PMT17-01694 City of Menifee Permit No.: PMT17-01694
29714 HAUN RD. Type: Residential Electrical
<A-CCELA-> MENIFEE,CA 92586
MENIFEE Date Issued: 0 6/1 312 01 7
PERMIT
Site Address: 30093 BRISTOL GATE LN, MENIFEE,CA Parcel Number: 364-380-002
92584 Construction Cost; $7,650.40
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 11 MODULES,2.92 KW
LOT 70
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description -ObE Amount($)
Solar,Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after Issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Pennit Terrplate.rpt Page 1 of 1
BUILDING • APPLICATION
,Menifee
05/03/2017 TIMM
1.J1
DATE PERMIT/PLAN CHECK NUMBER
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL [-]MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑✓ ADDITION [-]ALTERATION ❑DEMOLITION ❑ELECTRICAL [-]MECHANICAL
❑NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2399-2.92 kW/11 PCS
Master Solar Permit No.:PMT14-02630
PROJECT ADDRESS 30093 Bristol Gate Ln
ASSESSOR'S PARCEL NUMBER �j�y—.3�j�'"'(�("jJ LOT 70 TRAGT 30422-3
PROPERTY OWNER'S NAME Lerner Homes of California, Inc.
ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California,Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION
VALUATION$ $7,650.40 q FT L SO.FT
APPLICANT'S SIGNATURE DATE 05/02/2017
CITY STAFF USE ONLY
DEPARTMENT DISTRIBUTION _ O CIWOF MENIFEE BU51NE55 UCEN5E NUMBER
BUILDING PLANNING ENGINEERING FIRE I GREEN 't k• SMIP
INVOICE 12�A/�`3 PAIDAMOUNT
AMOUNT {{ U'l3•�v O CASH O CHECKN O CREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT O CASH O CHECK N 0 CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED p YES 0 NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM DTV HER. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.915 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE II PCS. HYUNDAI HIS-SZ65RG(265W) BUYER:
INVERTER II PCS. ENPHASE M215-60-2LL-S22-IG City of Menifee -------------
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY Building Dept DATE __ ----------------
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY# 7
MOD OTY II NA NA JUN 06 2011 BUYER:
TILT 23° NA° NA°
AZIMUTH250° NA' NA- 1 DATE: —
Received CITY ofMEi
BUILDIA G AI
PLAN A PR(
REVIEW ED B
19'-9'ARRAY
6'-9- 2W-7-FLASHING *Appel oft ese 01
approral of,a F vblal
regulatim an.ordirc
FFFIJjobsh until cc ".
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY) e
PV AC DISCONNECT
EXTERIOR-GARAGE ——————'� e
� � J
UTILITY METER I ------J ��
MAIN SERVICE PANEL —— —— Q
(VERIFIED BY BUILDER)
COO
0--p
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
®Z
PLAN 2 ELEVATION B-L
ORIENTATION 4 LO # 0
ORIGINAL BY: KIM ABCOUWER I DATE:17.01.02
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA I DATE:17-01.03
_
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
�namaste
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Brae dwa
INDIVIDUAL 30093 ERISTOL GATE LANE Boulder,CO 80304
304
PLOT PLAN I I/16'=I'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE /CALC UNIT DETAIL ITEM NOTE/CALL UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP.AMBIENT HIGH(THAR) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M215-60-2LLS22-1G
TEMP.AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER,(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VOc MAX) INVERTER SPEC VOLTS(99) 48
TEMP,DELTA LOW(TEELTA) THIN-TTEST °C -27 INV.OUTPUT V.(VAc NOM) INVERTER SPEC VOLTS(AC) 240
MOD.MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT.Inc INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(% MODULE SPEC WATTS(6c) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(oc) 238 COMPLIANCE INVERTER SPEC UL174ItIEEEI547
MOD. OPERATING VOLTAGE CVMP) MODULE SPEC VOLTS 00 1 31.30 INV. GROUNDING INVERTER SPEC IS
MOD. OPEN CCT.VOLTAGE(Voc) MODULE SPEC VOLTS(uU 38.10 INV. QTY.MAX/BRANCH CCT. INV.OTYac OTY 11 Hot
MOD.COEFF.VOLT/TEMP(CORR) MODULE SPEC V/°C -0JI4 BRANCH CCT.OUTPUT.IMAXSC (IAC°INV.QTYBU AMPS(AC) 9.90
MOD.MAX VOLTAGE(VMAXMOa) (Voc• (TO°COEF)) VOLTS(00 41.18 INV.QUANTITY,TOTAL INV.OTYT QTV II DER
MOD. OPERATING CURRENT(imp) MODULE SPEC AMPS Wc) B.50 TOTAL SYSTEM OUTPUT,IMAXTS (IAC°INV.QTYT) AMPS(AC) 9.
MOD.SHORT CCT.CURRENT(Isc) MODULE SPEC AMPS(Oc) 9.00 ���
MOD.MAXIMUM CURRENT(IMAX) (ISC° 1.25) AMPS(00 11.25
MIN.AMPACITY REQ'D,PER NEC (IMAX-1.25) AMPS(oc) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS Wd IS
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES - TRADE
1 II HYUNDAI XIS-S265RG(265W) PV MODULE SOLAR
2 II ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR °
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.24OV.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR, 120V SOLAR all not be core fted tI
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR of any provisior s of the
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS;I X ISA-IP(ENVOY) SOLAR �,`,
9 NOTE CUTLER-HAMMER TEO PV BREAKER, I%2OA-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR Illls set of a prowl
10 1 TBD TBD SERVICE PANEL.MIN. 125A BUS BLDR.ELEL.
11 1 TBD TED UTILITY METER,[PH,1207240V,200A BLDR.ELEC.
12 1 I 1 TBD I TBD I GROUNDING ELECTRODE UFER I BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
I)CONDITION OF USE(COL): (AMPACITY°TEMPI DERATE°FILL.DERATE) vs. REWD(IMAX) ITEM UNIT .PANEL
2)TERMINALS(TERM): I AMPACITY AT TERMINALS. y .REO'D.(IMAX° 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT M' DDBUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 ALLOWED PV PER NEC AMPS 40
TERM 25 25 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 TERM 35 35#10 CU NM-B COU 40 0.91 1.0 36.40 TERM 35 35
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE
A I-7N2 ENGAGE CABLE, 1-#6G,FREE AIR I CU I TC-ER ARRAY SOLAR
B 1 3-#10,1-#10 EGG I CU I NM-B(ROMER) INTERIOR I SOLAR
C 1 3410,1-A10 EGC I CU I NM-8(ROMEX) I INTERIOR I SOLAR
D I CAT5E,ETHERNET CABLE I CU I CATSE I INTERIOR I SOLAR 5 6 11
7 � o o
SEE NOTE 15 10
O15AlIP
O O i0O
O ✓
N
0— 0 0�
I A B I C —� I
ROOF E%TERIOR-GARAGE )
ELECTRICAL DIAGRAM 2.915 KW
LOT#70
LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.01.02
CAMELLIA AT REVIEWED BY:SHAUN MARUNA DATE:17.01.03
980 NA,CA I92 DRIVE,#302
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
Qd namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 1571 Bmatl y S"al
INDIVIDUAL 30093 BRISTOL GATE LANE Boulder,CO 603M
PLOT PLAN 2 NTS MENIFEE,CA 303.447.0300
ELECTRICAL
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
1)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3-ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-1CC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH 01 SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
Q DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'. ��
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV.ARRAY AT ROOFING MATERIAL TRANSITION.IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(0 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIROSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
perm, i
ELECTRICAL NOTES: le al,state
GENERAL- n mast be
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT e'.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: KIM ABCOUWER I DATE:I .01.02
CAMELLIA AT 980 MONTECITO DRIVE,#302 REVIEWED BY: SHAUN MARLNA I DATE:17.01.03
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
d namaste
sous
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bmadway Sbeel
INDIVIDUAL 30093 BRISTOL GATE LANE Boeldu.C080304
PLOT PLAN 3 NTS MENIFEE,CA 303.447.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SATE
o an
:Ity
SOLADECX WIRE
TRANSITION BOX )t on the
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 9.9 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: NIM ABCOUWER I DATE:17.01.02
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE.#302 REVIEWED BY:SHAUN MARUNA I DATE:17.01.03
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
b namaste
cz- SOL�R
DWG TITLE: PAGE*: SCALE: SITE LOCATION: 4571 Braadway Street
INDIVIDUAL 30093 BRISTOL GATE LANE Boulder,CO 80304
PLOT PLAN A NITS MENIFEE.CA 303.4 7.0300
PLACARDS