PMT16-01970 City of Menifee Permit No.: PMT16-01970
29714 HAUN RD.
SACCEL/-> MENIFEE,CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 07/22/2016
PERMIT
Site Address: 28939 SKYKLARK ST, MENIFEE,CA Parcel Number: 333-631-031
92584 Construction Cost: $10,689.60
Existing Use: Proposed Use:
Description of SOLAR TR 31582-1 MENIFEE HILLS
Work: 16 MODULES,4.24KW
LOT 78
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ALISO VIEJO,CA 92656
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO,CA 92656
Fee Description (3ly Amount
Solar,Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template..rpl Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
Menifee
DATE 06/15/2016 PERMIT/PLAN CHECK NUMBER 1�Q� O 1
TYPE: []COMMERCIAL Q RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA ❑SIGN
SUBTYPE: QADDITION ❑ALTERATION ❑DEMOLITION ❑ELECTRICAL [—]MECHANICAL
[—]NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 3404-4.24 kW/16 PCS
Master Solar Permit: p MT I LI — 7
PROJECT ADDRESS 2893Akylark St., Menifee, CA 92584
ASSESSOR'S PARCEL NUMBER 333-631-031 LOT 78 TRACT 3�5 2—
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremish.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennaccom
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A8B
VALUATION $ $ 10,689.60 L SQ FT
APPLICANT'S SIGNATURE DATE 0 6/1 512 01 6
CITYSTAFF USE ONLY Aww
DEPARTMENT DISTRIBUTION �.q CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING IRE GREEN SMIP VV
INVOICE
AMOUNT PAID AMOUNT O CASH O CHECK# 0 CREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT O CASH O CHECK It OCREDITCARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 4.24 NW I LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 16 PCS. HYUNDAI HIS-S265RG(265W) BUYER:
INVERTER 16 PCS.1 ENPHASE I M215-60-2LL-S22-IG
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION f^�5'
ARRAY#1 ARRAY#2 ARRAY#3 �"' t y C ENII
MOD OTY 16 NA NA BUYER: p /'�
TILT 23• NA° NA° DATE: �afir DING NI.
AZIMUTH 112° NA° NA•
City di g Dept
_�.N ARP OV,
Building Dept
JUN 2 81 FVIEVvED
Receive
: rava!of these laps sh
2'-2'FL SHIN aoLrinalof,anyviol tionol
2T-2'FLASHING 3'
I L'9013tions and Or(II antes,
--------- f , )ohsitO Until completon,
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
————___————
J PV DISCONNECT
{ w y � EXTEE RIOR-GARAGE
L------- UTILITY METER&
MAIN SERVICE PANEL
— _J (VERIFIED BY BUILDER) �y
9
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 3404 ELEVATION B-REVERSE ®v
ORIENTATION I LOT#078
ORIGINAL BY: ANGELA BURKE DATE:11.25.2015
MENIFEE HILLS LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:JIMMY METER I DATE 1.27.2015
CORONA,CA 92879 REV.# BY DATE I DESCRIPTION
namastA.
eoue
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway SVeet
INDIVIDUAL 28939 SKYLARK STREET Baum",,CO ffl 0
PLOT PLAN 1116'=1'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE.CA INV. MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV. MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV. MAX POWER,(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC 'C 25 INV. INPUT V.(VDC MAX) INVERTER SPEC VOLTS(DC) 48
TEMP,DELTA LOW(TDELTA) THIN-TTEST °C -27 INV.OUTPUT V.(VAC NOM) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(DC) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(DC) 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547,
MOD.OPERATING VOLTAGE WHO MODULE SPEC VOLTS(oc) 31.30 INV.GROUNDING INVERTER SPEC I ISOLATED
MOD.OPEN CCT, VOLTAGE NOD) MODULE SPEC VOLTS(DC) 38.10 INV.CITY,MAX/BRANCH CCT. INV.OTYBC QTY 16
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/PC -0.114 BRANCH CCT.OUTPUT.IMAX8c I(IAC`INV.QTYSC) AMPS(AC) 14.40
MOD.MAX VOLTAGE(VMA%MOD) (VOC♦(TD•COEF)) VOLTS(Dc) 41.18 INV.QUANTITY.TOTAL I INV.OTYT QTY 16
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS CDC) 8.50 TOTAL SYSTEM OUTPUT,IMAziS (IAC`INV.QTYT) AMPS(AC) 14.40
MOD.SHORT CCT.CURRENT(ISC) MODULE SPEC AMPS(oc) 9.00
MOD.MAXIMUM CURRENT(IMAX) Osc` 1.25) AMPS(DC) 11.25
MIN.AMPACITY REQ'D,PER NEC (IHAX`1.25) AMPS(DC) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(DC) 15 - -
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE
I 16 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR
2 16 ENPHASE M215-60-2LL-S22-IG PVINVERTER SOLAR - DII$f'll
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR plUV 1011$01
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R.240V.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR :se: f appr0
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS;I X 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 2CA-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 TBD TBD SERVICE PANEL.MIN. 125A BUS BLDR.ELEL.
II TBD TBD UTILITY METER,IPH,120/24OV.200A BLDR.ELEC.
12 1 1 1 TBD I TBD I GROUNDING ELECTRODE UFER I BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
D CONDITION OF USE(COU): (AMPACITY` TEMP. DERATE•FILL DEBATE)VS.REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS.Vs.REO'D,(IMAX` 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE N/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL RESULT READ CD BUS RATING AMPS 200
TYPE DEBATES DEBATE DEBATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 A 22.80 14.40 ALLOWED PV PER NEC AMPS 40
TERM 25 25 18.00 20 PV OCPD DEVICE USED AMPS 20
B #10 LU NM-B COU 40 0.91 1.0 36.40 14.40
TERM 35 35 18.00 20
C #10 CU No COU 40 0.91 L0 36.40 14.40
TERM 35 1 35 118.00 1 20
CONDUCTOR SCHEDULE
KEY 1 CONDUCTORS CU/AL TYPE LOCATION TRADE
A I-#12 ENGAGE CABLE,I-#6G.FREE AIR Co TC-ER ARRAY SOLAR
B 1 3-#10, 1-#10 EGG CU NM-B(ROMEX) I INTERIOR I SOLAR
L 3-#10.I-#10 EGC CU NM-0(ROMEX) I INTERIOR ISOLAR 5 6 II
D I CAT5E,ETHERNET CABLE CU CAT5E I INTERIOR ISOLAR
7 • o 0
� M -
SEE NOTE 15 I 0
B
O lO
OI 2 0
O O 1204/
_ SIN
G GJ
A B C =12
I I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 4.24 KW
LOT#078
LENNAR: ORIGINAL BY: ANGELA BURKE I DATE:11.25.2015
MENIFEE HILLS REVIEWED BY;JIMMY METER DATE:11.27.2015
CORONNA,CA
980 A.CA I 2 DRIVE,#302
92879 REV.# BY DATE DESCRIPTION
nama=6
..LA[
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 4577 aO Street
PLOT PLAN 2 NTS 28939 SKYLARK STREET BO3 ldw.03.4 CO8D804
ELECTRICAL MENIFEE,CA 03.447.0300
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS.IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB M0113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH D')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2')BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP HE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'. ? a 11 R G(I
ROOFING CONTRACTOR- r�Il IYICI
D DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIOEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(0 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE)0
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAV .
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS. ol
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE. BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
`,e a permit h
euler il,state(
,fans mustbeI
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SMALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SMALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE U1.1703.IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING 15 LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING.OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL HE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
IB)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT k-
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY IQ.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
20 SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: ANGELA BURKE DATE:11.25.2015
MENIFEE HILLS 980 I DRIVE,#302 REVIEWED BY:JIMMY METER DATE:11.27.2015
CORONNk A,C LA A 92079 REV.# 8Y DATE I DESCRIPTION
n ZOLA.
SOtM
DWG TITLE: PAGE#: I SCALE: SITE LOCATION:
INDIVIDUAL 4377 Broadway Streal
PLOT PLAN 3 NTS 28939 SKYLARK STREET BOultler,C080304
NOTES MENIFEE.CA 303.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
)AT E
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
'an
Y
in e
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER&
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 14.4 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
MENIFEE HILLS LENNAR: ORIGINAL BY: ANGELA BURKE DATE:11.25.2015
980 MONTECITO DRIVE.*302 REVIEWED BY:JIMMY METER DATE:11.27.2015
CORONA,CA 92879 REV.* BY DATE DESCRIPTION
nann(=6
DWG TITLE: PAGE 7f: SCALE: SITE LOCATION: some
INDIVIDUAL 4577 Broadway Street
PLOT PLAN 4 NTS 28939 SKYLARK STREET Boulder,CO 803N
PLACARDS MENIFEE,CA 303.447.0300