PMT17-03198 City of Menifee Permit No.: PMT17-03198
29714 HAUN RD. Type: Commercial Electrical
'CAC CELA> MENIFEE, CA 92586
MENIFEE Date Issued: 09/13/2017
PERMIT
Site Address: 31721 EATON LN, MENIFEE, CA 92584 Parcel Number:
Construction Cost: $5,000.00
Existing Use: Proposed Use:
Description of 100A METER PEDESTAL
Work: STA 13+69
TR30142-2
Owner Contractor
KB COASTAL, INC. KB HOME COASTAL INC
36310 INLAND VALLEY DR. 10990 WILSHIRE BLVD SUITE 700
WILDOMAR, CA 92595 LEGAL DEPT
Applicant phone: 3102314000
KB HOME COASTAL INC License Number:630879
10990 WILSHIRE BLVD SUITE 700
LEGAL DEPT
LOS ANGELES, CA 90024
Fee Description Qty Amount
Services, Switchboards, Control Centers&Panels 1 183.00
Building Permit Issuance 1 27.00
Additional Plan Review Building 148 148.37
GREEN FEE 1 1.00
General Plan Maintenance Fee-Electrical 1 9.15
$368.52
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg Permit_Tempiatespt Page 1 of 1
. APPLICATION
Menifee 2
DATE 08/11/17 PERMIT/PLAN CHECK NUMBER
TYPE: ❑COMMERCIAL ®RESIDENTIAL MULTI-FAMILY ❑MOBILEHOME POOL/SPA []SIGN
SUBTYPE: []ADDITION []ALTERATION ❑DEMOUTION ❑ELECTRICAL ❑MECHANICAL
✓❑NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Address Assignment and Pedestal Permit
Location: West side of Eaton Lane Across Street from lot 136-Station 13+69 (see exhibit)
PROJECTADDRESS 21 Eaton Lane
ASSESSOR'S PARCEL NUMBER 360-180-009 LOT TRACT 30142-2
PROPERTY OWNER'S NAME KB Home Coastal, Inc.
ADDRESS 36310 Inland Valley Drive,Wildomar CA 92595
PHONE 951-691-5300 EMAIL clarsen@kbhome.com
APPLICANT NAME KB Home Coastal,Inc.
ADDRESS 36310 Inland Valley Drive,Wildomar CA 92595
PHONE 951-259-1495 EMAIL marcielavallee5l@gmail.com
CONTRACTOR'S NAME OWNER BUILDER? ❑YES❑NO
BUSINESS NAME KB Home Coastal,Inc.
ADDRESS 36310 Inland Valley Drive,Wildomar CA92595
PHONE 951-691-5300 EMAIL clarsen@kbhome.com
CONTRACTOR'S STATE LIC NUMBER 630879 LICENSE CLASSIFICATION B
VALUATION$ 5000,00 SQ FT LSQFT
APPLICANT`SSIGNATURE-- DATE 08/11/17
CITY STAFF USE ONLY�W
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS UCENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE PAIDAMOUNi
AMOUNT L 1 OCASH OCHECK# OCREDITCARD VISA/MC
PLAN CHECK FEES PAIDAMOUNi OCASH OCHECKn OCREDITCARD VLSA/MC
OWNER BUILDER VERIFIED OYES O NO DLNUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Deportment 29714 Noun Rd. Menifee, CA 92535 951-672-5777
www.cityofinenifee.us Inspection Request Line 951-246-6213
=- rn Z O
O D m
o W O i D Z p T �
m
a = r to m
s � n -
v o m iE
a n o D
c � v
N a rn
m
ro o Z
00
m N
e v
EM
o x pa '
4 69 d
owe
`.\.I t
b ; Fig
W
SOUIIIERN CAUIORNIA
EDISONO
An EOIs'ov/,VIMA1TIONALo C-Pally
Figure 3-26: Non-Residential Service Pedestals—0-200 A—0-600 V
EUSERC No. 308
Enclosing Cover r�'11" Meter Socket
�A�fA-� (See Note 2 and 7 (See Note 1)
.��i Test Bypass 1225 Test Bypass
Hinged demand yp Support
reset cover Cover(See Note 3)
(See Detail D)
1 PE Controller 6"MAX
Window(See Note 9) 10.65"
0
Test Bypass Landing Lugs and Factory
Facilities(See 75"MAX Extend meter section Conductors(See Note 6)
Note 4 and 5) 36"MIN barrier to edge of test
Customer (See block barrier. Customer
Section Note 1) Section I Pull section
and cover.
17" (See Note 6 and 7)
M N (See Detail C)
Load Line
.a'o. •a'o. 74
" . Front View " Side View
Exhibit A Exhibit B
1-112"TYp.
3"MIN 3/4"MIN *2"
"
6��
17" LL
5"MAX MIN
2"MIN Hinged Demand Reset Cover
with Polycarbonate Viewing Window
F W Exhibit D
Wire Pull Section
Exhibit C
Table 3-7: Terminating Pull Section Minimum Dimensions
War AbI
Service (in) (in)
1 Phase 10-112 10
3 Phase 12-112
See Note 6.
w SeeNote 2.
Note(s):
1. The meter socket shall be rigidly mounted on a support,attached to the meter panel,and provided with a sealing ring.Ringless
sockets are not acceptable.Meter height is measured from the center of the meter socket.
EFFECTIVE DATE
10-28-2016 Underground Service Connections 0-600 V ESR-3
APPROVED e Electrical Service Requirements PAGE
I-SCE Public-4 3-45
SOUMERN CAUFOMIA
EDISON'
An MWV IATFFA'AMNALO C puny
2. The meter socket shall be enclosed and the enclosing cover shall be as follows:
❑ Hinged to allow the top and front to be rotated back as one unit to expose the metering compartment.The"A"Dimension
applies when the metering compartment side panels are fixed and obstruct the meter side clearance.The lifting force required
to open the cover shall not exceed 25 pounds.
❑ Equipped with a lifting handle.
❑ Provided with a demand reset cover with a viewing window(see Exhibit D).The reset cover shall be sealable and lockable
with a padlock having a 5/16-Inch Iockshaft.
3. Test-bypass compartment covers shall he sealable and fitted with a lifting handle;covers exceeding 16 inches in width shall
require two lifting handles.
4. Test-bypass blocks with rigid barriers shall be furnished,installed,and wired or bussed to the meter socket by the manufacturer.
Connection sequences shall be LINE-LOAD from left to right and clearly identified by 3/44nch minimum block letter labeling.See
ESR-5 for test-bypass block details.
5. Test-bypass shall be installed with the following clearances:
❑Three inches of vertical clearance from the upper test connector stud to the upper compartment access opening and 3 inches
from the center of the cable terminal screw to the lower compartment access opening.
❑ One and one-half inches of side clearance from the rigid insulating barriers to the compartment sides and one inch to the
compartment access openings.
6. The terminating pull section requirements are as follows:
❑ Comply with the minimum dimensions shown in Table 3-7(the"W"Dimension is measured between the access opening
return flanges),accept a minimum three-inch conduit,and the cover shall be equipped with a lifting handle.
❑ Be equipped with aluminum-bodied,pressure-type lugs,with a range of#6 AWG through 250 kcmil,for termination of the
service conductors.Insulated cable or bus shall be installed between the termination lugs and the test-bypass facilities.
❑ Have a protective metallic barrier(16-gauge minimum)between the pull section and the customer distribution section.There
shall be a 1/4-inch minimum clearance between the customer section wall and the barrier to prevent screws and bolts from
protruding into the pull section.
7. Compartment covers(for example,meter cover,demand reset cover,and pull section)shall be sealable and lockable with a
padlock having a 5/16-inch Iockshaft.
8. Internal equipment attached to the outer walls of the enclosure shall be secured in place with devices that may not be loosened
from the outside.Screws or bolts requiring special tools for installation or removal are not acceptable.
9. Pedestals serving both metered and unmetered loads,for instance,traffic signals and street lighting,must have landing lugs,
with customer wire from lugs-to-bypasses(metered load)and from lugs-to-breakers(unmetered loads).A photoelectric(PE)
receptacle shall be required in the meterltest bypass compartment for the unmetered service.Company will furnish and install PE
controller for unmetered service.
10. Pedestal shall be structurally supported with anchors on a concrete pad.
11. For identification purposes,the numeric portion of the address must be painted with weatherproof paint on the exterior face of the
portion of the pedestal facing the street or drivable surface in numbers at least one inch high.
EFFECTIVE DATE
ESR-3 Underground Service Connections 0-600 V 10-28-2016
PACE 3-46 Electrical Service Requirements APPROVED
►SCE Public