PMT17-03460 City of Menifee Permit No.: PMT17-03460
29714 HAUN RD.
�RCCEL/kT MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 1 010 6/2 01 7
PERMIT
Site Address: 29143 BOTANICAL CIR, MENIFEE, CA Parcel Number:
92584 Construction Cost: $8,017.20
Existing Use: Proposed Use:
Description of SOLAR TR 31582 HERITAGE HEIGHTS
Work: 10 MODULES, 1 INVERTER 3.20kW
LOT 75
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant Phone: 9493498269
JEREMIAH ACAYTURRI License Number: 728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description -q Amount($I
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg Permit Template.rpt Page 1 of t
SAFETYBUILDING & PERMIT/PLAN CHECK APPLICATION
"Menifee
DATE:09/25/2017 PERMIT/PLAN CHECK NUMBER
TYPE: O COMMERCIAL RESIDENTIAL a MULTI-FAMILY O MOBILE HOME O POOL/SPA O SIGN
SUBTYPE: <ADDITION O ALTERATION O DEMOLITION O ELECTRICAL O MECHANICAL
4EW O PLUMBING 0 RE-ROOF NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit- Plan 2686 - 3.20 kW/ 10 PCS
Master Solar Permit No.: PMT17-00129
PROJECTADDRESS 29143 Botanical Cir Zip 92584
ASSESSOR'S PARCEL NUMBER TBD LOT 75 TRACT31582
OWNER NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr. Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito DR., Suite 302, Corona, CA 92879
PHONE 951-817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? O YES ONO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Carona, CA 92879
PHONE 951-817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ 8017.20 SQ FT L SO FT
APPLICANT'S SIGNATURE DATE 09/25/2017
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE ACCEPTED BY:
PERMIT FEE y� SMIP a GREEN '
PLAN CHECK FEE INVOICE TOTAL L4. 6
OWNER BUILDER VERIFIED OYES O NO DRIVERS LICENSE!! NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM Q 1 HER. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.200 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE I0PCS.I LG I LG320EIK-A5(3207) BUYER: —_—
INVERTER 1 IO PCS.I ENPHASE I 06PLUS-72-ACM-US
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3 ARRAY#4
MOD OTY 10 NA NA NA BUYER
-
TILT 23' NA' NA' NA'
AZIMUTH 1 270' NA' NA' NA' DATE: —
City of Menifee
Building Dept
3 111'
C �17
N
ZI
Q LL
SOLADECK WIRE 4
TRANSITION BOX
(UNDER ARRAY)
CITY OF MENIFF.E
BUILDING AND SAFLTY DEP RTMENT
PLAN APPROVAL
O PV E DISCONNECT
A'
EXTERIOR-GARAGE
REVILWEDBY-- DAL UTILITY METER P
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
Approval of these plans shall not he construed o be a pertnit r,or an �P
apploval of,.mv L od HI , -� m1 I-""'1*ions of he federal,sla a or elty AC COMBINER BOX
rcgolm".11,;u.., ,i:u:.;.r,_s Ins sct of approv d plans must kept on the .
jobsde 1.11141 L.umplcuon.
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF '
PLAN 2628 ELEVATION B-RIGHT
ORIENTATION 3 LOT#75
LENNAR: ORIGINAL BY:CHRISTINE MARTINI DATE:17.07.11
HERITAGE HEIGHTS 980 MONTECITO DRIVE, #302 REVIEWED BY:JIM PARKS DATE:1707AI
CORONA,CA 92879 REV.# BY DATE DESCRIPTION C�i i9
Gre namasbtb
SOLAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
4671 Broadway Street
INDIVIDUAL
29I43 BOTANICAL CIR Boulder,0080304
PLOT PLAN 1 I/16"=I'-D" MENIFEE,CA 303447.0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY QTY I MANUFACTURER MODEL NOTES TRADE
1 10 1 LG LG320NIK-A5(520W) PV MODULE SOLAR
2 10 I ENPHASE 106PLUS-72-ACM-US PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 I CUTLER-HAMMER DG2211JRB PV AC DISCONNECT,NEMA 3R,240V.30A SOLAR
5 1 ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR, I20V SOLAR
6 1 ENPHASE X-IQ-AMI-240-B AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER,I X 20A-2P. I X 5A-IP SOLAR
8 1 CUTLER-HAMMER TBD PV BREAKER, I X 20A-2P,RATING MAY VARY SOLAR
9 1 TBO TBD SERVICE PANEL.200A BUS BLDR. ELEC.
10 1 TBD TBD UTILITY METER, IPH, 120/24OV,ZOOA BLDR. ELEC.
II 1 TBD TBD GROUNDING ELECTRODE,UFER BLDR. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE.CA PANEL MFR. CUTLER-HAMMER
TEMP,AMBIENT HIGH(TMAN) ASHRAE 2% 'C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(TMIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP, MODULE TEST(TTEST) MODULE SPEC •C 25 ALLOWED PV PER NEC AMPS 40
TEMP,DELTA LOW(TEELTA) THIN-TTEST °C -27 PV OCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALCS:
MOD. PART NUMBER AC MODULE SPEC LG320NIK-A5 WOW) I.RA X IO(MODS)= 11.10A OF CURRENT
MOD. POWER STC(P) AC MODULE SPEC WATTS(DC) 320 II.70A x 1.25= 14.53A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A 20A/2P 2 SPACE PV BACKFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT OAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC H2(AC) 60/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC UL1741/IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY,MAX PER BRANCH CIRCUIT MOD, OTY Be QTY 10
BRANCH CIRCUIT OUTPUT, IMAXRC (IAC'MOD.OTY Be) AMPS(AC) 11.70
AC MODULE QUANTITY,TOTAL MOD. QTY T QTY Ip
TOTAL SYSTEM OUTPUT IMAXTs (IAC-MOD. QTY T) AMPS(AC) 11.70
CONDUCTOR SIZING CALCULATIONS
1)CONDITION OF USE(COK (AMPACITY• TEMP.DERATE - FILL DEBATE)Ls— (IMAX)
2)TERMINALS(TERM). AMPACITY AT TERMINALS- vs. REWD.(IMAX• 1.25)
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULTg(A) USED(A)
TYPE OERATES DERATE DERATE (A)A #12 CU THWN-2 COU 30 .76 1.0 22.80TERM 25 25 B #10 CU NM-B COU 40 .91 L0 36.40TERM 35 35 C #10 CU NM-B COU 40 .91 L0 36.40TERM 35 35
CONDUCTOR SCHEDULE
KEY 1 CONDUCTORS CU/AL TYPE LOCATION TRADE
q -.C12 ENPHASE Q CABLE, I-#6G,FREE AIR CU TC-ER ARRAY SOLAR
B 3-#10,I-#10 EGC CU NM-B(ROMEX) I INTERIOR I SOLAR 10
C 3410,1410 EGC I CU I NM-B(ROMEX) I INTERIOR I SOLAR
O
9
5 Q
aIP O
O xi12
A
20 /3
r7 G_IN
A B D c z 11
I I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 3.200 Kw
LOT# JS
ORIGINAL BY:CHRISTINE MARTINI DATE:17.07.11
HERITAGE HEIGHTS LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE17.07.11
CORONA,CA 92879 REV.# BY DATE DESCRIPTION
�PmamastdMA.
eoiA¢
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 45]1lder,D 8Streel
PLOT PLAN 2 NTS MENI BOTANICAL CIR Boulder, 7030304
ELECTRICAL MENIFEE,CA 303.44].0300
INSTALLATION NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE PORTION OF ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
APRIL 2016 EDITION.
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(")SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
10)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
II)26 GAUGE INTERLOCKING FLASHING'SIDEWALU'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
12)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT OD OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE
TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
13)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
14)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE UNLESS PV ARRAY IS SPECIFIED TO BE INSTALLED OVER TILE.
BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
])ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 201L.NEC,
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT i
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED"PHOTOVOLTAIC POWER SOURCED OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26,
ORIGINAL BY:CHRISTINE MARTINI DATE17.07.11
HERITAGE HEIGHTS LENNAR: REVIEWED BY:JIM PARKS DATETOT11
980 MONTECITO DRIVE,#302 •�
CORONA,CA 92879 REV.# BY DATE DESCRIPTION
n MCII
soue
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4571 Broadway Street
INDIVIDUAL
PLOT PLAN 3 NTS ENI BOTANICAL SIR Boulder,GOBO804
M
NOTES ENIFEE,CA 303_dd].0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOt ECI(WIRE
TRANSITION BGx
(UNDER ARRAY)
PV AC DISCONNECT
E%TERIOR-GARAGE
UrILITY METER G
MAIN GERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BO%
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 11.70A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:CHRISTINE MARTINI DATE:17.07.11
980 HERITAGE HEIGHTS LENNAR: REVIEWED BY:JIM PARRS DATE:17.07.11
CORONA,CA,CA
DRIVE,#3O2 O 92879 REV.# BY DATE I DESCRIPTION
VnamasI56
30LAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4B Broadway Street
OAL 29143 BOTANICAL CIR BGDldeq 803M C0
PLOTT PLAN 4 NTS LACARDS MENIFEE,CA
303.447.0300
P