PMT16-04083 City of Menifee Permit No.: PMTH-04083
29714 HAUN RD. Type: Residential Electrical
<A—CCELA—> MENIFEE,CA 92586
0-1 N�k— MENIFEE Date Issued: 01/09/2017
P E R M I T
Site Address: 29597 ARGYLE CIR, MENIFEE, CA 92584 Parcel Number: 364-360-039
Construction Cost: $8,331.60
Existing Use: Proposed Use:
Description of SOLAR TR30422-3 CAMELLIA
Work: 12 MODULES,3.1 8 KW MASTERPLAN PMT14-02630
LOT 130
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR. STE 302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number.,728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description Qtv Amount($
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of emars in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA�Bldg_Penit.-remplate.ript Page 1 of I
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
Menifee
DATE PERMIT/PLAN CHECK NUMBER 'VIvn-r u - v4*5
TYPE: [—]COMMERCIAL EIRESIDENTIAL [-]MULTI-FAMILYEIMOBILEHOME []POOL/SPA [-]SIGN
SUBTYPE: E]ADDIT(ON F]ALTERATION [—]DEMOUTION [—]ELECTRICAL —]MECHANICAL
[-]NEW [-]PLUMBING [:1 RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2785-3.18kWl 12 PCS
Master Solar PMT#:PMT1 4-02630
PROJEcTADDRESS 29597 Argyle Circle
ASSESSOR'S PARCEL NUMBER 30-3GO -039 LOT 130 TRACT 30422-3
PROPERTY OWN ER'S NAME Lerner Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANTNAME Lerner Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lermar Homes of California,Inc. OWNERBUILDER? R]YESE]NO
BUSINESSNAME Lermar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lenner.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $8.331.60 SO FT
/01
APPLICANT'S SIGNATURE DATE 12/01/2016
DEPARTMENT DISTRIBUTION 2,Q) CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE PAID AMOUNT
AMOUNT I I OCASH OCHECKN 0 CREDIT CARD VISAIMC
PLAN CHECK FEES PAID AMOUNT I 1 0 CASH 0 CHECK h 0 CREDIT CARD VISA C
OWNER BUILDER VERIFIED 0 YES 0 No DL NUMBER NOTARIZED LET-TER 0 YES 0 NO
City of Menifee Building&Safety Department 29714 Houn Rd Menifee, CA 92586 951-672-6777
www.cityofmenifee.us Inspection Request Line 951-246-5213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM QTY 1 MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
L Y-STEM SIZE 13.18OMW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 12 PCS.1 HYUNDAI I HiS-S265RG(265W) BUYER:
INVERTER 1 12 PCS.l ENPHASE I M215-60-2LL-S22-IG Lily OF MEN
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION SUILDINGAN
I ARRAY#1 ARRAY#2 1 ARRAY*3
i7
MOD OTY 12 NA A BUYER
TILT 23' 1 W NA' III APPRO1
176- 1 NA- NA' DATE:
�'i E
-VIEWE14
city ot menifee
Building Dept
'Approval of thesE plans s
DEC 13 2016 approval of,any violation�
regulations and orc inanco
Received jobsite until complc tion.
19'-9*ARRAY
6. 20'-7'FLASHING
--�TRANSITION BOX
SOLADECK WIRE
F (UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER&
MAIN SERVICE PANEL
(VERIFIED By BUILDER)
—— ————————
0
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2785 ELEVATION B-REVERSE
ORIENTATION LU If 13U N
CAMELLIA AT LENNAR ORIGII L BY: ANGELA BURKE DATE:11.09.16
980 MONTECITO DRIVE,#302 REVIEWED BY:KIM ABCOUWER I DATE:11.10.16
THE LAKES CORONA.CA 92879 REVw# _LY_ DATE DESCRIPTION Vnamast;6
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4S71 B...day Slx�l
INDIVIDUAL 29597 ARGYLE CIRCLE Bmld�,GO 80304
PLOT PLAN 1 1116'=1'-0' MENIFEE.CA 303,"7.OWG
SYSTEM LAYOUT I
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE ICALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE.CA INV. MAKE INVERTER SPEC ENPHASE
TEMP.AMBIENT HIGH(TMAX) ASHRAE 2% C 37 INV. MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP.AMBIENT LOW(THIN) ASHRAE EXTR.MIN 'C -2 INV. MAX POWER.(WAC MAX) INVERTER SPEC WATTS(A0 225 -
TEMP.MODULE TEST(TTEST) MODULE SPEC C 25 INV. INPUT V,(VDC MAX) INVERTER SPEC VOLTS(DQ 4��
TEMP.DELTA LOW(TDELTA) TMIN-TTEST C -27 INV.OUTPUT V.(VAC NON) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ &o
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT.IAC INVERTER SPEC AMPS(AC) 7
.9 7Y
MOD.POWER STC.(P) MODULE SPEC WATTS(od 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS 00 236 COMPLIANCE INVERTER SPEC UL17411IEEEI54 I
MOD.OPERATING VOLTAGE(VmP) MODULE SPEC VOLTS(oc) 31.30 INV. GROUNDING l�VLRTER SPEC �ISOLATED
MOD.OPEN CCT.VOLTAGE(Voc) MODULE SPEC VOLTS(DC) 3B.10 INV.OTY.MAX/BRANCH CCT, 1 N�.QTYSC 1 OTY 112
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/-C -0.114 BRANCH CCT.OUTPUT.IMAXIBC I CIAC*INV.QTYaC) I AMPS(AQ Flo_80
MOD.MAX VOLTAGE(VmAxmoo) (VOC+(TO-COEF)) VOLTS(00 41.18 INV.QUANTITY,TOTAL I INV.OTYT I QTY
MOD.OPERATING CURRENT(imp) MODULE SPEC AMPS(00 B-50 TOTAL SYSTEM OUTPUT.IMAXTS (IAC-INV.QrYT) I AMPS CAC) 110.80
MOD.SHORT CCT.CURRENT(Isc) MODULE SPEC AMPS(00 9.00
MOD.MAXIMUM CURRENT(UlAX) (Isc- 1.25) AMPS(oc) 11.25
MIN.AMPACITY REG'D,PER NEC (IMAX-1.25) AMPS(00 14.06
SERIES FUSE RATING.MAX MODULE SPEC AMPS(00 1 15
ELECTRICAL EQUIPMENT SCHEDULE "otbE consta
KEY GTY MANUFACTURER MODEL NOTES TRADE I Pro'Isions o
1 12 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR
2 12 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR setafaPpro
3 1 RSTCI SOLADECK 0786-3R5 PV ROOF JUNCTION BOX.NEMA 313 SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R.24OV.30A SOLAR
5 1 ENPHASE ENVOY PVF DATA MONITOR.120V SOLAR
6 1 TBD TED 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TED CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TED PV BRANCH CIRCUIT BREAKERS;I x 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 2OA-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
1 12 SETRVjTlCE�pATNER,,NIN. 125A BUS L C�
I I jL FE P
1 TBD 1 TED H. IZO/Z40V.ZIJUA 1 BLDR�EELEE
1 12 11 1 TBD I TED I GROUNDING ELECTRODE UFER
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COO): (AMPACITY-TEMP.BERATE-FILL BERATE)VS.REG'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS..9. REOID.(IMAX' 1.25) PANEL MFR. CUTLER-HAMME
K CALC. AMPACITY WIO E OLT REO'D OCID BUS RATING AMPS 200
T S ' �A
TYPE BERATES TEIE 1 a MAIN DISCONNECT AMP§ 12700
EY SIZE CU/AL INSULATION GERA —TC ROAT (A) USED(A)
A #12 CU THWN-2 COU 0 0 76=111 00 22.80 10.80 1 ALLOWED PV PER NEC AMPS 0
TERM 25E 25 20 -Fv—o(
#IQ cu NM_B COU 40 91 36.40 10.80
TERM 35 35
C #10 CU NM-B COU 40 091 0 36.40 10.80
TERM 35 35 13.50 20
CONDUCTOR SCHEDULE
EY CONDUCTORS IC LOCATION 1 E
8 11-*12 ENGAGE CABLE.146G,FREE AIR I CU I TC-ER ARRAY MIR
#10.]-#IG EGE I CU I NM-B(ROMEX) INTERIOR ISOLAR
C 6-910.J-#IO EGC I CU I NM-B(ROMEX) INTERIOR I SOLAR
D CAT5E.ETHERNET CABLE I CU I CAT5E INTERIOR ISOLAR
SEE NOTE 15
03 22
N
A G G
Toa c
ROOF EXT RIOR-GARAGE
ELECTRICAL DIAGRAM 3.IBOKW
LOT*130
LENNAR ORIGINAL BY: ANGELA BURKE DATE: . .
CAMELLIA AT 980 MONTECITO DRIVE,#302 REVIEWED BY:KIM ABCOIJWER I DATE:11.10.16
THE LAKES CORONA,CA 92879 REV.# .BY DATE DESCRIPTION amastias
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bmaday Stmet
INDIVIDUAL 29597 ARGYLE CIRCLE Bouldw.CO 80304
PLOT PLAN 2 NTS MENIFEE,CA 303.�7.0300
ELECTRICAL I
STRUCTURAL NOTES-
SOLAR CONTRACTOR-
1)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS.TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED. 'R IRTTV
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL.VERSION 227.3.PUB 140113-ICC.JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(F)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF Y.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO HE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION.IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
�3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT W)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE-COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY 70 THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION, jerall sta
Is alust I
ELECTRICAL NOTES
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING.NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703.IEC61646.IEC61730.
6)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING 15 LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTFR SYSTEM-
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING I PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT k.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED"PHOTOVOLTAIC POWER SOURCE.'OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIG114AL BY: ANGELA BURKE DATE:11.
CAMELLIA AT LENNAR: REVIEWED BY:KIM ABCOUWER DATE:11.10.16
990 MONTIECITO DRIVE.#302
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION tamastO
SOLAN
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Bmadw.y S".t
INDIVIDUAL 29597 ARGYLE CIRCLE Boulder,CO 80304
PLOT PLAN 3 NTS MENIFEE.CA 303.447.0300
NOTES I
CAUTION: y"
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
)AT
an
.�q the
'_-1 SOLADUCK WIRE
__�TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER&
]_�MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 10.8 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
CAMELLIA AT LENNAR; ORIGINAL BY: ANGELA BURKE DATE..11.09.16
930 MONTECITO DRIVE.#302 REVIEWED BY:KIM ABCOUWER DATE-11.10.16
THE LAKES CORONA,CA 92879 REV.# -BY DATE DESCRIPTION mastiS
tit
DWG TITLE: PAGE#: I SCALE: SITE LOCATION 4571 B=dway Street
INDIVIDUAL 29597 ARGYLE CIRCLE Boulder.CO 8OX9
PLOT PLAN 4 NTS MENIFEE.CA 303.4470300
—PLACARDS