 980 Montecito Dr., Suite 302, Corona CA 92879
ADDRESS 980 Montecito Dr., Suite 302,Carona, CA 92879
PHONE 951-817-3680 EMAIL Jeremiah.acayturd@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
� SQ FT L SQ FT VALUATION$ <j7
APPLICANT'S SIGNATURE DATE 10/18/2017
CITY AFk USE ONLY
DEPARTMENT DISTRIBUTION ACCEPTED BY: CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE
PERMIT FEE U aSMIP GREEN
L
AN CHECK FEE INVOICE TOTALER BUILDER VERIFIED O YES O NO DRIVERS LICENSE# NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityofmenifee.us
SYSTEM INFORMATION
"✓�,�J BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY HER, MODEL Nuke DO SO" ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.385 KW sr VPOP1.1- LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 9PCS. HYUNDAI I HIS-S265RG(265W) I ❑tlF1001133 OessB g(p ER: ['
INVERTER 9PCS ENPHASE M215-60-2LL-522-IG C 1 Y OF Eh
ROOF TYPE TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION BUILDING
1 I I IL DI A M t
ARRAY#1 ARRAY#2 ARRAY#3 V .
MOD OTY 9 NA NA BUYER:--- --- N A PRQ
TILT 23° NA° NA'
AZIMUTH 1 IBO' 1 NA' I NA' DATE:
City of Menifee REVIEW D�
Building Dept.
OCT 2 5 20i1 •Approval oft ese pla
approval of,an V vjolatl
Received regulations an I ordina
jobsite until co Yipletio
16'-5'ARRAY
17'-3'FLASHING
F— ---- - - - -----�
I
- I
I OI
I I
SOLADECK WIRE
' I TRANSITION BOX
(UNDER ARRAY)
I I
PV AC DISCONNECT 1
I I E%TERIOR-GARAGE
I r UTILITY METER
MAIN SERVICE PANEL
—— —J (VERIFIED BY BUILDER)
woo
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN TATI 3 ELEVATION A RIGHT
ORIENTATION LOT#25 N
ORIGINAL BY: JIM PARKS DATE:17.05.04
MARIPOSA LENNAR: REVIEWED BY:KIM ABCOUWER DATE:17.05.05
CO
AT THE LAKES I2 DRIVE.#302
CORONNA,A,C CAA 92879 REV.# BY DATE DESCRIPTION
Vnamast;6
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
tmet
INDIVIDUAL 4Bo Boulder.
GO
a8 304
PLOT PLAN 1/16'7 1'-0' 29671 EDGEMERE WAY Boulder, 7030009
SYSTEM LAYOUT MENIFEE,LA 303.447.0300
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE.CA INV. MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(THAR) ASHRAE 2% °C 37 INV. MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP,AMBIENT LOW(TMIN) ASHRAE EXTR.MIN -C -2 INV. MAX POWER.(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC 'C 25 INV. INPUT V.(Voc MAX) INVERTER SPEC VOLTS(Dc) 48
TEMP,DELTA LOW(TDELTA) TMIN-TTEST °C -27 INV. OUTPUT V.(Vac MOM) INVERTER SPEC VOLTS(AC) 240 qFE'
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(OC) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(DC) 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS CBO) 31.30 INV. GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT. VOLTAGE(VOC) MODULE SPEC VOLTS(OC) 38.10 INV.OTY,MAX/BRANCH CCT. INV.OTYBC OTY 9
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/'C -0.114 BRANCH CCT. OUTPUT,IMAXBC I(IAC•INV.QTYBC) AMPS(AC) 8.10
MOD.MAX VOLTAGE(VMAXMOD) (VOC+(TD-COEF)) VOLTS(00 41.18 INV.QUANTITY,TOTAL I INV.OTYT OTY 9
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS 00 8.50 TOTAL SYSTEM OUTPUT.]MASTS I(IAC•INV.GTYT) AMPS(AG) 8.10
MOD.SHORT CCT.CURRENT(ISC) MODULE SPEC AMPS 00 9.00
MOD.MAXIMUM CURRENT(IMAX) (ISC• 1.25) AMPS(Oc) 11.25
MIN. AMPACITY REQ'D,PER NEC (IMAX.1.25) AMPS 00 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(OC) 1 15 nal not be
ELECTRICAL EQUIPMENT SCHEDULE of yprovi
KEY QTY MANUFACTURER MODEL NOTES TRADE
1 9 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR �s, his set(
2 9 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR
3 1 RSTC 7 SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.24OV,30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 I TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I X ISA-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL.MIN. 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER.IPH.120/24OV,200A BLDR.ELEC.
12 1 TBD TBD I GROUNDING ELECTRODE UFER BLDR.ELEC.
13 1 TBD TBD I GROUNDING ELECTRODE,690.47(0) SOLAR
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
D CONDITION OF USE(COLD: I (AMPACITY•TEMP.DERATE °FILL DERATE)VB.REQ'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): I AMPACITY AT TERMINALS.v . REO'D,(IMAX• 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL RESULT REQ'D OCD BUS RATING AMPS 200
TYPE DERATES DEBATE DEBATE W (A) USED(A) MAIN DISCONNECT AMPS ZOO
A #12 CU I THWN-2 30 0.76 1.0 22.80 8.10 ALLOWED PV PER NEC AMPS 40
LOU
TERM 25 1 25 10.13 20 PV OLPD DEVICE USED AMPS 20
B #10 Cu NM-B COU 40 0.91 1-0 36.40 8.10
TERM 35 35 10.13 20 \ n
C #10 1 CU I NM-B COU 40 0.91 1.0 36.40 8.10
TERM 35 135 10.13 20 MI%e Dufault
5r VPOpemdans
CONDUCTOR SCHEDULE Utl1100103 CimB
KEY CONDUCTORS 4CU/ALTYPE LOCATION TRADE
A I-#12 ENGAGE CABLE,1-#6G,FREE AIR TC-ER ARRAY SOLAR
B 3-#10.1-#10 EGC NM-B(ROMEX) INTERIOR SOLAR
C 3-#10.1-#10 EGC NM-B(ROMEX) INTERIOR SOLAR
D CAT5E.ETHERNET CABLE CAT5E INTERIOR SOLAR
E I-#6GEC.2010 CEC 690.47(D) BARE EXTERIOR SOLAR
5 6 11
7 • o ® O
SEE NOTE 15 j 10
0
ISA/W
2 0
O zoArz
EZZIT=12
ROOF E%TER10ft-GARAGE
ELECTRICAL DIAGRAM 2.385 KW
LOT#25
LENNAR: ORIGINAL BY:JIM PARKS DATE:17.05.0E
MARIPOSA 980 MONTECITO DRIVE,#302 REVIEWED BY:KIM ABLOUWER I BATE:17.05.05
AT THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namasti§
sosnv
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
treet
INDIVIDUAL 4571ldeT,C 8 3D4
PLOT PLAN 2 NTS 29671 EDGEMERE WAY Ba303.4C080304
ELECTRICAL
MENIFEE,CA 303.44].03W
lt
STRUCTURAL NOTES: Mike Default
SOLAR CONTRACTOR- Sr VP Operations
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C. Ur/110oM3 aasf e
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED. Cnw
5)PV ARRAY WILL BE A MINIMUM OF 3"ABOVE THE COMPOSITE SHINGLE ROOF SURFACE. EPA
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH 0')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
U DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'. _
2)26 GAUGE INTERLOCKING FLASHING"SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION.IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT W)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF SAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE. -1 UPd t0 hl
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE. BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO :+ f the fee
INSTALLATION.
1p oved pla
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD,
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE U1.1703,IEC61646.IEC61730.
B)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
I6)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT e.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: JIM PARKS DATE:17.05.04
MARIPOSA REVIEWED BY:KIM ABCOUWER DATE:17.05.05
AT THE LAKES CO NA.CA I92379TO E.#302
CORONA;CA 92879 REV.# BY DATE DESCRIPTION
tm
masrB
felAe
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
treet
INDIVIDUAL 0.Bo Broadway 304
PLOT PLAN 3 NTS 29671 EDGEMERE WAY Bo303.4C080304
NOTES MENIFEE,CA 303.447.0300
� �
Mike Ou(ault
5r VP Operations
Lkp 3003133 GIassB
CAUTION: MENT
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
lmit for,or an
state or city
oust be kept on e
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER e
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 8.1 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: JIM PARKS DATE:17.05.04
MARIPOSA LENNAR:
980 MONTELITO DRIVE.#302 REVIEWED BY:KIM ABCOUWER DATE:17.05.05
AT THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION •�
namasb6
SOLAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Broadway SVeet
INDIVIDUAL 29671 EDGEMERE WAY Boulder.CO 80304
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS