Loading...
PMT17-01231 City of Menifee Permit No.: PMT17-01231 29714 HAUN RD. �CCELA—> MENIFEE,CA 92586 Type: Residential Electrical MENIFEE Date Issued: 0 5/0 512 01 7 PERMIT Site Address: 29566 EDGEMERE WAY, MENIFEE,CA Parcel Number: 364-360-047 92584 Construction Cost: $6,328.72 Existing Use: Proposed Use: Description of SOLAR TR 30422-3 MARIPOSA Work: 9 MODULES,2.39KW LOT 211 Owner Contractor LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC 980 MONTECITO DR#302 25 ENTERPRISE CORONA,CA 92879 ATTN GOREEN MUELLER Applicant Phone:9493498269 JEREMIAH ACAYTURRI License Number:728102 LENNAR HOMES OF CALIFORNIA INC 25 ENTERPRISE ATTN GOREEN MUELLER ALISO VIEJO,CA 92656 Fee Description Piz Amount(Sl Solar,Residential or Small Commercial 1 252.00 Building Permit Issuance 1 27.00 GREEN FEE 1 1.00 SMIP RESIDENTIAL 1 1.00 General Plan Maintenance Fee-Electrical 1 12.60 $293.60 The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and specifications or from preventing builiding operations being carded on thereunder when in violation of the Building Code or of any other ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be forfeited. AA_Bldg_Permit_Templatespt Page 1 of 1 BUILDING & SAFETY,PERMIT/PLAN CHECK APPLICATION. VMenlfee DATE PERMIT/PLAN CHECK NUMBER TYPE: ❑COMMERCIAL Z RESIDENTIAL ❑MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA ❑SIGN SUBTYPE: ❑✓ ADDITION ❑ALTERATION ❑DEMOLITION [—]ELECTRICAL ❑MECHANICAL ❑NEW [_]PLUMBING ❑RE-ROOF-NUMBER OF SQUARES DESCRIPTION OF WORK Solar Permit-Plan 1769-2.39 kW/9CS Master Solar Permit No.:PMT16-00910 PROJECTADDRESS 29566 Edgemere Way,,Menifee,CA 92584 ASSESSOR'S PARCEL NUMBER 3C9 "-360 —0417 LOT 211 TRACT 30422-3 PROPERTY OWNER'S NAME Lennar Homes of California, Inc. ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879 PHONE (951)817-3680 EMAIL leremiah.acaytuM@lennar.com APPLICANT NAME Lennar Homes of California, Inc. ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879 PHONE (951)817-3680 EMAIL leremiah.acaytum@lennar.com CONTRACTOR'S NAME Lennar Homes of California,Inc. OWNER BUILDER? ❑✓ YES❑NO BUSINESS NAME Lennar Homes of California, Inc. ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879 PHONE (951)817-3680 EMAIL jeremiah.acaytum@lennar.com CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICAT N A&B VALUATION$ $6,328.72 S L SQ FT APPLICANT'S SIGNATURE DATE 04/06/2017 CITY STAFF USE OAfLY DEPARTMENT DISTRIBUTION GREEN $MAP ".I.,MENIFEE BUSINESS LICENSE NUMBER BUILDING PLANNING ENGI EERING FIRE% WW INVOICE PAID AMOUNT AMOUNT OCASH OCHECK# OCREDITCARD VISA/MC PLAN CHECK FEES PAID AMOUNT OCASH OCHECK# OCREDITCARD V6A/MC OWNER BUILDER VERIFIED OYES O NO DL NUMBER NOTARIZED LETTER O YES O NO City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777 www.cityofinenifee.us Inspection Request Line 951-246-6213 SYSTEM INFORMATION --��J BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED ITEM OTY 1 MFR. MODEL Mike Oufaun ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE SYSTEM SIZE 12.385 KW Sr VP Operations LOCATIONS INDICATED BY THE ILLUSTRATION. MODULE 9 PCEI.1 HYUNDAI I HIS-S265RG(265W) DO 1001133 Clan BUYER: INVERTER , 1 9 RCS.1 ENPHASE 11215-60-2LL-S22-IG _ . ROOF TYPE TILE W/COMPOSITE SHINGLE UNDER ARRAY BATE: MEN FEE SUB-ARRAY INFORMATION ARRAY#I 1 ARRAY#2 ARRAY#3 MALDWG A D S? MOD OTY 9 NA NA BUYER: �, PRO TILT 23° NA' NA- AZIMUTH 165° NA' NA' DATE: I(Fl�II;WFDB - 4a City of Menifee Building Dept \,zu„nl..I tbcsc pl s steal MAY 0 3 ZW7 n,,,.11 ally viol tion of cgulanum and nrdi nces.' )abwe until complct n. Received ` ------ I � I � , I I I 16'-5'ARRAY I7'-3-FLASHING IB' I I I SOLADECK WIRE _ BOX B TRANSITION (UNDER ON BOX PV AC DISCONNECT { — EXTERIOR-GARAGE UTILITY METER B { MAIN SERVICE PANEL L------__J — (VERIFIED BY BUILDER) NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF A r PLAN1769 ELEVATION A-LEFT ORIENTATION I I-Olf Zil LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.03.23 MARIPOSA "' ' - REVIEWED BY:JIM PARKS DATE:17.03.23 AT THE LAKES CO NA,CA I92 DRIVE.#302 CORONA,CA 92879 REV.# BY DATE DESCRIPTION Z to namdsGe DWG TITLE: PAGE#: SCALE: SITE LOCATION: 6571 Broadway Street INDIVIDUAL 29566 EDGEMERE WAY Boulder,CO 803M PLOT PLAN 1 1/16'=1'-0' MENIFEE,CA 303.a67.030D SYSTEM LAYOUT MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC. UNIT DETAIL LOCATION MENIFEE,CA INV. MAKE INVERTER SPEC ENPHASE TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV. MODEL INVERTER SPEC M215-60-2LL-S22-IG ^� sTEMP,AMBIENT.LOW.,(THW) ASHRAE EXTR.MIN °C .. -2 .,., .INV. MAX POWER.(WA:MAX), INVERTER SPEC WATTS(Ac) 225 _ T TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VDC MAX) INVERTER SPEC VOLTS(DC) 48 TEMP,DELTA LOW(TDELTA) THIN-TTEST °C -27 INV.OUTPUT V,(Vac NON) INVERTER SPEC VOLTS(AC) 240 DEP, MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60 MOD.PART NUMBER MODULE SPEC HIS-S265RG INV. OUTPUT CURRENT,LAC INVERTER SPEC AMPS(AC) 0.9 MOD. POWER STC(P) MODULE SPEC WATTS(oc) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I MOD. POWER PTC MODULE SPEC WATTS(oC) 238 COMPLIANCE INVERTER SPEC (L1741/IEEEI5 MOD. OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(DO 31.30 INV.GROUNDING INVERTER SPEC ISOLATED MOD. OPEN CCT.VOLTAGE Nod MODULE SPEC VOLTS(0c) 38.10 INV.QTY,MAX/BRANCH CCT. INV.OTYec1 OTY 9 - MOD. LOEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT.OUTPUT,IMAXBC I(LAC-INV.QTYBC) I AMPS(AD) 8J0 MOD, MAX VOLTAGE(VHAXMDD) (VOC+(TD°COEF)) VOLTS(DC) 41.18 INV.QUANTITY,TOTAL I INV.OTYT I OTY 9 MOD. OPERATING CURRENT(IMP) MODULE SPEC AMPS(DO 8.50 TOTAL SYSTEM OUTPUT.IMAXTB I(IAC-INV.QTYT) AMPS(AC) 8.10 MOD. SHORT CCT. CURRENT(ISO MODULE SPEC AMPS(DO 9.00 -mBlruu MOD. MAXIMUM CURRENT(IMAX) (ISO° 1.25) AMPS(DO) 11.25 /t ON Sion MIN.AMPACITY REO'D,PER NEC ([MAX° 1.25) AMPS(Oc) 14.06 'et c appm SERIES FUSE RATING,MAX MODULE SPEC AMPS(DC) IS ELECTRICAL EQUIPMENT SCHEDULE KEY CITY MANUFACTURER MODEL NOTES TRADE 1 9 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR 2 9 ENPHASE M215-60-2LL-S22-IG PVINVERTER SOLAR 3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR 4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V,30A SOLAR 5 1 E14PHASE ENVOY PV DATA MONITOR.t20V SOLAR 6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR 7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR 8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS; I X 15A-IF(ENVOY) SOLAR 9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR 10 1 TBD TED SERVICE PANEL,MIN. 125A BUS BLDR.ELEC. 11 I TBD TED UTILITY METER.]PH.120/24OV,200A BLDR.ELEC. 12 I TBD TED GROUNDING ELECTRODE UFER BLDR.ELEC. 13 1 TBD I TBD I GROUNDING ELECTRODE,690.47(D) I SOLAR CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS 1)CONDITION OF USE(COU): I (AMPACITY°TEMP.BERATE°FILL DEBATE) vs.REO'D(IMAX) ITEM UNIT PANEL 2)TERMINALS(TERM): I AMPACITY AT TERMINALS. vE.REO'D,(IMAX° 1.25) PANEL MFR. CUTLER-HAMMER KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REQ'D OCD BUS RATING AMPS 200 TYPE DEBATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200 A #12 CU I THWN-2 COU 30 0.76 Lo 22.80 8.10 ALLOWED PV PER NEC AMPS 40 TERM 25 25 10.13 20 PV OCPD DEVICE USED AMPS 20 B #10 CU NM-S COU 40 0.91 1.0 36.40 9.10 TERM 35 35 10.13 20 C #10 CU NM-B COU LO 0.91 1.0 3b.40 8.10 J��t TERM 35 35 10.13 20 p Dufault ° CONDUCTOR SCHEDULE Sr VPOlreraHODs KEY CONDUCTORS CU/AL TYPE LOCATION TRADE Uc#1001133 OxsO A 1-#12 ENGAGE CABLE, I46G,FREE AIR CU TC-ER ARRAY SOLAR B 3410.1-#10 EGC CU NM-B(ROMEX) INTERIOR SOLAR C 3410,1410 EGC CU NM-B(ROMEX) INTERIOR SOLAR O CAT5E,ETHERNET CABLE CU CAT5E INTERIOR SOLAR 5 6 II E I-06GEC,2010 CEC 690.47(D) CU BARE EXTERIOR SOLAR O e o M — SEE NOTE 15 10 B O 15A/Ojp OO 20Al2P 'N G G G� 13 = E A B C = 12 I I I ROOF E%TERIOR-GARAGE ELECTRICAL DIAGRAM 2.385 XW LOT#211 LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.03.23 MARIPOSA 900 MONTECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:17.03.23 AT THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION Z namaste SOLAR DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street INDIVIDUAL 29566 EDGEMERE WAY Boulder,CO 80304 PLOT PLAN 2 NTS MENIFEE,LA 301,147.0300 ELECTRICAL It — STRUCTURAL NOTES: Mike Dulaul[ SOLAR CONTRACTOR- 3r VPOperudons O ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48,O.C. U&1001II3 cans 2)ALL PV ROOF ATTACHMENTS WIIL.BE.STAGGEREDI BYaOW:AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT ILE. i..L 3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL SE SEALED WITH AN APPROVED SEALANT. 4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED. ri SENT 5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE. 6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY 2014. 7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I')SPACE BETWEEN PV MODULES. SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE OF THE PV ARRAY/SUB-ARRAY. 8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'. ROOFING CONTRACTOR- 1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'. U/ 2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE APROVED PRIOR TO PV SYSTEM INSTALLATION. ` PC it 1 3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 01 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO (V 1eml,SI81 BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. p)' 3IIIUSI Ih 4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE. 5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS. 6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO INSTALLATION. ELECTRICAL NOTES: GENERAL- 1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL). 2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC. 3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC WELD. 4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED. 5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE. 6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE. SOLAR CONTRACTOR- 7)MODULE CERTIFICATIONS WILL INCLUDE U1_1703,IEC61646.IEC61730. 8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS. 9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO.INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS. 10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM. 10 MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER. 12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122. 13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS. 14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT. 15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR. SIGNAGE- 16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES. 17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS. 18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF MINIMUM HEIGHT t. 19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'. BUILDER ELECTRICAL AND SOLAR CONTRACTORS- 20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER. 21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26. ORIGINAL BY: KIM ABCOUWER DATE:17.03.23 LENNAR: MARIPOSA REVIEWED BY: JIM PARKS DATE:17.03.23 AT THE LAKES 900 DRIVE,#302 S'2namasrA CORONA,NA,CA CA 92 92879 REV.* BY DATE DESCRIPTION SOl/R OWG TITLE: 1PA.GE#: SCALE: SITE LOCATION: INDIVIDUAL 4B71 B.r.CO B 304 PLOT PLAN NTS 29566 EOGEMERE WAY Boulder,CO B0304 NOTES MENIFEE.CA 303.447.0300 t Mike Du7aui Sr VP OpemdOOs 1101001133 Cla 11 CAUTION: POWER TO THIS BUILDING IS SUPPLIED BY THE UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS ARE LOCATED AS SHOWN. an I), I on the SOLADECK WIRE TRANSITION BOX (UNDER ARRAY) PV AC DISCONNECT EXTERIOR-GARAGE UTILITY METER 6 MAIN SERVICE PANEL (VERIFIED BY BUILDER) SERVICE BY QUALIFIED PERSONNEL ONLY CONTACT: SUNSTREET ENERGY GROUP I-877-SLR-POWR PV POWER SOURCE - AC SPECS AC OPERATING VOLTAGE: 240 V AC OPERATING CURRENT: U A NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION LEN14AR: ORIGINAL BY: KIM ABCOUWER DATE:17.03.23 MARIPOSA "' 930 MOMECITO DRIVE,#302 REVIEWED BY:JIM PARKS I DATE:17.03.23 AT THE LAKES CORONA,CA 92679 REV.# BY I DATE I DESCRIPTION �namastEi sour DWG TITLE:. PAGE#: SCALE: SITE LOCATION: I S4571 Bmadway Street INDIVIDUAL 29566 EDGEMERE WAY Boulder,CO W304 PLOT PLAN 4 NTS MENIFEE.CA 303.447.0300 PLACARDS