PMT17-03469 City of Menifee Permit No. PMT17-03469
29714 HAUN RD. Type: Residential Electrical
<NCCELA.. MENIFEE, CA 92586
MENIFEE Date Issued: 1 0/1 912 01 7
PERMIT
Site Address: 29028 BOTANICAL CIR, MENIFEE, CA Parcel Number:
92584 Construction Cost: $8,017,20
Existing Use: Proposed Use:
Description of SOLAR TR 31582 HERITAGE HEIGHTS
Work: 10 MODULES, 1 INVERTER, 3.20 kW
LOT 67
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description O ( Amount(SI
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise staled,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_BIdgPennit_Templ ate.rpt
Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
Menifee
DATE:09/25/2017 PERMIT/PLAN CHECK NUMBER
TYPE: 0 COMMERCIAL <ESIDENTIAL 0 MULTI-FAMILY 0 MOBILE HOME O POOL/SPA SIGN
SUBTYPE: DDITION 0 ALTERATION 0 DEMOLITION 0 ELECTRICAL 0 MECHANICAL
O NEW 0 PLUMBING £; RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit- Plan 2686 - 3.20 kW/ 10 PCS
Master Solar Permit No.: PMT17-00129
PROJECTADDRESS 29028 Botanical Cir ZIP 92584
ASSESSOR'S PARCEL NUMBER TBD LOT 67 TRACT31582
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito DR., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? 0 YES Cr NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 8017.20 SQ.FT L SQ FT
APPLICANT'S SIGNATURE DATE 09/25/2017
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIFE ACCEPTED BY:
PERMIT FEE SMIP GREEN
PLAN CHECK FEE INVOICE TOTAL &,v
OWNER BUILDER VERIFIED 0,YES 0 NO DRIVERS LICENSE# NOTARIZED LETTER YES 0 NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee,. CA 92586 951-672-5777
www.cityofmenifee.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM QTY MI MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.200 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE IO PCS.l LG I LG320EIK-A5(32OW) BUYER:
INVERTER 1 IO PCS.1 ENPHASE I IQ6PLUS-72-2-US
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#MNA'
MOD OTY 10 NA NA BUYER:
TILT 23° NA' NA°
AZIMUTH 222• NA' NA' DATE:
City of Menifee
3' Building Dept
CT 0 5 20V
Received
,_
�a U
P-
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
CITYDISCONNECT
F MENIF O
BU[L ING A 4Cons
PARTME
PLAN PPRO PV E IOR-GARAG
EXTERIOR-GARAGE 1
REVIE ED BY I1 MAIN METER a v
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
DATE
,nval (these Pla d Io he a AC COMBINER BOX
d o,any viola ��Opc
oranI the lederal, liv Plans mustI'on
the
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2606 ELEVATION B-RIGHT ®�
ORIENTATION 4 LOT#67
LENNAR: ORIGINAL BY:ANGELA BURKE DAT :09.20.1
HERITAGE HEIGHTS 2603 CAMINO RAMON#525 REVIEWED BY:ARTHUR HICKS DATE:09.21.n
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION
P- mamast;6
anraR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29028 BOTANICAL CIRCLE Bouldw,CO 803N
PLOT PLAN /Ib'=I'-0" MENIFEE.CA 303.447.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 10 LG LG32CEIK-A5(320W) PV MODULE SOLAR
2 10 ENPHASE 1Q6PLUS-72-2-US PV INVERTER SOLAR
3 1 REPO/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT, NEMA 3R.24OV,30A SOLAR
5 1 ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR, 120V SOLAR
6 1 ENPHASE X-IQ-AMI-240-8 AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER,I X 20A-2P,I X 5A-1P SOLAR
8 1 CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P.RATING MAY VARY SOLAR
9 1 TBD TBD SERVICE PANEL,200A BUS BLDR. ELEC.
10 TBD TBD UTILITY METER,IPH,120/240V,200A BLDR. ELEC.
II TBD TBD GROUNDING ELECTRODE.]JEERBLDR ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL HER. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% 'C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN 'C -2 MAIN DISCONNECT AMPS 2DO
TEMP, MODULE TEST(TTEST) MODULE SPEC 'C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TDELTA) THIN-TTEST 'C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALCS:
MOD. PART NUMBER AC MODULE SPEC LG320NIK-A5(320W) 1.17A X m(MODS)= 11]0A OF CURRENT
MOD. POWER STC(P) AC MODULE SPEC WATTS CDC) 320 11.70A x L25= 14.63A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 790 TIE-IN WITH A 20A/2P 2 SPACE PV RACFFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC HZ(AC) 60/59.3-605
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741 / IEEEI547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD. OTY BC OTY 10
BRANCH CIRCUIT OUTPUT, IMAXBC (IAC'MOD.QTY SO AMPS(AC) 11.70
AC MODULE QUANTITY,TOTAL MOD. QTY T QTY Ip
TOTAL SYSTEM OUTPUT IMAXTS (IAC'MOD. CITY T) AMPS(AC) 11.70
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COU) (AMPACITY• TEMP. DEBATE • FILL DEBATE)vs. RED (TMAX)
2) TERMINALS(TERM). AMPACITY AT TERMINALS. 05. REG'D,(TMAX • 1,25)
KEY SIZE CU/AL INSULATION CALC AMPACITY W/0 TEMP. FILL RESULT REOD OCD
TYPE DEBATES DEBATE BERATE (A) (A) USED(A)
A #12 LU THWN-2 COU 30 .7fi L0 22.80 11.70
TERM 25 25 14.63 20
B #10 CU NM-B COU 40 .91 1.0 36.40 11.70
TERM 35 35 14.63 20
C #70 CU NM-B COU 40 .91 1.0 36.40 11.70
TERM 35 35 14.63 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS 1 CU/AL TYPE 1 LOCATION TRADE
A 1 1-#12 ENPHASE Q CABLE, 146G,FREE AIR I CU TC-ER JARRAY SOLAR
B 1 3410. 1-#10 EGG I CU NM-B CROMEX) I INTERIOR I SOLAR 0
C 3-#10, I-#I0 EGC I CU I NM-B(ROMEX) I INTERIOR I SOLAR O
9
5 O4
suzP O
Q zau
20A/ZP
._ .._.._ _.T
..D N
A B C C = II
I I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 3.20OKW
LOT#67
ORIGINAL BY:ANGELA BURKE DATE:09,20.
LENNAR: 17
HERITAGE HEIGHTS REVIEWED BY:ARTHUR HICKS DATE09.21.17
2603 GAMING RAMON#525
SAN RAMON.CA 94583 REV.# BY DATE DESCRIPTION
namasrd
SOLAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
treet
INDIVIDUAL 4Bo Broadway 304
PLOT PLAN 2 NTS 29028 BOTANICAL CIRCLE Boulder,CO3004
ELECTRICAL MENIFEE,CA 303.447.000
INSTALLATION NOTES.
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48,O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3"ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(J')SPACE BETWEEN PV MODULES. SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(29 BEYOND
THE EDGE OF THE PV ARRAY/SUB ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3
IU 26 GAUGE INTERLOCKING FLASHING"SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(I)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
15)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF SAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703. IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS,
10)DO WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
IU MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS. WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
I5)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT e.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED"PHOTOVOLTAIC POWER SOURCE,"OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:ANGELA BURKE JDATED9.20.17
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ARTHUR HICKS DATE99.21.17
2603 CAMINO RAMON#525
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION tit
masCB
bOLAL
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4571eer,CO Street
INDIVIDUAL 29020 BOTANICAL CIRCLE Boulder, 80304
PLOT PLAN 3 NTS
NOTES MENIFEE.CA 3033.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
TRI ICI N 8
(WEER WP1YI
PV PC OISCeNNECY
EXiEPIOP-4CRi6E
Ty!PUB.
MPIN fFRVIf£PYJEL
IVERIflEN BY 9111L1¢RI
PC CP`I&NEfl BO%
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 11.70A
I PC., NEC 690.54 I PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:ANGELA BURKE DATEC9.20.17
HERITAGE HEIGHTS LENNAR:2603 CAMINO RAMON#525 REVIEWED BY:ARTHUR HICKS JDATE,0921.I7
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION tit
mast6
fo1.nf
DWG TITLE: PAGE#: I SCALE: .SITE LOCATION:
INDIVIDUAL 4571l mr, 304
PLOT PLAN 4 NTS MENIF BOTANICAL CIRCLE Boulder,C000303W
PLACARDS MENIFEE,CA 303.447.0300