PMT17-03467 City of Menifee Permit No.: PMT17-03467
29714 HAUN RD. Type: Residential Electrical
A'' MENIFEE, CA 92586
MENIFEE Date Issued:
10/19/2017
PERMIT
Site Address: 29056 BOTANICAL CIR, MENIFEE, CA Parcel Number:
92584 Construction Cost: $8,017.20
Existing Use: Proposed Use:
Description of SOLAR TR 31582 HERITAGE HEIGHTS
Work: 8 MODULES, 1 INVERTER,2.56kW
LOT 65
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant Phone: 9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description Qtv Amount ISI
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Pennit_Template.rpt Page 1 of 1
BUILDING SAFETY PERMIT/PLAN APPLICATION
A Menifee
DATE:09/25/2017 ,,// PERMIT/PLAN CHECK NUMBER 1 1 n-
TYPE: 0 COMMERCIAL ,- ESIDENTIAL 0 MULTI-FAMILY 0 MOBILE HOME ') POOL/SPA G SIGN
SUBTYPE: /<ADDITION 0 ALTERATION 0 DEMOLITION n ELECTRICAL 0 MECHANICAL
O NEW O PLUMBING '> RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit- Plan 2131 - 2.56 kW /8 PCS
Master Solar Permit No.: PMT17-00129
PROJECTADDRESS 29056 Botanical Cir Zip 92584
ASSESSOR'S PARCEL NUMBER TBD LOT 65 TRACT31582
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito DR., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL Jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNERBUILDER? OYES ONO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 8017.20 S L SQ FT
APPLICANT'S SIGNATURE DATE 09/25/2017
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
B
BUILDING PLANNING ENGINEERING FIRE ACCEPTED Y:
PERMIT FEE I 0AL00SMIP Ol GREEN
PLAN CHECK FEE INVOICE TOTAL v
OWNER BUILDER VERIFIED ^.YES - NO DRIVERS LICENSE# NOTARIZED LETTER YES L? NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.citycfmenifee.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM KPCS.1
R. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE LG320EIK-A5 MDR) BUYER:
INVERTERPHASE I 106PLUS-72-2-US
ROOF TYPE I TILE Wf COMPOSITE SHINGLE UNDER ARRAY DATE: -
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3 ARRAY#4
MOD CITY 1 8 NA NA NA BUYER: — - - - -
TILT 23° NA° NA° NA'
AZIMUTH 1 252 RA. NI NA-
city
City of Meniiee
Building Dept
5'-6" ,3'
OCT 0 5 2017
Received
V
�aa
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT ^
CITY OF ME IFE1" TNTNT
EXTERIOR-GARAGE V
BUILDING A D S ,
UTILITY METER 8
MAIN SERVICE PANEL
PLAN APPRIC j
lop (VERIFIED BY BUILDER)
4g!! t AC COMBINER BOX
REVIEWED BY D,�I
Approval of these plans shall not Inc wretrucd to be a pe s
or an
V o
approval of,any violation of any prow uiuns ot'Ihe Cederal, r city
e 1 the
rrgulanar,;:u ul ordinances.THIS scl of approved plans to p
pbsltc until comPlcllon.
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF ^,
PLAN 2131 ELEVATION C-RIGHT ®'V
ORIENTATION I LOT#65
LENNAR: ORIGINAL BY:ANGELA BURKE DATE:09.20.17
HERITAGE HEIGHTS 2603 CAMINO RAMON#525 REVIEWED BY:ARTHUR HICKS I DATE:09.21.17
SAN RAMON,CA 94593 REV.# BY DATE DESCRIPTION
�Pmamast;6
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29056 BOTANICAL CIRCLE BmIdw.CO 80304
PLOT PLAN 1 I/16"=1'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 8 LG LG320EIK-A5(32OW) PV MODULE SOLAR
2 8 ENPHASE I06PLUS-72-2-US PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V,30A SOLAR
5 1 ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR, 120V SOLAR
6 1 ENPHASE X-10-AMI-240-B AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER, I X 20A-2P. I X 5A-IP SOLAR
B I CUTLER-HAMMER TRIG PV BREAKER,I X 2OA-2P,RATING MAY VARY SOLAR
9 1 TBD TBD SERVICE PANEL,200A BUS BLDR. ELEC.
IO TBD TBp
UTILITY METER, IPH,120/24OV,200A BLDR. EL EC.
11 TBD TBD GROUNDING ELECTRODE,UFER BLDR. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL HER. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% •C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN -C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC 'C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TDELTA) THIN-TTEST •C -27 PV COED DEVICE USED AMPS 1 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALLS:
MOD. PART NUMBER AC MODULE SPEC LG320NIK-A5(327W) 1.17A X e(MODS)= 9.36A OF CURRENT
MOD. POWER STC OF) AC MODULE SPEC: WATTS(DO 320 9.36A X 1.25= I130A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A 20A/2P 2 SPACE PV BACKFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC H2(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741I IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY.MAX.PER BRANCH CIRCUIT MOD. OTY BG OTY 8
BRANCH CIRCUIT OUTPUT,IMAXBC 0AC'MOD.OTY BO) AMPS(AC 9.36
AC MODULE QUANTITY,TOTAL MOD. QTY T QTY 8
TOTAL SYSTEM OUTPUT IMAXTS (IAC'MOD. OTY T) AMPS(AC) 1 9.36
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(LOU) (AMPACITY • TEMP.DERATE - FILL DEBATE)VS.REG'D(TMAX)
2)TERMINALS(TERM): AMPACITY AT TERMINALS. vti. REG 0(TMAX' 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REO'D OCD
TYPE DERATES DEBATE DEBATE (A) (A) USED(A)
A #12 CU THWN-2 COU 30 .76 1 1.0 22.80 9.36
TERM 25 1 25 11.70 20
B #10 CU NM-B COU 40 .91 I:0 36.40 9.36
TERM 35 35 11.70 20
C #10 CU L0 NMI COU 40 .91 36.40 9.36
TERM 35 35 11.70 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS CORAL TYPE LOCATION 1 TRADE
A 1-#12 ENPHASE Q CABLE, -#6G,FREE AIR I CU TC-ER ARRAY I SOLAR
B 3410, 1-#10 EGG CU I NM-B(ROMEX) I INTERIOR I SOLAR 10
C 3410, I-#10 EGG CU NM-B(ROMEX) INTERIOR I SOLAR
O
5 44
snnP
zaO
0
xonr
�_ N
A B C C = II
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.56OKW
LOT#65
ORIGINAL BY:ANGELA BURKE 1 DATE:09.20.17
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ARTHUR HICKS I DATE:09.21.17
2603 CAMINO RAMON#525
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION
namasbe
lOLA4
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
4571 Broadway Street
INDIVIDUAL 29056 BOTANICAL CIRCLE BO303.4 7030304
PLOT PLAN 2 NTS
ELECTRICAL MENIFEE,CA 03.44 .000
INSTALLATION NOTES:
SOLAR CONTRACTOR-
I)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48"O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3"ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH({')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(29 BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8).UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3".
IU 26 GAUGE INTERLOCKING FLASHING"SIDEWALL"TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT OH)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730.
6)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS,
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAWLIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT J''.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19) INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:ANGELA BURKE DATEO9.20.17
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ARTHUR HICKS DATE09.21.17
2603 CAMINO RAMON#525
SAN RAMON,CA94583 REV.# BY DATE DESCRIPTION
Vnamcist6
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 4571 Broadway GO8Street
PLOT PLAN 3 NTS 29056 BOTANICAL CIRCLE Boulder,
014 7, 0304
NOTES
MENIFEE,GA 03.4470300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER e
MAIN SERVICE PANEL
ERIFIED BY BUILDER)
"":AC�—z
COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 9.36A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:ANGELA BURKE DATE:09.20.17
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ARTHUR HICKS DATEo09.21.17
SAN AMOCAMINO RA945 #525
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION
Vnicimasri§
mva
DWG TITLE: PAGE#: SCALE: SITE LOCATION-
4Bo Ber,GO6dway 3D4
INDIVIDUAL MENIF BOTANICAL CIRCLE Boulder, 7030004
PLOT PLAN 4 NTS MENIFEE,CA 303:447.0300
PLACARDS