PMT17-01235 City of Menifee Permit No.: PMT17-01235
29714 HAUN RD.
<ACCELA MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 0 510 512 01 7
PERMIT
Site Address: 29614 EDGEMERE WAY, MENIFEE, CA Parcel Number: 364-360-051
92584 Construction Cost: $6,328.72
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 MARIPOSA
Work: 9 MODULES,2.39KW
LOT 215
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description Ply Amount
Solar,Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The Issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpl Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN APPLICATION
41"Nenifee
DATE PERMIT/PLAN CHECK NUMBER
TYPE: []COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑✓ ADDITION []ALTERATION []DEMOLITION [—]ELECTRICAL El MECHANICAL
❑NEW ❑PLUMBING [I RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK SolarPennit-Plan 1924-2.39kW/9CS
Master Solar Permit No.: PMT16-00910
PROJECTADDRESS 29614 Edgemere Way, Menifee,CA 92584
ASSESSOR'S PARCEL NUMBER 36q LOT 215 TRACT 304223
PROPERTY OWNER'S NAME -Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817 3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT'NAME Lennar Homes of Cal'Ifomia,-Inc.
ADDRESS 9BOWontecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California,Inc. OWNER BUILDER? ❑✓ YES.❑NO
BUSINESSNAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona, CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acaytuni@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A'B
VALUATION$ $6,328.72
APPLICANT'S SIGNATURE DATE 04/06/2017
CITYSTAFF USE ONLY
DEPARTMENT 0151RIBUIlUN CITY OF MENIFEE 8U51NESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE I GREEN W SMIP
INVOICE w,0 PAID AMOUNT
AMOUNT 0CASH 0 CHECK 41 0CREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT OCASH 0CHECK# 0CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DL NUMBER NOTARIZED LETTER O YES C NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.citycfinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION ]^�
-w'�y J BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO Be INSTALLED
ITEM OTY MFR. MODEL Mike Dutault ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.385 aW I Sr VPOperations LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 1 9 PCS.1 HYUNDAI HIS-S265RG (265W) Ue111001133 ClassB
BUYER:
. : INVERTER I.. -9 PCS.1 ENPHASE I M215-60-2LL-522-IG .. -. _ . .. . .._
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#I 1 ARRAY#2 ARRAY#3
MOD OTY 9 NA NA BUYER: !`TTV$�7 ME E1
TILT °23 NA' NAB
AZIMUTH 123 NWNA° DATE: R tTT DING` A D LS
PLAN APPRC VAL
City of Menifee
Building Dept RI-VfFWFDl3Yi Ff.
MAY 0 3 2017
Approval of these pl and;she
approval of,any viol itim o
R e e i\1 e, regulations and urdi antes.
t/C+ 1 V �• jobsite until complet on.
16'-5'ARRAY
17'-3'FLASHING II'-4'
I
1
t
I
SOLAOECK WIRE '
TRANSITION BOX
(UNDER ARRAY)
owso
_�—
PV AC DISCONNECT-GARAGE
EXTERIOR GARAGE
UTILITY METER 0 '
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF N
PLAN 1924 ELEVATION C-LT
ORIEN ATION I LOTEF#215
LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.03.23
MARIPOSA 980 ITO DRIVE,#302 REVIEWED BY:JIM PARKS DATE:17.03.23
AT THE LAKES
CORONNA,A,CA 92879 REV.# BY DATE DESCRIPTION •,
is namasbe
Sa LAS
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 457t leer,W 8 Sheet
2ENIF EDGEMERE WAY Boulder, 7080304
PLOT PLAN I I/Ifi'=I'-0' MENIFEE,CA 303.44].0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE.CA INV. MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP,AMBIENT LOW(TMIN) ASHRAE EXTR.,MIN,.'C..,..,. ,,.-.-2 ... .. _ .INV. MAX POWER,(WAC MAX) INVERTER SPEC. ,WATTS4AC) .22 . ..... .
TEMP.MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V,(VDC MAX) INVERTER SPEC VOLTS(00 _48
TEMP,DELTA LOW(TOELTA) TMIN-TTEST °C -27 INV. OUTPUT V.(VAC NOM) INVERTER SPEC VOLTS(Ac) 240
MOD.MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(A0 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(DO 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I Y DE
MOD.POWER PTC MODULE SPEC WATTS(DO 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(oc) 31.30 INV. GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT.VOLTAGE(VISO MODULE SPEC VOLTS(m) 38.10 INV. OTY,MAX/BRANCH CCT. INV.OTYBO QTY 9
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT.OUTPUT.IMRXBC (IAC-INV.OTYBC) AMPS(Ad 88.10
MOO.MAX VOLTAGE(VMAXMDD) (Voc♦(To-COEF)) VOLTS(m) 41.18 INV. QUANTITY,TOTAL JiNV.QTYT QTY 9
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS(DO 8.50 TOTAL SYSTEM OUTPUT,IMAXTS (IAC-INV.OTYT) I AMPS(AC) 1 8.10
MOD.SHORT CCT. CURRENT OSC) MODULE SPEC AMPS Too) 9.00
MOD.MAXIMUM CURRENT(IMAX) (ISC• 1.25) AMPS(oc) 11.25
MIN.AMPACITY REO'D,PER NEC (IMAX' 1.25) AMPS(00 14.06
SERIES FUSE RATING.MAX MODULE SPEC AMPS(00 15 constn
ELECTRICAL EQUIPMENT SCHEDULE / vision!
KEY OTY MANUFACTURER MODEL NOTES TRADE �4 ofappi
1 9 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR
2 9 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R.240V,30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBO TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
B NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS;1 X ISA-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 2OA-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL,MIN- 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER.IPH,120/24OV,200A BLDR.ELEC.
12 1 TBD I TBO GROUNDING ELECTRODE UFER BLDR.ELEC.
13 11 1 TBD I TBO I GROUNDING ELECTRODE,690.47(D) SOLAR
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY•TEMP.DERATE•FILL DERATE) M REO'D(IMAX) ITEM MIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS. Vs.REQ'D,(IMAX' 1.25) PANEL MFR. CUTLER-HAMMER
KEY SI2E CU/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE DERATES DERATE DERATE {A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #I2 CU THWN-2 COU 30 0.76 1.0 22.80 6.10 ALLOWED PV PER NEC AMPS 40
TERM 25 25 10.13 20 PV OCPD DEVICE USED AMPS 26
B #10 CU NM-B COU 40 0.91 1.0 36.40 8.10
TERM 35 35 10.13 20 n
C #10 CU NM-B COU 40 0.91 1.0 36.40 8.10 �JJ�[�-
TERM 35 35 10.13 20 Ouhult
CONDUCTOR SCHEDULE srwopmwm
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE UDBMln3 LIMB
A "12.ENGAGE CABLE.I-*6G.FREE AIR CU TC-ER ARRAY SOLAR
B 3-#10,1-#10 EGC CU NM-B(ROMEX) INTERIOR SOLAR
C 3-#10,1-it 10 EGC CU NM-B(ROMEX) INTERIOR SOLAR 0 ,.
D CAT5E.ETHERNET CABLE CU CATSE INTERIOR SOLAR 5 6 II
E 1- 6GEC,2010 CEC 690.47(D) CU BARE EXTERIOR SOLAR Q• o u O
SEE NOTE 15 10
OIsaIP
O O O222P
3
N
T115
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.385 KW
LOT#215
: ORIGINAL BY: KIM ABCOUWER DATE:17.03.23
980 T30NTECITO DRIVE.#302
MARIPOSA LENNAR REVIEWED BY:JIM PARKS DATE:17.03.25- . .�
' -'
AT THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
Qu namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
tmat
INDIVIDUAL 4577 B.,.CO 304
PLOT PLAN 2 NTS 29614 EDGEMERE WAY BD303.4 C080004
ELECTRICAL MENIFEE,CA 303.447.0300
t
STRUCTURAL NOTES: Mike Outaul
SOLAR CONTRACTOR- Sr VPOperatlons
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C. U03001133 class
2)ALLP.V.ROOF.AZT.ACHMENTS.WIl I RF.STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS..SO.MAXIMUM,EXTENT POSSIBLE
---_. S90—CI .. .. ..__.-_- .•�--^--t---__... ._ _. ..
3)ROOF PENETRATIONS ASBOCIA ED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4).SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY Z014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH 01 SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2-)BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY. ,
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(I')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS. he C/CfaLa'
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE. BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO I is must
INSTALLATION.
ELECTRICAL NOTES:
GENERAL-
I)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE I1.1703,IEC61646,IEC61730.
B)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING, BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE,'OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26,
p p LENNAR: ORIGINAL BY: KIM ABCOUVVER DATE:17.03.23
MAp[�I QOQ. ,
980 REVIEWEDBY:,JIMPARKS. DATE:17.03.23
- DRIVE.#302
AT THE LAKES CORONNA,A,C CA A 92879 REV.# BY GATE DESCRIPTION
`d namaste
tee
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29614 EDGEMERE WAY Boulder 0080304
PLOT PLAN 3 NTS MENIFEE.CA 303.447.0300
NOTES
t
Mike Duhul
Sr VPOpelatlom
UOIOOI133 Claull
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN. 00
r an
Lily
pt On the
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 6
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: U A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.03.23
MARIPOSA REVIEWED BY:JIM PARKS DATE17.03.23
9B0 NA.CA I92 DRIVE,#302
AT THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
lanamaste
SOLnR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29614 EDGEMERE WAY Boulder,CO 80304
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS