PMT17-01223 City of Menifee Permit No.: PMT17-01223
29714 HAUN RD. Type: Residential Electrical
<A-CCFLA> MENIFEE,CA 92586
MENIFEE Date Issued: 0 5/0 512 01 7
PERMIT
Site Address: 30309 BRISTOL GATE LN,MENIFEE,CA Parcel Number: 364-360-023
92584 Construction Cost: $6,328.72
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 MARIPOSA
Work: 9 MODULES,2.39KW
LOT 53
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number.728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description Oy, Amount lSl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permil_Tempiate.rpl Page 1 of 1
SAFETYBUILDING & PERMIT/PLAN CHFCK APPLICATION
Menifee
DATE PERMIT/PLAN CHECK NUMBER
TYPE: ❑COMMERCIAL Z RESIDENTIAL ❑MULTI-FAMILY []MOBILE HOME ❑POOL/SPA []SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION []DEMOLITION ❑ELECTRICAL [I MECHANICAL
❑NEW []PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK SolarPermit-Plan 1769-2.39 kW/9CS
Master Solar Permit No.:PMT16-00910
PROIECTADDRESS 30309 Bristol Gate Ln, Menifee,CA92584
ASSESSOR'S PARCEL NUMBER^360 — 623 LOT 53 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturd@lennar.com
APPLICANT NAME Lerner Homes of California.Inc.
ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennaccom
CONTRACTOR'S NAME Lerner Homes of California, Inc. OWNER BUILDER? ❑� YES❑NO
BUSINESS NAME Lerner Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE UC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $6,328.72 L SO FT
APPLICANT'S SIGNATURE "06/2017
CITY STAFF USE ONLY
DEPARTMENT DISTRIBUTION IVQ CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN { SMIP
INVOICE a�n
J PAID AMOUNT
AMOUNT ` OCASH OCHECK# OCREDITCARD VISA/MC
PLAN CHECK FEES PAID AMOUNT OCASH 0 CHECK 4 0CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DL NUMBER NOTARIZED LETTER O YES ^v NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION '^'7.0,�.�-- BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. MODEL m1w 0i uft ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
LVPopentlw LOCATIONS INDICATED BY THE ILLUSTRATION.
SYSTEM SIZE 2.3B5 KW S,woorua rCuesil m
MODULE 9 PCS. HYUNDAI HIS-S265RG(265W) BUYER:
]INVERTER, 9 PCS. ENPHASE MZI5-60-2LL-S22-IG
ROOF TYPE TILE W/COMPOSITE SHINGLE UNDER ARRAY -1 DATE:—
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3
MOD OTY 9 NA NA BUYER:
TILT 23° 1 NA' I NA- DATE: CITY OF MENIF E
AZIMUTH 242° 1 NA' I NA-
G AND AFf
City of Mewtee PLAN APPROV
Building Dept
REVIEWED BY
MAY 0
p Approval of these plans sh II not 1
R [�[� L. f '1 t` approval of,any violation f any f
e�+e i ,I 4' regulations and ordinances.This si
johsite until completion.
-------------------
29'-B'ARRAY
11'-2' 30'-e'FLASHING
f
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
I PV AC DISCONNECT
EXTERIOR-GARAGE
I ~
+ + L— UTILITY METER e
-------J MAIN SERVICE PANEL
---J (VERIFIED BY BUILDER)
L_
r
L
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 1769 ELEVATION B REVERSE
ORIENTATION 4 LOT# 3
LENNAR; ORIGINAL BY: SHAUN MARUNA DATE:16.12.07
MARIPOSA 980 MONTECITO DRIVE,#302 REVIEWED BY:KIM ABCOUWER I DATE:16.12.08
AT THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
Qts namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 30309 BRISTOL GATE LN Boulder,CO 803N
PLOT PLAN 1 1116'=1'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC i UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP,AMBIENT.LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER..(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) 'MODULE SPEC °C 25 INV. INPUT V,(Voc MAX) INVERTER SPEC VOLTS(Dc) 48
TEMP.DELTA LOW(TOELTA) THIN-TTEST °C -27 INV. OUTPUT V.(VAC NOM) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV. OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD. PART NUMBER MODULE SPEC HtS-S265RG INV. OUTPUT CURRENT, IAC INVERTER SPEC AMPS(AC) 0.9
MOD. POWER STC(P) MODULE SPEC WATTS(oc) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(oc) 238 COMPLIANCE INVERTER SPEC UL174111EEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(110 31.30 INV.GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT.VOLTAGE(Voc) MODULE SPEC VOLTS(oc) 38.10 INV.DTY,MAX/BRANCH CCT. INV.QTYBC OTY 9 EPA
MOD. COEFF.VOLT/TEMP(COEF) MODULE SPEC V/.c -0,114 BRANCH CCT. OUTPUT,IMAXB6 (IAC-INV.OTYBc) AMPS(Ac) 8.10
MOD. MAX VOLTAGE(VMAXMOD) (Voc+(To•COEF)) VOLTS(Dc) 41AB INV.QUANTITY,TOTAL INV.OTYT I CITY 9 I
MOD. OPERATING CURRENT(IMP) MODULE SPEC AMPS(Dc) 8.50 TOTAL SYSTEM OUTPUT,IMAXTS (IAc•INV.QTYT) AMPS(Ac) 18.10
MOD.SHORT CCT.CURRENT(Isc) MODULE SPEC AMPS(DD) 9.00
MOD. MAXIMUM CURRENT OMA%) (Isc• 1.25) AMPS(oc) 11.25
MIN, AMPACITY REO'D,PER NEC (IMAX• 1.25) AMPS(Dc) 14.06
SERIES FUSE RATING.MAX MODULE SPEC AMPS(Dc) 15
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE ^ trued I,
1 9 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR I ms Ord
2 9 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR a Proved
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR, 120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I x ISA-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER. I%2GA-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 I TED TBD SERVICE PANEL,MIN. 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER,IPH,IZO/24OV.200A BLDR.ELEC.
12 TBD TBD GROUNDING ELECTRODE UFER BLDR.ELEC.
13 1 1 1 TBD I TBD GROUNDING ELECTRODE,690.47(D) I SOLAR
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
U CONDITION OF USE(COU): (AMPACITY' TEMP.BERATE'FILL BERATE)vs.REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS.vs.REO'D,(I"X• 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/O TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE BERATES DEBATE BERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 8.10 ALLOWED PV PER NEC AMPS ILO
TERM 25 25 10.13 20 PV OCPD DEVICE USED AMPS 1 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 BAD
TERM 35 35 10.13 20 //77
C #10 CU NM-B COU 40 0.91 1.0 36.40 8.10 "7J`(�—
TERM 35 35 10.13 20 rvpo h
s.Mp s
CONDUCTOR SCHEDULE uew9ss33 aura
KEY CONDUCTORS jCU/ALTYPE LOCATION TRADE
A 1-#12 ENGAGE CABLE.1-#6G,FREE AIR TC-ER ARRAY SOLAR
B 3-#10,1-#10 EGC NM-B(RDMEX) INTERIOR SOLAR
C 3-#10,1-#10 EGC NM-B(RDMEX) INTERIOR SOLAR
D CAT5E,ETHERNET CABLE CAT5E INTERIOR SOLAR
E I-#6GEC,2010 CEC 690.47(D) BARE EXTERIOR SOLAR
5 6 II
]S•
SEE NOTE 15 10 -
O O 9
O IN�
G � G N�
13 = E A B C = 12
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.385 KW
LOT#53
LENNAR: ORIGINAL BY: SHAUN MARUNA I DATE:16.12.07
MARIPOSA 980 MONTECITO DRIVE,#302
,... REVIEWED BY:KIM ABCOUWER DATE:16.12.08
'
AT THE LAKES CORONA.CA 92879 REV.# BY DATE DESCRIPTION
�N namasU6
:DI,•
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Breedway Slreet
INDIVIDUAL 30309 BRISTOL GATE LN Boulder,CO 80304
PLOT PLAN 2 NTS MENIFEE,CA 303.447.0300
ELECTRICAL
mi4 oulwle
STRUCTURAL NOTES: xwaaema
SOLAR CONTRACTOR- un l0ovae clone
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
ALL,PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF,FRAMING.MEMBERS.TO MAXIMUM EXTENT POSSIBLE.
33'ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED%qtT—W N APPROVED SEALANY. -
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH U')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 401.
ROOFING CONTRACTOR- 'AE,N
O DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT U')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIROSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION. r
I permit
leml,SN
mUSI h
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE(A.1703. IEC61646, IEC6173D.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
IU MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT i'.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
MARIPOSA LENNAR: ORIGINAL BY: SHAUN MARUNA DATE:16.12.07
980 MONTECITO DRIVE.#302 REVIEWED BY:KIM ABCOUWER DATE:16.12.08
AT THE LAKES CORONA,CA 92879 REV.-- BY DATE DESCRIPTION
%mas GB
.oL.a
DWG TITLE: PAGE A: SCALE: SITE LOCATION: 4571 Broadway Slre t
INDIVIDUAL 30309 BRISTOL GATE LN B9u1Cec,CO 80304
PLOT PLAN 3 NTS MENIFEE.CA 303.447.0300
NOTES
swoo..,iw�:
' tw lmv3a Oasva
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
E
I sh,
n�
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER&
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 8.1 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
LENNAR: ORIGINAL BY: SHAUN MARUNA DATE:16.12-07
MARIPOSA REVIEWED BY:KIM ABCOUWER I DATE:15:12:138
980 MONTECITO DRIVE,#302
AT THE LAKES CORONA,CA 921379 REV.# BY DATE DESCRIPTION
d namasb6
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bmad y Street
INDIVIDUAL 30309 BRISTOL GATE LN Baulde,CO 903O4
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS