PMT17-01691 City of Menifee Permit No.: PMT17-01691
29714 HAUN RD.
�AACCELA—> MENIFEE,CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 0611312017
PERMIT
Site Address: 30129 BRISTOL GATE LN, MENIFEE,CA Parcel Number: 364-370-008
92584 Construction Cost: $8,331.60
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 12 MODULES,3.18KW
LOT 67
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description PIE Amount IEl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing building operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_PermH_Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
r..;t
"Menifee
DATE 05/03/2017 PERMIT/PLAN CHECK NUMBER Vol 'Q (o-6
TYPE: []COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑✓ ADDITION [—]ALTERATION ❑DEMOLITION ❑ELECTRICAL ❑MECHANICAL
❑NEW []PLUMBING ❑RE-ROOF-NUMBEROFSQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2785-3.18 kW/12 PCS
Master Solar Permit No.:PMT14-02630
PROJECTADDRESS 30129 Bristol Gate Ln ^7
ASSESSOR'S PARCEL NUMBER 36y- 3 /O "()018 LOT 67 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California,Inc.
ADDRESS 980 Montecito Dr.,suite 302,Carona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acaytum@lennar.com
APPLICANT NAME Lennar Homes of California,Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona, CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION
VALUATION$ $8,331.60 S LSQ FT
APPLICANT'S SIGNATURE DATE 05(02/2017
DEPARTMENT DISTRIBUTION pp CITY OF MENIFEE BUSINESS UCENSENUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN IP
INVOICE ��� (,fJ PAIDAMOUNT
AMOUNT OCASH OCHECK# OCREDITCARD VISA/MC
PLAN CHECK FEES PAIDAMOUNT I OCASH OCHECKR OCREDITCARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DL NUMBER NOTARIZED LETTER 3 YES O NO
City of Menifee Building&Safety Deportment 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityof,nenifee.us Inspection Request Line 951-245-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES.TO BE INSTALLED
ITEM OTY 1 MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 13.ISO KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 12 PCS.1 HYUNDAI HIS-S265RG (265W) BUYER:
INVERTER 1 12 PCS.j ENPHASE I M2I5-60-2LL-S22-IG
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE: _ CITY OF ME NIFE
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3 BUILDING ND !
MOO OTY 1 12 1 NA NA BUYER:
TILT 23- NA° NA' DATE: Pf AN-APPR VAI
AZIMUTH 270- NA' NA'
Cif' enifee REVIEWED IU
Et—jnlg Japt
'Approval of these pi ins shal
pp approval of,any viola ' of a
I� I �#'e d regulations and ordin nceL 1
19'-9'ARRAY jobsite until completi .
20'-7'FLASHING 9'-7'
( i
I �
———J SOLADECK WIRE _
TRANSITION BOX
I I � (UNDER ARRAY)
I I I
I I �
PV AC DISCONNECT
J EXTERIOR-GARAGE
—— ———— i UTILITY METER 8
i MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
L———— -------- ————————-
Ali
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
®Z
PLAN 3 ELEVATION B-R
ORIENTATION LO #67
ORIGINAL BY: KIM ASCOUWER I DATE:17.01.02
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA I DATE:17.01.03
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
2amaste
SOL,�R
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Smo ay Street
INDIVIDUAL 30129 BRISTOL GATE LANE B..1deA CO BO 4
PLOT PLAN 1 1/16'=1'-0' MENIFEE,CA 303."7Z3D0
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALL UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M2{5-60-2LL-S22-IG
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER.(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VOc MAX) INVERTER SPEC VOLTS(00 48
TEMP,DELTA LOW(TOELTA) THIN-TTEST °C -27 INV.OUTPUT V.(Vac NON) INVERTER SPEC VOLTS(AC) 240 EPA
MOD.MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(Ac) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(110 265 INV.PHASE QUANTITY INVERTER SPEC PHASE 1
MOD. POWER PTC MODULE SPEC WATTS 00 238 COMPLIANCE INVERTER SPEC UL1741/1 EE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS 00 31.30 INV.GROUNDING INVERTER SPEC ISOLAT
MOD. OPEN CCT. VOLTAGE(Voc) MODULE SPEC VOLTS 00 38.10 INV.OTY,MAX/BRANCH CCT. 1 INV.OTYBC OTY 12
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT. OUTPUT,IMAXBC I (IAC-INV.QTYBc) AMPS(AC) IO.BO
MOD.MAX VOLTAGE(VMAXn00) (Voc+(TD-COEF)) VOLTS(oc) 41.18 INV.QUANTITY,TOTAL I INV.OTYr OTY 12
MOD. OPERATING CURRENT(IMP) MODULE SPEC AMPS(oc) 8.50 TOTAL SYSTEM OUTPUT.IMAXTS I (IAC INV.OTYT) AMPS(AC) 10.80
MOD.SHORT CCT.CURRENT(Isc) MODULE SPEC AMPS(00 9.00 144.0
MOD.MAXIMUM CURRENT(IMAX) (ISC• 1.25) AMPS(oc) 11.25 '
MIN. AMPACITY REO'D.PER NEC (IMAX• 1.25) AMPS(DC) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(K) 1 15 of he conV rued to
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE provision of the
1 12 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR s set of ap roved 1
2 12 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER OG221URB PV AC DISCONNECT.NEMA SR,24OV.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TED PV BRANCH CIRCUIT BREAKERS:I x ISA-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER. I x 20A-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 TBD TBD SERVICE PANEL,MIN. 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER.]PH,120/24OV,20OA BLDR.ELEC.
12 1 1 1 TBD I TEO I GROUNDING ELECTRODE LIFER I BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
Q CONDITION OF USE(COU): I(AMPACITY•TEMP.BERATE'FILL DEBATE) vs.REO'D([MAX) ITEM UNIT PANEL
2)TERMINALS(TERM I AMPACITY AT TERMINALS. vs. REO'D.(IMAX• 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT jREOa'DN20
BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 ALLOWED PV PER NEC AMPS 40
TERM 25 25 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 091 1.0 36.40 TERM 35 35 C #10 CU NM-B COU 40 0.91 1.0 36.40 TERM 35 35
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL 1 TYPE 1 LOCATION TRADE
A 1-#12 ENGAGE CABLE, 1-96G.FREE AIR I CU TC-ER IARRAY SOLAR
B 34#10.1-#10 EGC I CU NM-B(ROMEX) I INTERIOR ISOUR
C 3410.1410 EGC I CU NM-B(ROMEX) I INTERIOR I SOLAR
D CAT5E,ETHERNET CABLE I CU I CAT5E I INTERIOR i SOLAR 5 5 II
SEE NOTE 15 ( 10
OISAIIP
0 0 O9 20AI2P
3
N
G G
G
A B C
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 3.180 KW
LOT#67
ORIGINAL BY: KIM ASCOUWER I DATE:1
LENNAR: 7.01.02
CAMELLIA AT REVIEWED BY:SHAM MARUNA DATE:17.01.03
980 MONTECITO DRIVE.#302
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
ov namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway 56ee1
INDIVIDUAL 30129 BRISTOL GATE LANE Boulder,CO 80304
PLOT PLAN 2 NITS MENIFEE,CA 303.447.0300
ELECTRICAL
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'QC-
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE,
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED. T ENT
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I-)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3-.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION. '
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(I')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS. a nt
6)BIRDS70P WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIROSTOP TO BE SPECIFIED BY ROOFER PRIOR TO !'
INSTALLATION. oral stoor
is ff udbe(III
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(VRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING.NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)OC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
10 MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING.OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED-PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: KIM ASCOUWER DATE:I .
900 MONTECITO DRIVE,#302 01.02
CAMELLIA AT REVIEWED BV: SHAUN MARUNA DATE:17.01.03
THE LAKES CORONA,CA 92879 REV.# BV DATE DESCRIPTION
to namaste
DWG TITLE: PAGE#: SCALE: SITE LOCATION: AS-/1 Broadway Siree[
INDIVIDUAL 30129 BRISTOL GATE LANE Boulder,CO 8030d
PLOT PLAN 3 NTS MENIFEE,CA -----7.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
in
r
m the
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 1o.8 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.01A2
CAMELLIA AT 980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA DATE:17.01.03
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION Sm
mastd
..lAl
SOtI.R
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 B.dmyStreet
INDIVIDUAL 30129 BRISTOL GATE LANE Boulder,CID 803N
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS