PMT17-03466 City of Menifee Permit No.: PMT17-03466
29714 HAUN RD. Type: Residential Electrical
qq%C:CEL^'J' MENIFEE,CA 92586
MENIFEE Date Issued: 10l19/2017
PERMIT
Site Address: 29084 BOTANICAL CIR, MENIFEE, CA Parcel Number:
92584 Construction Cost: $8,017.20
Existing Use: Proposed Use:
Description of SOLAR TR 31582 HERITAGE HEIGHTS
Work: 10 MODULES, 1 INVERTER,3.20 kW
LOT 64
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant phone: 9493498269
JEREMIAH ACAYTURRI License Number: 728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description Qty Amount t51
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Men'rfee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
Menifee
DATE:09/25/2017 PERMIT/PLAN CHECK NUMBER M,O
-- -TI-FAMILY O MOBILE HOME 0 POOL/SPA O SIGN
DEMOLITION O ELECTRICAL O MECHANICAL
)OF NUMBER OF SQUARES
DE.
Ah I
Q V 3.20 kW/ 10 PCS
1
Mav
pp
Pe�[-
hTs92584
PRC PA
ZIP
ASSI ase � _ LOT 64 TRAcr31582
OWI
ADD Solo r 1,Wm.1 S ;A 92879
PHOI /� _ � jeremiah.acayturri@lennar.com
APPL, Dmes of California, Inc.
ADDRESS `u Ivlunteato DR., Suite 302, Corona,. CA 92879
PHONE 951-817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACrOWS NAME Lennar Homes of California, Inc. OWNER BUILDER? OYES `NO
BUSINESS NAME Lerner Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL Jeremiah.acayturd@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 8017.20 SQ Fr L SQ FT
APPLICANT'S SIGNATURE DATE 09/25/2017
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE ACCEPTED BY.
PERMIT FEE I.t.�oO SMIP a GREEN
L'LAN CHECK FEE INVOICETOTALI� LQO
R BUILDER VERIFIED OYES O NO DRIVERS LICENSE# NOTARIZED LETTER YES ? NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityofimenifee.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM 1 OTY HER. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.200 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 1 10 PCS.1 LG I LG3ZOEIK-A5(3200) BUYER:
INVERTER 1 10 PCS.1 ENPHASE I IO6PLUS-72-2-1JS
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3 ARRAY#4
MOD CITY 10 NA NA NA BUYER:
TILT 1 23° 1 NA' I NA- NA°
AZIMUTH 259° 1 NA- I NA- NA° DATE:
City of Menifee
Building Dept
3'
OCT 0 5 2017
eceived
,_
Va
SOLADECK WIRE
TRANSITION BOX I
(UNDER ARRAY)
OF MENIFEE
EXTERIORS-`GANRAAGe L G AND SAFET PARTM ' T O
P ATAP OVAL
UTILITY METER e
MAIN SERVICE PANEL 1
(VERIFIED BY BUILDER)
R Ewr:OBY 000
AC OONBINER BO% DA"FE
A r v of these planqp�sha 1 not he co
ed to be a pe it for,or an
ap v of,any vinlatii#Wn .n1)provision of the federal,slate or city
rcg s and ordinam es. pans most he kept on the
jobsite mlil completion.
NOTE: DIMENSIONS ARE SHOWN IN PLANE OF ROOF Ar
PLAN 2686 ELEVATION A-LEFT ®
ORIENTATION I LOT#64
LENNAR: ORIGINAL BY:ANGELA BURKE DATE:09.20.17
HERITAGE HEIGHTS 2603 CAMINO RAMON#525 REVIEWED BY:ARTHUR HICKS I DATE09.2I.17
SAN RAMON,CA 94583 REV.# BY I DATE I DESCRIPTION 2. namast8
souv
DWG TITLE:. PAGE #: I SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29084 BOTANICAL CIRCLE Boulder,DO 80304
PLOT PLAN I/16" =V-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY CITY I MANUFACTURER MODEL NOTES TRADE
10 LG LG320EIK-AS(320W) PV MODULE SOLAR
2 IQ ENPHASE IG6PLUS-72-2-US PV INVERTER SOLAR
3 I RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,24OV,30A SOLAR
5 1 ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR, 120V SOLAR
6 1 ENPHASE X-10-AMI-240-8 AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER,I X ZOA-2P, 1 X 5A-IP SOLAR
8 1 CUTLER-HAMMER TBD PV BREAKER, I X 20A-2P.RATING MAY VARY SOLAR
9 1 TBD TBD SERVICE PANEL,200A BUS BLDR. ELEC.
10 1 TBD TBD UTILITY METER, IPH, 120/24OV,200A im BLDR. ELEC.
II 1 TBD 1 TBD 1
GROUNDING ELECTRODE,UFER BLDR ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL HER. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TDELTA) THIN-TTEST IF -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALCS:
MOD.PART NUMBER AC MODULE SPEC LG320NIK-A5(32OW) 17A X WHOM)= 11.70A OF CURRENT
MOD.POWER STC(P) AC MODULE SPEC WATTS(DC) 320 II.70A x I.25= I4.63A
PEAK OUTPUT POWER STG(P) AL MODULE SPEC WATTS(AC) 290 1 TIE-IN WITH A 20A/2P 2 SPACE PV BACKFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC j WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY 7 RANGE AC MODULE SPEC H2(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741 7 IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY, MAX PER BRANCH CIRCUIT MOD. OTY ac CITY 10
BRANCH CIRCUIT OUTPUT.IMAXBC 0AC'MOD.QTY BC) AMPS(AU 11.70
AC MODULE QUANTITY,TOTAL MOD. CITY T GTY 10
TOTAL SYSTEM OUTPUT IMAXTS (IAC`MOD. QTY T) AMPS(AC) 11270
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COO): (AMPACITY- TEMP. DEBATE •FILL DERATE)v .RED(TMAX)
2)TERMINALS(TERM). AMPACITY AT TERMINALS. YS.REO'D,(IMAX• 1.25)
KEY SIZE CU/AL INSULATION GALS. AMPACITY W70 TEMP. FILL RESULT REQ'D OCD
TYPE DERATES DERATE DERATE (A) (A) USED(A)
A #12 CU THWN-2 COU 30 .7 11.0 22.80 11.70
TERM 25 25 14.63 20
B #10 CU NM-B COU 40 .91 L0 36.40 11.70
TERM 35 35 14.63 20
C *10 CU NM-B COU 40 .91 1.0 36.40 11.70
TERM 35 35 14.63 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS CWAL TYPE LOCATION TRADE
A 1-#12 ENPHASE 0 CABLE, 1-#6G,FREE AIR LU TC-ER ARRAY SOLAR
B 3-#10, I-#IO EGC I CU I NM-B(ROMEX) I INTERIOR I SOLAR 10
C 3-#10, 1-#10 EGG I CU I NM-B(ROMEX) I INTERIOR I SOLAR _
O
9
5
5A/2P a
O � O
� ° Lz0alz
A B C C = II
I I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 3.20OKW
LOT#64
ORIGINAL BY:ANGELA BURKE DATE:09.20.17
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ARTHUR HICKS I DATE:09.21.17
2603 CAMINO RAMON#525
SAN RAMON.CA 94583 REV.# BY DATE DESCRIPTION
namast�
.G, .
DWG TITLE: PAGE#: SCALE:. SITE LOCATION:
INDIVIDUAL 4571 CO
8 SBeet
29084 BOTANICAL CIRCLE Boulder,,C780369
PLOT PLAN 2 NTS
ELECTRICAL MENIFEE,CA 303.44.0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
1)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48,O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S.INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3"ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(}')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND
THE EDGE OF THE PV ARRAY/SUB ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
11)26 GAUGE INTERLOCKING FLASHING"SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 09 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE,
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED-OVERTILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO.INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING.NOTING THAT TERMINAL LUGS BOLTED.ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED,
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT J'.
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE,"OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY:ANGELA BURKE DATE09.20.17
HERITAGE HEIGHTS LENNAR: REVIEWED BY:ARTHUR HICKS DATEO9.2L17
2603 CAMINO RAMON#525
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION
Vnamasrd
wue
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4571 Broadway Street
INDIVIDUAL
PLOT PLAN 3 NTS 29084 BOTANICAL CIRCLE Ban 303. 80004
NOTES MENIFEE,CA 3.447,70300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLAOEC.WIRE
TRANSITION BO%
(UNDER ARRAY)
PV AC DISCONNECT
ESTERIOR-GARAGE
unum METER A
MAIN SERVICE PANEL
(VH IFIED BY BUILDER)
AC COMBINER BOX Ls
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 11.70A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
LENNAR: ORIGINAL BY:ANGELA BURKE DIHERITAGE HEIGHTS REVIEWED BY:ARTHUR HICKS DI2fiO3 CAMINO RAMON#525
SAN RAMON,CA 94583 REV.# BY DATE DESCRIPTION
Vnamasb6
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION'
INDIVIDUAL 45TI dew,C a8 Street
290B4 BOTANICAL CIRCLE
PLOT PLAN 4 NTS Boullder, 030304