PMT17-01187 City of Menifee Permit No.: PMT17-01187
29714 HAUN RD. Type: Residential Electrical
<A-CCEL/> MENIFEE,CA 92586
MENIFEE Date Issued: 0 5/2 312 01 7
PERMIT
Site Address: 30160 SUTTON CT, MENIFEE,CA 92584 Parcel Number: 364-370-050
Construction Cost: $8,331.60
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 12 MODULES,3.18KW
LOT 151
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number.728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO,CA 92656
Fee Description QQtt( Amount(5)
Solar,Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bidg_Permit_Template.rpt Page 1 of 1
APPLICATIONBUILDING & SAFETY PERMIT/PLAN CHECK
4,•
,5
"Menifee
DATE PERMIT/PLAN CHECK NUMBER PY_1 (-7- C D 1
TYPE: []COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION ❑DEMOLITION [—]ELECTRICAL ❑MECHANICAL
❑NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2785-3.18 kW/12CS
Master Solar Permit No.: PMT14-02629
PROJECTADDRESS 30160 Sutton Ct,Menifee,CA 92584
ASSESSOR'S PARCEL NUMBER ??6q -370 -D LOT 151 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL )eremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California,Inc.
ADDRESS 980 Montecito Dr.,suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturd@lennar.com
CONTRACTOR'S NAME Lennar Homes of California,Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 /EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $8,331.60 S L SQ FT
APPLICANT'S SIGNATURE —ME 04/06/2017
CITY STAFF USE ONLY
DEPARTMENT DISTRIBUTION do
I.V,1 CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE 1nO PAIDAMOUNT
AMOUNT S UCASH 6CHECKq GCREOIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT OCASH OCHECKM OCREOITCARD VISA/MC
OWNER BUILDER VERIFIED OYES O NO DL NUMBER NOTARIZED LETTER G YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.180 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 12 PCS. HYUNDAI I HIS-S265RG (265W) BUYER:
INVERTER . 12 PCS. EMPHASE I M215-60-2LL-522-IG . .. ..
ROOF TYPE TILE W1 COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 1 ARRAY#3
MOD OTY 12 NA NA BUYER:
TILT 23° NA' NA'
AZIMUTH 270° 1 NA' I NA' DATE:
City of Mam'+<e CITY OF MEN11 EE
Building Dept BUILDING ANE SAF
PLAN APPROV
APR 2 0 211
It IiVfE WED BY
Recei +.!
I'P+In'•il ldlhcse planss all not
�ppn+val o(,any Violation of any;
legolalllms and ordinance.This:
Fohsitc Mill completion.
F---- ————— ----�
I 1
23'-1'ARRAY
SOLADECK WIRE 6'-10- 23'-II'FLASHING
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT i
EXTERIOR-GARAGE
UTILITY METER B I 00
MAIN SERVICE PANEL
(VERIFIED BY BUILDER) sonso
r
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
Z®
PLAN 2785 ELEVATION C-L
0 IENTATION I LO #151
LENNAR:. ORIGINAL BY: KIM ABCOUWER DATE:17.01.05
CAMELLIA AT - - -"
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA DATE:17.01.06
THE LAKES CORONA,CA 92879 REV.# BV DATE DESCRIPTION
ma ste
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bwdway Street
INDIVIDUAL 30160 SUTTON COURT Bouldv,OD SD304
PLOT PLAN 1 1116'= 1'-0' MENIFEE.CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE.CA INV. MAKE INVERTER SPEC ENPHASE
TEMP.AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV. MODEL INVERTER SPEC 1215-60-21L-S22-I13
TEMP,AMBIENT LOW.(TMIN). ".ASHRAE EXTR.MIN °C -2 INV. MAX POWERJWACMAX), INVERTER SPEC WATTS,(AU_ 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VDc MAX) INVERTER SPEC VOLTS(DO 48
TEMP,DELTA LOW(TDELTA) THIN-TTEST 'C -27 INV. OUTPUT V,(VAC NOM) INVERTER SPEC VOLTS(Ac) 240
MOD.MANUFACTURER MODULE SPEC HYUNDAI INV. OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD. PART NUMBER MODULE SPEC HIS-S265RG INV. OUTPUT CURRENT, IAc INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(m) 265 INV. PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(DO 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(Dc) 31.30 INV. GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT.VOLTAGE(VOC) MODULE SPEC VOLTS(m) 38.10 INV. OTY,MAX/BRANCH CCT. INV.OTYec OTY 12
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT.OUTPUT,IMAXBC I DAC•INV.OTYSc) AMPS(AC) 10.80
MOD.MAX VOLTAGE(VMAXMOD) (VOC a (TO'COEF)) VOLTS(cc) 41.18 INV. QUANTITY,TOTAL INV.QTYi I OTY 112
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS(OU 8.50 TOTAL SYSTEM OUTPUT,IPAXTS (IAc9NV.QTYT) AMPS(AC) 110.80
MOD.SHORT CCT. CURRENT(ISc) MODULE SPEC AMPS(cc) 9.00
MOD. MAXIMUM CURRENT(IMAX) (ISC• 1.25) AMPS(cc) IL25 DER
MIN.AMPACITY REG'D,PER NEC (IMAX` 1.25) AMPS(cc) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(cc) 15
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
1 12 HYUNDAI HIS-S265RG (265W) PV MODULE SOLAR
2 12 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX.NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221LIRB PV AC DISCONNECT,NEMA 3R.24OV,30A SOLAR r.Amcd I
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR Ions 011
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR / PPTOYC
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I X 15A-IF(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 2OA-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 I TBD TBD SERVICE PANEL,MIN. 125A BUS BLDR.ELEC.
11 I TBD TBD UTILITY METER.IPH, 120/24OV,200A BLDR,ELEC.
12 11 1 TBD I TBD GROUNDING ELECTRODE UFER I BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
U CONDITION OF USE (COU): (AMPACITY•TEMP.DERATE•FILL DERATE) VS.REO'D'DMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS.M. REO'D,(IMAX° 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALL. AMPACITY W/O %DERATE
L RESULT REO'D OCD BUS RATING AMPS 200
TYPE DERATES RATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 22.80 10.80 ALLOWED PV PER NEC AMPS 40
TERM 25 25 13.50 20 PV OCPD DEVICE USED AMPS 20
#10 CU NM-B COU 40 36.40 10.80
TERM 35 35 13.50 20
NM-B COU 40 36.40 10.80
TERM 35 35 113,50 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS CU/AL i TYPE 1 LOCATION 1 TRADE
A I -#12 ENGAGE CABLE,146G,FREE AIR I CU I TC-ER ARRAY I SOLAR
B 1 3-#10, 1-410 EGC CU NM-B(ROMEX) INTERIOR I SOLAR
C 1 3410, 1410 EGC CU NM-S(ROMEX) INTERIOR I SOLAR O 6 II
0 I CAT5E,ETHERNET CABLE CU CAT5E I INTERIOR I SOLAR
O° 10 -
SEE NOTE 15 ID
0 O
ISA/IP
O O O— O 20A/2P
3
'N
G G G�
ROOF EXTERIOR.-GARAGE
ELECTRICAL DIAGRAM 3.180 KW
LOT#151
LENNAR: ORIGINAL BY: KIM ABCOUWER DATE:17.01.05
980 MONTECITO DRIVE,#302
CAMELLIA- AT. .. . .. REVIEWED BY:SHAUN.MARUNA DATE:17.0L06
'
THE LAKES CORONA.CA 92879 REV.# BY DATE I DESCRIPTION
u namaste
OLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bmacimy Street
INDIVIDUAL 30160 SUTTON COURT Boulder,CO 80304
PLOT PLAN 2 NTS MENIFEE,CA 30344T0300
ELECTRICAL
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG.MODULE RACKING RAILS AT NOT GREATER THAN 48-O.C.
.T-`4-AU L PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF F AM
MEMBERS_TO.MA_XIMUM EXTENT POSSIBLE.
3TROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED,
5)PV ARRAY WILL BE A MINIMUM OF 3-ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL.VERSION 227.5,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I-)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2-)BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO.TILE)WILL BE A MINIMUM OF 3-.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT W)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. ITMB
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
t
a permit
feral,sta
S must b
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/GEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS..
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUS PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REWIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED*PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY: KIM ABCOUWER DATE:17.0LG5
LENNAR:
CAMELLIA AT REVIEWED BY: SHAUN TARUNA I DATE:17.01.06
980 MONTECITO DRIVE.#302
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
�namaste
aue
DWG TITLE: JPACESCALE: SITE LOCATION: 4571 Broadway SMal
INDIVIDUAL 30160 SUTTON COURT BauldaA CO 803M
PLOT PLAN NTS MENIFEE,CA 303.447.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE or
TRANSITION BOX
(UNDER ARRAY) I city
I),On the
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 6
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 10.8 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: KIM ABCOUWER DATE:17.01.05
LEN.N-AR:
CAMELLIA AT - REVIEWED BY:SHAUN MARLINA DATE:17.01.06
980 MONTECITO DRIVE.#302
THE LAKES CORONA,CA 92879 REV.# By DATE DESCRIPTION
I I -- Cz b namasGe
:oLAr
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Smadmy Street
INDIVIDUAL 30160 S(TfTON COURT Boulder,CO 80304
PLOT PLAN 4 NTS _ MENIFEE,CA 303.447.0300
PLACARDS