PMT16-04062 City of Menifee Permit No.: PMT16-04062
29714 HAUN RD. Type: Residential Electrical
<A-CCIELA> MENIFEE. CA 92586
MENIFEE Date Issued: 0110912017
P E R M I T
Site Address: 28864 SKYLARK ST, MENIFEE, CA 92584 Parcel Number: 333-631-022
Construction Cost: $9,353.40
Existing Use: Proposed Use:
Description of SOLAR TR 31582-1 MENIFEE HILLS
Work: 14 MODULES,3.71 KVV, MASTER PLAN PMT14-00706
LOT 32
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ATTN GOREEN MUELLER
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number: 728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ATTN GOREEN MUELLER
ALISO VIEJO, CA 92656
Fee Description -0-ty Amount
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of emors in the plans and
specifications or from preventing builicling operations being carded on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA.Bidg_Permt-Template.rpt Page I of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
P-Menifee
0
DATE PERMIT/PLAN CHECK NUMBER 0
TYPE: EICOMMERCIAL R]RESIDENTIAL [:]MULTI-FAMILY [—]MOBILEHOME EJPOOL/SPAE1SIGN
SUBTYPE: R]ADDITIONE]ALTERATION F]DEMOUTION [—]ELECTRICAL []MECHANICAL
[:]N EWE]PLUMBING [—]RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2809 3.7lkW/14PCS
Master Solar PMT#:PMT14-00706
PROJEcTADDRESS 28864 Skylark Street
ASSESSOR'S PARCEL NUMBER 333 1 -C)ZZ LOT 32 TRACT 31582-1
PROPERTY OWNER'S NAME Lermar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANTNIAME Lermar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (961)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRAcrOR'S NAME Lermar Homes of California,Inc. OWNERBUILDER? ZYESE:INO
BUSINESSNAME Lennar Homes of California, Inc.
ADDRESS 980 Mantecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturei@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $9,353.40 L SQ FT
APPLICANT'S SIGNATURE DATE 12101/2016
DEPARTMENT DISTRIBUTION co CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE PAID AMOUNT
AMOUNT 0 CASH 0 CHECK# 0 CREDIT CARD VISA/MC
PLAN CHECK FEES PAIDAMOLINT 0 CASH 0 CHECK# 0 CREDIT CARD VIsAjmc
[OWNER BUILDER VERIFIED 0 YES 0 NO DL NUMBER NOTARIZED LETTER 0 YES '0 NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityefrnenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 1 3.71KW I LOCATIONS INDICATED BY THE ILLUSTRATION.
FODULE 14 PCS.I HYUNDAI I HjS-S265RG(265W) BUYER:
INVERTER 1 14 PCS.1 ENPHASE I M215-60-2LL-S22-IG
ROOF TYPE I TILE W1 COMPOSITE SHINGLE UNDER ARRAY DATE: MENIFE
SUB-ARRAY INFORMATION
I ARRAY#1 ARRAY#2 1 ARRAY#3 N'LDING AND !
T
MOD QTY to 4 A BUYER:
i�_
ILT 23- 27- 1 NA' LA N APPRIC VAI
AZIMUTH 255- 345- 1 NA' DATE:
� !AIEDB4
CitY of Menifee
Building Depi
of1these pla is shal,
DEC 13 2 0 i�s oroval of,any violati In of a
-.ulations and ordinai ces, 7
Received isite until completior.
F———— — —- — — ————————
16'-5"ARRAY SOLADECK WIRE
,L3 TRANSITION BOX
IT-Y FLASHING (UNDER ARRAY)
IMMMIMMMUNNOM
PV AC DISCONNECT
EXTERIOR-GARAGE—",-,,
UTlLITY METER&
MAIN SERVICE PANEL---'
(VERIFIED BY BUILDER) t
L
SR9
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2809 ELEVATION B
ORIENTATION I L—Org-T2
MENIFEE HILLS LIENNAR: ORIGINAL BY: JIM PARKS D .12.
980 MONTECITO DRIVE.#302 REVIEWED BY:TOM FIDDES DATE:15.12.02
CORONA,CA 921179 REV.# BY DATE DESCRIPTION
01 KA 16.7.20 PLAN REVISION ;pmannasiud
DWG TITLE: PAGE #; SCALE: SITE LOCATION: SOLAR
- 4571 Bmadway Street
INDIVIDUAL 28864 SKYLARK STREET Boulder.CO 803M
PLOT PLAN 1 1/16"= 1*-0' MENIFEE.CA 303.447.OWD
SYSTEM LAYOUT I
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE lCALC UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% C 37 INV.MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP.AMBIENT LOW(THIN) ASHRAE EXTR.MIN 'C �2 INV.MAX POWER.(WAC MAX) INVERTER SPEC WATTS(AQ 225
TEMP.MODULE TEST(TTEST) MODULE SPEC C 25 INV- INPUT V.(Voc MAX) INVERTER SPEC VOLTS(00 48
TEMP.DELTA LOW(TOELTA) TmiN-TTEST C -27 INV.OUTPUT V,(VAc NOM) INVERTER SPEC VOLTS(Ad 240
MOD.MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HtS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AQ 0.9 �c T D
MOD.POWER STC(P) MODULE SPEC WATTS 00 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(Dc) 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(DC) 31.30 INV.GROUNDING RTER SPE ISOLATED
MOD.OPEN CCT. VOLTAGE(Voc) MODULE SPEC VOLTS 00 38.10 INV- M L BRANCH CCT. 1 !NNYVE QTYB� OTY 14
MODULE SPEC V/-C -0.114 BRA'TYA TPUT. MAXBG I (lAC-lNV.GTYBC) AMPS(Ad 12.60
MOD.COEFF.VOLT/TEMP(COEF) wCw .FU
MOD.MAX VOLTAGE(VMAXMKID) (Voc+(TD-COEF)) VOLTS(OC) 41.18 INV. QTAL I INV.QTYT OTY 14
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS 00 8.50 TOTAL SYSTEM OUTPUT,IMAXTS (IAC-INV.QTYT) AMPS(AC) 12.60
MOD.SHORT CCT.CURRENT(Isc) MODULE SPEC AMPS(n) 9.00
MOE).MAXIMUM CURRENT(IMAX) OSC*1.25) AMPS(Dc) 11.25
111W AMPACITY REQ'D,PER NEC (]MAX-1.25) AMPS 00 14.06
SERIES FUSE RATING.MAX MODULE SPEC AMPS(oc) 1 15
ELECTRICAL EQUIPMENT SCHEDULE v onstru
KEY QTY 14ANUFACTURER MODEL NOTES TRADE al: ans ol
1 14 HYUNDAI HiS-S265RG(265W) PV MODULE SOLAR
2 14 ENPHASE M215-6O-2l_l_-S2Z-IG PVINVERTER SOLAR et 0 appro
3 2 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX.NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R,240V.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR. 120V SOLAR
6 1 TDD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TED CATS PORT FOR SOUR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS; I X 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TED PV BREAKER.I x 20A-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
D St
1 5T�VICEi�PEATNEERL..MIN. 125A BUS BLDR.Ft E��
ILIT P
1 12, 11 41 1 RLD H.120/240V.200A BLDR E12C.
1 12 It I TED I TED I GROUNDING ELECTRODE UFER BLOR.Ei_EC
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COUD: I(AMPACITY-TEMP. DEBATE -FILL DERATE)vs.REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM I AMPACITY AT TERMINALS. Y.L.REDID.(IN"* 1.25) PANEL MFR. CUTLER-HAMMER
CALC. AMPACITY WIO TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
KEY SIZE CU/AL INSULATION TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU I THWN-2 COU 30 0.76 0 22.80 12.60 ALLOWED PV PER NEC AMPS 40
I I - TERM 25 25 15.75 20 PV OCPD DEVICE USED I AMPS 20
#10 CU NM-B COU 1 340 0.91 1.0 36.40 12.60
TERM g 35 15.75 20
c- #10 1 CU I NM-8 COU 1 40 0.91 1-0 36.40 12.60
1 TERM 1 35 35 15.75 20
CONDUCTOR SCHEDULE
LEY 1 CONDUCTORS 1 CUIAL 1 TYPE 1 LOCATION TRADE
A 1-#12 ENGAGE CABLE,I-#6G.FREE AIR I CU I TC-ER I ARRAY SOLAR
B I 5-#Io. 1-#10 EGC I Cu I NM-B(ROMEX) I INTERIOR I SOLAR
C 1 3-410. 1-#10 EGC I CU I NM-B(ROMEX) I INTERIOR I SOLAR
D I CAT5E,ETHERNET CABLE I CU I CAT5E INTERIOR I SOLAR
SEE NOTE 15
SAllp
15
20A/V
_IN
G
GIL 11 MG
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 3-71 ALM
LOT*32
MENIFEE HILLS LENNAR: ORIGINAL BY: JIM PARKS I DATE:I
980 MONTECITO DRIVE.#302 REVIEWED BY:TOM FIDDES I DATE-15.12.02
CORONA.CA 92879 REV.# BY DATE DESCRIPTION
ol KA 16.7.20 PLAN REVISION SOLAR
DWG TITLE: PAGE#: SCALE: I
I SITE LOCATION 4571 Bra�ay Steel
INDIVIDUAL 2BB64 SKYLARK STREET BoLdder.CO 80304
PLOT PLAN I NTS MENIFEE,CA 303.447.0300
ELECTRICAL
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
1)ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 4y D.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED,
5)PV ARRAY WILL BE A MINIMUM OF 5"ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION I
MANUAL,VERSION 227.3.PUS 140113-ICC.JANUARY 2014. �- RTIV
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH 01 SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE
OF THE PV ARRAY I SUB-ARRAY.
8)UNIRAC SOLARMOL94T REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3%
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT W)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE-BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION. .,a peri
deral,s
ans mu!
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL)-
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NECICEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINTIFINISH. PANTIFINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE U1703.IEC61646.IEC61730.
0)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS Of WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED LINDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING.OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRI14TED LETTERING. EIACKGROL94D WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT 1%
19)ALL WIRINGIRACEWAYS/JUNCTION BOXES WILL BE MARKED*PHOTOVOLTAIC POWER SOURCE.'OR EOUIVALENT�WIRINGIRACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY JIM PARKS DATE:15.12.01
MENIFEE HILLS 980 MONTECITO DRIVE.#302 REVIEWED BY: TOM FIDDES DAT :15.12.02
CORONA.CA 92879 REV.# BY— DATE DESCRIPTION
—DI 16.7.20 PLAN REVISION Masties
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: SOL I.L�.
4571 Bmadway SVeat
INDIVIDUAL 28864 SKYLARK STREET 13..Id�.CO 80304
PLOT PLAN 3 NTS MENIFEE,CA 3M."7.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE 4T
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY) oran
Ir city
kept on the
RV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER a
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 12.6 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
MENIFEE HILLS LENNAR: ORIGINAL BY: JIM PARKS DATE:15.12.01
980 MONTECITO DRIVE.#302 REVIEWED BY:TOM FIDDES DATE:15.12.02
CORONA,CA 92879 REV.# BY I DATE A DESCRIPTION
01 KA 1 16 7.20 PLA REVISION VnaMC35t;d
SOLAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Bma�ay S".t
INDIVIDUAL 28Bb4 SKYLARK STREET Boulder.CO 130304
PLOT PLAN 4 NTS MENIFEE,CA 303."7.0300
PLACARDS I