PMT17-03038 City of Menifee Permit No.: PMT17-03038
29714 HAUN RD.
'ACCELA7 MENIFEE,CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 08/28/2017
PERMIT
Site Address: 24848 COLDWATER CANYON TR, Parcel Number: 358-680-001
MENIFEE,CA 92584 Construction Cost: $6,778.88
Existing Use: Proposed Use:
Description of SOLAR TR 32025 DAKOTA 8 PANELS.,8 MICROINVERTERS,2.560 kW LOT 68
Work:
Owner Contractor
WOODSIDE HOMES SUNSTREET ENERGY GROUP LLC
11870 PIERCE STREET,#250 760 NORTHWEST 107 AVENUE
RIVERSIDE, CA 92505 MIAMI, FL 33172
Applicant Phone:3054854110
KRISTEN MURRAY License Number: 1001133
SUNSTREET ENERGY GROUP LLC
760 NORTHWEST 107 AVENUE
MIAMI, CA 33172
Fee Description OQt Amount($
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carded on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise staled,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpl Page 1 of 1
BUILDING : APPLICATION
Menife
DATE 08/14/2017 PERMIT/PLAN CHECK NUMBER �J
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑ADDITION []ALTERATION [—]DEMOLITION [Z]ELECTRICAL ❑MECHANI t.Vllding Deo Menif e
C
[-]NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
pt
DESCRIPTION OF WORK 2.56kW ROOF MOUNTED PV SYSTEM AUG 2 5 2017
PROJECT ADDRESS 24848 COLDWATER CANYON,MEN IFEE, CA 92584 `^
ASSESSOR'S PARCEL NUMBER 358-680-001 LOT 68 TRACT 32025
PROPERTY OWNER'S NAME WOODSIDE HOMES
ADDRESS 11870 PIERCE STREET SUITE 250
PHONE (949)939-9564 EMAIL MIKEJ@WOODSIDEHOMES.COM
APPLICANT NAME KRISTEN MURRAY
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S NAME SUNSTREET ENERGY GROUP LLC OWNER BUILDER? ❑YES❑d NO
BUSINESS NAME SUNSTREET ENERGY GROUP LLC
ADDRESS 6531 IRVINE CENTER DR SUITE 200
PHONE (949)450-5840 EMAIL KRISTEN.MURRAY@SUNSTREET.COM
CONTRACTOR'S STATE LIC NUMBER 1001133 LICENSE CLASSIFICATION B
VALUATION $ $6,778.88 �/ SO FT 200 L SO FT
APPLICANT'S SIGNATURE ,\&"t DATE 08/14/2017
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE I GREEN SMIP
INVOICELr
22 � ��yy++�� PAID AMOUNT O
AMOUNT ✓'lY� p/"�:J '� )CASH CHECK# OCREDITCARD VISA/MC
PLAN CHECK FEES PAID AMOUNT 0CASH %CHECK# 0CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED OYES 0 NO DL NUMBER NOTARIZED LETTER '.) YES 0 NO
Ci.h/o Sa/eyGepartmeni29714;;ac, :r'. r✓enlfee, CA525so'95Z-672-5777
www.citYojmenijee.us Inspection Pecuest Line 9.51-245-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM QTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SY STEM SIZE .56OKW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 8PCS. LG I LG320NIK-A5(32OW) BUYER:
INVERTER 8PCS.I ENPHASE I IQ6PLUS-72-ACM-US
ROOF TYPE I CONC. TILE DATE:
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3 ARRAY#4
MOD QTY 8 NA NA NA BUYER:
TILT 27• NA' NA° NA°
AZIMUTH 266° NA" NA- NA° DATE:
City Of tMenifee
Building Dept
AUG 2 5 2017
5'-6" 3'
Received
P
}
K
a
0
NEMA 3R JUNCTION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER B
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
AC COMBINER BO%
CITY OF M
BUILDING ,
PLAN A PP1
NOTE: DIMENSIONS ARE SHOWN IN PLANE OF ROOF
�IE ED
PLAN I ELEVATION B OPT-L
ORIENTATION I LOT#68
ORIGINAL BY:BRI MORRIS DATE:I7.07.II hese
WOODSIDE HOMES: �
DAKOTA AT AUDIE REVIEWED BY;JIM PARKS DATE:17.0 u
M URPH Y RANCH RIVERSIDE.CA 92505 1IB70 PIERCE STREET.SUITE#100 REV.# BY DATE n
DESCRIPTION h PPif"'oval ,a ce@pq ar I ordirdi
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4671 Boulder C�80304fiI C RI�iEI
INDIVIDUAL 24848 COLDWATER CANYON TRAIL Bo303, 7, 80804
PLOT PLAN I/16"=I'-0" MENIFEE,CA 303.44Z0300
SYSTEM LAYOUT
ELECTRICAL EQUIPMENT SCHEDULE
KEY QTY I MANUFACTURER MODEL NOTES TRADE
1 8 LG LG320NIK-A5(320W) PV MODULE SOLAR
2 8 ENPHASE IQ6PLUS-72-ACM-US PV INVERTER SOLAR
3 I ORBIT ZDB75-5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 I CUTLER-HAMMER DG221URB PV AC DISCONNECT, NEMA 3R,24OV,30A SOLAR
5 I ENPHASE IQ ENVOY ENV-IQAMI-240 PV DATA MONITOR, I20V SOLAR
6 1 ENPHASE X-IQ-AMI-240-8 AC COMBINER BOX SOLAR
7 1 ENPHASE TBD PV BREAKER, I X 2OA-2P, I X 5A-IP SOLAR
8 1 CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P,RATING MAY VARY SOLAR
9 1 TBD TBD SERVICE PANEL.200A BUS BLDR. ELEC.
G I TBD TBD UTILITY METER.IPH, 120/240V. 200A BLDR. ELEC.
II 1 TBD TBD GROUNDING ELECTRODE,UFER BLDR. ELEC.
AC MODULE SPECIFICATIONS AND CALCULATIONS INTERCONNECTION CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM UNIT PANEL
LOCATION MENIFEE,CA PANEL PER. CUTLER-HAMMER
TEMP,AMBIENT HIGH (TMAX) ASHRAE 2% °C 37 BUS RATING AMPS 200
TEMP,AMBIENT LOW(TMIN) ASHRAE EXTR.MIN °C -2 MAIN DISCONNECT AMPS 200
TEMP,MODULE TEST(TTEST) MODULE SPEC "C 25 ALLOWED PV PER NEC AMPS 40
TEMP.DELTA LOW(TEELTA) THIN-TTEST °C -27 PVOCPD DEVICE USED AMPS 20
MOD. MANUFACTURER AC MODULE SPEC LG INTERCONNECTION CALCS:
MOD. PART NUMBER AC MODULE SPEC LG320NIK-A5(320W) I.I7A%B(MOOS)= 9.36A OF CURRERT
MOD. POWER STC(P) AC MODULE SPEC WATTS(DC) 320 9.36A%I.z5= 11.70A
PEAK OUTPUT POWER STC(P) AC MODULE SPEC WATTS(AC) 290 TIE-IN WITH A ZOA/2P 2 SPACE Pv BACKFEED BREAKER
MAX CONTINUOUS OUTPUT POWER STC (P) AC MODULE SPEC I WATTS(AC) 280
NOMINAL VOLTAGE/RANGE AC MODULE SPEC VOLTS(AC) 240/211-264
NOMINAL OUTPUT CURRENT(IAC) AC MODULE SPEC AMPS(AC) 1.17
NOMINAL FREQUENCY/RANGE AC MODULE SPEC Hz (AC) 50/59.3-60.5
OUTPUT PHASE QUANTITY AC MODULE SPEC PHASE I
COMPLIANCE AC MODULE SPEC U1_1741 / IEEE1547
GROUNDING AC MODULE SPEC ISOLATED
MAX BRANCH CIRCUIT OCPD AC MODULE SPEC AMPS(AC) 20
AC MODULE QUANTITY.MAX PER BRANCH CIRCUIT MOD. OTY Bc QTY 8
BRANCH CIRCUIT OUTPUT. IMAXRC (IAC°MOD.QTY BO) AMPS(AC) 9.36
AC MODULE QUANTITY;TOTAL MOD. QTY T QTY 8
TOTAL SYSTEM OUTPUT IMAXTS I (IAC•MOD. OTY T) I AMPS(AC) 1 9.36
CONDUCTOR SIZING CALCULATIONS
D CONDITION OF USE(COU): (AMPACITY -TEMP. DERATE °FILL DERATE)Vs. REQ'D(MAX)g20
2)TERMINALS(TERM): AMPACITY AT TERMINALS. vs.REQ'D,(IMAX' 1.25)
KEY SIZE CU7AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REST
TYPE DERATES DERATE DERATE (A) (A)
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 9.36
TERM 25 25 11.70
B #IQ CU NM-B COU 40 0.91 I.0 36.40 9.36
TERM 35 35 11.70 C #10 CU NM-B COU 40 0.91 1.0 36.40 9.36
TERM 35 35 11.70
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE
p I-#12 ENPHASE Q CABLE.1-#6G, FREE AIR CU TC-ER ARRAY SOLAR
B 3-#10, 1-#10 EGC Cu I NM-13(ROMEX) I INTERIOR SOLAR 10
C 3-#10, 1-#10 EGG Cu I NM-B(ROMEX) I INTERIOR I SOLAR O
9
5 e 4
5AAP
0 0I itr o VD SAFE
0 JIFEE 39A,P
A"
D
A 6 C C II IVAL
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.560XW
LOT#68
ORIGINAL BY:BRI MORRIS DATE:17.07.11
DAKOTA AT AUDIE WOODSIDE HOMES REVIEWED BY:JIM PARKS DATE:17.07.11 ali nOt be col strLW
11870 PIERCE STREET,SUITE#100
MURPHY RANCH RIVERSIDE,CA 92505 REV.# BY DATE I DESCRIPTION
DWG TITLE: PAGE#: SCALE: SITE LOCATION: MBepyy a pm"
INDIVIDUAL 24848 COLDWATER CANYON TRAIL Boulder,CO aD3D4
PLOT PLAN 2 NTS MENIFEE,CA 303.447.0300
ELECTRICAL
INSTALLATION NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW,TO MAXIMUM EXTENT POSSIBLE,
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
6)THE RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION MANUAL,
APRIL 2016 EDITION
7)UNIRAC TOP CLAMPS REQUIRE A ONE QUARTER INCH(k')SPACE BETWEEN PV MODULES. SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2)BEYOND
THE EDGE OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
9)PV PANEL HAS BEEN TESTED BASED ON UL 1703.
10)AN ANIMAL GUARD SHALL BE INSTALLED AROUND THE PERIMETER OF EACH PV ARRAY IN SUCH A WAY AS TO MAINTAIN THE MODULE MANUFACTURER'S WARRANTY.
II)BASE ATTACHMENT AND FLASHING TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS
12)ALL ROOF ATTACHMENTS TO BE FLASHED AND SEALED PER MANUFACTURER'S SPECIFICATIONS.
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTU.
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING.ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
7)ENPHASE MICROINVERTERS ARE TESTED AND LISTED FOR COMPLIANCE WITH RAPID SHUTDOWN REQUIREMENTS OF SECTION 690.12 OF THE 2014 NEC.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE ULI703. IEC61646. IEC61730,
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
IU MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
15)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
SIGNAGE-
15)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690AND OTHER APPLICABLE STATE AND LOCAL CODES.
16)ALL SAFETY MARKING /PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
17)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t
18)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE.'OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
19)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
'ARTME T
01
ORIGINAL BY:BRI MORRIS DATE17.07JI ea permit r oral
DAKOTA AT AUDIE WOODSIDE HOMES REVIEWED BY:JIM PARKS DATF17.07.11
11870 PIERCE STREET,SUITE#100 REV.# BY DATE DESCRIPTION .�'d.: :deral state f city
MURPHY RANCH RIVERSIDE,CA 9250s
4WIa"Offlabe kept on
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4871 B Street
INDIVIDUAL 24848 COLDWATER CANYON TRAIL Boulder,
er,GO C080304
PLOT PLAN 3 NTS MENIFEE,CA 303.447.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
W.lR'V TION BO%
tuwm ARRAn
P,AC DISCOrvN T
E Tmw-GAVAGE
NILII META 9
MA.S."J PLYEL
IV IFIID er euItDER)
AC COMBINER BOX
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS PHOTOVOLTAIC SYSTEM EQUIPPED
AC OPERATING VOLTAGE: 240 V WITH RAPID SHUTDOWN
AC OPERATING CURRENT: 7.20A
I PC., NEC 690.54 1 PC., NEC 690.12
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY:BRI MORRIS DATE:17.07.11
DAKOTA AT AUDIE WOODSIDE HOMES: REVIEWED BY:JIM PARKS DI TE:17.07.11
11870 PIERCE STREET,SUITE#100 A
MURPHY RANCH RIVERSIDE,CA 92505 REV.# BY DATE DESCRIPTION
Qd namast8
BOLAB
DWG TITLE: PA711SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 24848 COLDWATER CANYON TRAIL Boulder,CO 80304
PLOT PLAN 4S MENIFEE,CA 303.447.D3300
PLACARDS