PMT17-03552 City of Menifee Permit No.: PMT17-03552
29714 HAUN RD.
'q%CCEL/� MENIFEE, CA 9258E Type: Residential Electrical
MENIFEE Date Issued: 1 011 0/2 01 7
PERMIT
Site Address: 30168 BRISTOL GATE LN, MENIFEE, CA Parcel Number: 364-370-071
92584 Construction Cost: $7.650.40
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 11 MODULES, 1 INVERTER,2.92kW
LOT 204
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description gyt Amount
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carded on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,orwhere the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpt Page 1 of 1
CUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
�"Y A
Menifee
DATE:09/27/2017 PERMIT/PLAN CHECK NUMBER
TYPE: OCOMMERCIAL KRESIDENTIAL 0 MULTI-FAMILY 0 MOBILE HOME Q POOL/SPA O SIGN
SUBTYPE: DDITION 0 ALTERATION C DEMOLITION 0.ELECTRICAL O MECHANICAL
O NEW 0 PLUMBING 0, RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit- Plan 2399 -2.92kW/ 11 PCS
Master Solar Permit No.: PMT14-02630
PROJECTADDRESS 30168 Bristol Gate Ln ZIP 92584
ASSESSOR'S PARCEL NUMBER 364-370-071 LOT 204 TRAC7.u1a•
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL jeremiah.acayturd@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? :YES )NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302,Corona, CA 92879
PHONE 951-817-3680 EMAIL Jeremiah.aCayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 74 H 6 SOFT L SO FT
APPLICANT'S SIGNATURE DAT�9/27/2017
DEPARTMENT DISTRIBUTION '•� CITYOFMENIFEEBUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIFE ACCEPTED BY:
PERMIT FEE SMIP GREEN ' —
LLAN CHECK FEE INVOICETOTAL �• Le.R BUILDER VERIFIED 0 YES 0 NO DRIVERS LICENSE# NOTARIZED LETTER 0 YES NO
City of Menifee Building&Safety Deportment 29714 Haun Rd. Menifee, CA 92586 9S1-672-6777
www.cityofmenifEe.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM QTY HER. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.915 XW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 1 II PCSI HYUNDAI I HIS-S265RG(265W) BUYER: _—
INVERTER 1 II PCS.1 ENPHASE I 106-60-2-US
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#I 1 ARRAY#2 1 ARRAY#3M
CITY OF ME IFEI
MOD QTY II NA NA BUYER: D S`
TILT 23• NA' NA' City of Menlfee DATE: IilJI NG
AZIMUTH 87- NA' NA- Building Dept
OCT 10 2017 RI:VIEWFn
Received Appmval uf!lu' a tans sh
•pplo�nl of,m,y V ulunon
npclebmts and or manes
pIrmtc mad c9m eliun.
19'-9'ARRAY
20'-7`FLASHING 6'-9'
———— •
OLADECK
RANSITIO WIRE
TRANSITION BOX I
(UNDER ARRAY)
_ l
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER) �.
AC COMBINER 80% ----------� 4
(EXTERIOR-GARAGE)
i fl
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF Z
PLAN 2399 ELEVATION B-LEFT
ORIENTATION 2 LOT#204
CAMELLIA AT LENNAR: ORIGINAL BY:DESIREE WILLIAMS I DATE:17 8.17
980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:I7.8.17
THE LAKES CORONA,CA 92879 RE
BY DATE DESCRIPTION
I DW 17.8.17 10 SWAP. ;?namast;6
toLee
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 30168 BRISTOL GATE LN Boulder,GO 80304
PLOT PLAN 1 1/I6'=I'-0' MENIFEE,CA 303.44T=
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE /CALC UNIT DETAIL
LOCATION MENIFEE,CA INV. MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% "C 37 INV.MODEL INVERTER SPEC 106-60-2-US
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN 'C -2 INV. MAX POWER,(WAC MAX) INVERTER SPEC WATTS(AC) 330
TEMP,MODULE TEST(TTEST) MODULE SPEC "C 25 INV. INPUT V.(VDc MAX) INVERTER SPEC VOLTS(Dc) 48
TEMP.DELTA LOW(TOELTA) THIN-TTEST °C -27 INV.OUTPUT V,(VAC NOM) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD. PART NUMBER MODULE SPEC HIS-S265RG INV, OUTPUT CURRENT, IAC INVERTER SPEC AMPS(AC) 0.96
MOD. POWER STC(P) MODULE SPEC WATTS(DC) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD. POWER PTC MODULE SPEC WATTS(GO 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547 DEI
MOD. OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(DC) 31.30 INV. GROUNDING INVERTER SPEC ISOLATED
MOD. OPEN OCT. VOLTAGE(VOC) MODULE SPEC VOLTS(oc) 38.10 INV,CITY,MAX/BRANCH OCT. INV.QTYBC CITY 11 4
MOD. COEFF. VOLT/TEMP(COEF) MODULE SPEC V/=C -0.114 BRANCH OCT. OUTPUT,IMAXBC I (IAC°INV.QTYBC) AMPS(AC) 1 10.56
MOD. MAX VOLTAGE(VMAXMOD) (VOC+(TD°COEF)) VOLTS(DO) 41.18 INV.QUANTITY, TOTAL I INV.QTYT CITY 1 11
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS 000 8.50 TOTAL SYSTEM OUTPUT,IMAXTS (IAC-INV.QTYT) AMPS(AC) 1 10.56
MOD. SHORT OCT.CURRENT OSC) MODULE SPEC AMPS(Do) 9.00
MOD. MAXIMUM CURRENT(IMAX) (Isc- 1.25) AMPS(oc) 11.25
MIN.AMPACITY REQ'D,PER NEC (IMAX- 1.25) AMPS(DC) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(DC) 15
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 II HYUNDAI HIS-S2657G(265W) PV MODULE SOLAR
2 II ENPHASE IQ6-60-27S PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URS PV AC DISCONNECT,NEMA 3R,240V.30A SOLAR
5 1 ENPRASE 10 ENVOY ENV-IGAMI-240 PV DATA MONITOR, 120V SOLAR
6 1 ENPHASE X-10-AMI-240-B AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER,I X 20A-2P, IX 5A-2P SOLAR
8 I CUTLER-HAMMER TBD PV BREAKER, I X 20A-2P,RATING MAY VARY SOLAR
9 1 TBD TBD SERVICE PANEL,200A BUS BLDR. ELEC.
10 TBD TBD UTILITY METER, IPH, 120/240V,200A BLDR. ELEC.
II TIED TBD GROUNDING ELECTRODE,UFER BLDR. ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COU. (AMPACITY • TEMP. DERATE •FILL DEBATE)VS. REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS vs. REQ'D.(IMAX° 1.25) PANEL HER. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP FILL RESULT REO'D OCO BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 1 22.80 10.56 ALLOWED PV PER NEC AMPS 40
TERM 25 25 13.20 20 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 10.56 INTERCONNECTION CALCS:
TERM 35 35 13.20 20 0.96A X WHOM)= 10s6A OF CURRENT
C #10 CU NM-B COU 40 0.91 1.0 36.40 10.56 10.56A X 1,25= 13.20A
TERM 35 35 13.20 20 TIE-IN WITH A ZOAl2P 2 SPACE PV BACKFEED BREAKER
CONDUCTOR SCHEDULE
KEY 1 CONDUCTORS 1 CU/AL TYPE LOCATION TRADE
A 1-#12 ENPHASE 0 CABLE, 1-#6G,FREE AIR CU UL3003,DO CABLE ARRAY SOLAR
B 1 3-#10, I-#10 EGC CU I NM-B(ROMEX) I INTERIOR I SOLAR
C 13410, -#10.EGC CU NM-B(ROMEX) I INTERIOR I SOLAR
NOTE:NEUTRAL NOT USED AND CAPPED
10
O
:OA/2P
9
SA/2P
O O O
3
O �A/
'N
g � G
A 8 C
I I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.915 KW
LOT#204
ORIGINAL BY:DESIREE WILLIAMS DATE 7.B.17
CAMELLIA AT LENNAR: REVIEWED BY:JIM PARKS I DATE:17.8.I7
980 MONTECITO DRIVE,#302
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION 46.2
1 DW 17.8.17 IQ SWAP namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 4G/1 Broadway Street
PLOT PLAN 2 NITS MENI BE,CA GATE LN Boulder, 7. 80804
ELECTRICAL MENIFEE,CA 303.447.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
D ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE,
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(})SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND I Al :NT
THE EDGE OF THE PV ARRAY/SUB-ARRAY. 1
B)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3%
10 26 GAUGE INTERLOCKING FLASHING"SIDEWALL"TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE Lai A
APROVED PRIOR TO PV SYSTEM INSTALLATION. _
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT W)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF SAVE.PEEL-N-STICK BASE IQ
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
D ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS.BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
10 MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER.DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT�.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110,26.
ORIGINAL BYi DESIREE WILLIAMS DATEi7.6.17
CAMELLIA AT LENNAR. REVIEWED BY:JIM PARKS DATE17.8.17
980.MONTECITO DRIVE,#302
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
I
DW 17.8.17 10 SWAP namasbii
OLA[
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 BmeEwey Street
INDIVIDUAL 30168 BRISTOL GATE LN Boulder,CO 80304
PLOT PLAN 3 NTS MENIFEE,CA 3XL447,0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER&
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
��Z
AC COMBINER BOX
(EXTERIOR-GARAGE)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 10.56A
I PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:DESIREE WILLIAMS DATE97.8.17
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE,4302 REVIEWED BY:UIM PARKS DATE:17.8.17
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
DW 17,8.17 10 SWAP Vnamast6
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
INDIVIDUAL 4B l or,GO yXYA
PLOT PLAN L NTS MENI EE,CA L GATE LN Ba301 C08D304
PLACARDS MENIFEE,CA 303.447.0300