PMT16-01956 City of Menifee Permit No.: PMT16-01956
29714 HAUN RD.
�/ACCEL/� MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 0 712 2/2 01 6
PERMIT
Site Address: 30194 MUIRLANDS DR,MENIFEE,CA Parcel Number: 364-370-021
92584 Construction Cost: $6,943.00
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 10 MODULES 2.65KW
LOT 110
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ALISO VIEJO,CA 92656
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number.728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO, CA 92656
Fee Description OQt Amount fEl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_BIdg_Permit_Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
'Wenifee
DATE 0 611 5/2 0 1 6 PERMIT/PLAN CHECK NUMBER
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA [-]SIGN
SUBTYPE: ❑✓ ADDITION []ALTERATION ❑DEMOLITION ❑ELECTRICAL []MECHANICAL
[:]NEW [:]PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2077-2.65 kW/10 PCS
Master Solar Permit: PMT14-02630
PROJECT ADDRESS 30194 Mulrlands Dr., Menifee, CA 92584
ASSESSOR'S PARCEL NUMBER 364-370-021 LOT 110 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona, CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona, CA 92879
PHONE (951)817-36BO EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 72B102 LICENSE CLASSIFICATION A&B
VALUATION$ $6,943.00 L SQ FT
APPLICANT'S SIGNATURE DATE 06/15/2016
CITY STAFF USE ■NLY
- -
DEPARTMENT DISTRIBUTION .f1 CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP W
INVOICE ,^
AMOUNT - PAID AMOUNT OCASH OCHECK# 0CREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT 0CASH 0CHECK# OCREDITCARD VISA/MC
OWNER BUILDER VERIFIED OYES O NO DLNUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.citycfinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.65 KW I I LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 10 PCS.l HYUNDAI I HIS-S265RG(265W) BUYER:
INVERTER 10 PCS. ENPHASE M215-60-2LL-S22-IG
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY City of Menifee DATE:
SUB-ARRAY INFORMATION Building Dept
ARRAY#1 ARRAY#2 ARRAY#3
MOD OTY 1 10 NA NA BUYER: 1
TILT NA' NA.
AZIMUTH 90- NA' NA' JUN 2 3 20;a DATE: r3JILI
90'
R ® �t p a y 7l>J� r -AN
l e c e N �F 'c. di'� SrIVP Opersltions
Uc#1001133 Class B
.VI�
16'-5'ARRAY
2 IT-3-FLASHING '' oval of
app Oval Of,
— — —- —— — f2ist lations
jobs to until
SOLADECK n
TRANSITION WIRE
TRRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT I
EXTERIOR-GARAGE
UTILITY METERS
MAIN SERVICE PANEL l
(VERIFIED By BUILDER)
I I
I I
I l I I
L --_- r_--J L
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2077 ELEVATION B Z
ORIENTATION 2 Ru
CAMELLIA AT LEN14AR: ORIGINAL BY: GREG WONG DATE:16.04.12
900 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA DATE:16.04.12
THE LAKES CORONA.CA 92879 REV.# BY DATE I DESCRIPTION
01 AH 16.04.IB CD ECTED GMAGE D0.IMTATMN namasrd
DWG TITLE: PAGE#: SCALE: SITE LOCATION: rloue
INDIVIDUAL 4571 Bma&myStraet
30194 MUIRLANDS DRIVE Boulder,CO S0304
PLOT PLAN 1 1/16'=I'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALL UNIT DETAIL
LOCATION MENIFEE,CA INV. MAKE INVERTER SPEC ENPHASE
TEMP.AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M2I5-60-2LL-S22-IG
TEMP,AMBIENT LOW(TMIN) ASHRAE EXTR.MIN •C -2 INV.MAX POWER,(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VDC MAX) INVERTER SPEC VOLTS(DO 48
TEMP.DELTA LOW(TELLTA) TMIN-TTEST •C -27 INV.OUTPUT V.(VAC NOM) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60 94.
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV,OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AC) 0.9 '
MOD.POWER STC(P) MODULE SPEC WATTS(oc) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I -�
MOD.POWER PTC MODULE SPEC WATTS(Dc) 23B COMPLIANCE INVERTER SPEC UL174IAJE5t&' AFE
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(DC) 31.30 INV. GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT. VOLTAGE(VaC) MODULE SPEC VOLTS(00 38.10 INV. QTY.MAX/BRANCH CCT. INV.QTYBC 0TY
MOD. COEFF. VOLT/TEMP(CDEF) MODULE SPEC VPC -0.114 BRANCH CCT.OUTPUT, IMAxaC V.
NYV.QTYB[) AMPS(AC) 9.00
MOD. MAX VOLTAGE(VMAXMDD) (VOC♦(TD'COEF)) VOLTS(DC) 41.18 INV. I INV.QTYT OTY ID
MOD. OPERATING CURRENT(IMP) MODULE SPEC AMPS(DC) 8.50 TOTAL SYSTEM OUTPUT.MARTS I (IAC•INV.QTYT) AMPS
MOD. SHORT CCT. CURRENT(ISC) MODULE SPEC AMPS(DC) 9.00
MOD. MAXIMUM CURRENT(MAX) (ISC' 1.25) AMPS(DC) 11.25
MIN.AMPACITY REQ'D.PER NEC (]MAX' 1.25) AMPS(OC) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(00 15
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY MANUFACTURER MODEL NOTES TRADE SF. lanssha! not he
1 10 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR P
2 10 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR violation of YOV
3 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR P
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.240V,30A SOLAR ordinances, I his set 1
5 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR iplet10n.
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS; I X 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER, I x 20A-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 I TBD TBO SERVICE PANEL,MIN. 125A BUS BLOB. ELEC.
II I TBD TBD UTILITY METER,IPH.120/24OV.200A BLOR. ELEC.
12 1 1 1 TBD I TBD I GROUNDING ELECTRODE UFER BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
D CONDITION OF USE(COU): I (AMPACITY'TEMP.OERATE•FILL OERATE)vs.REQ'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS. VS.REQ'D.(]MAX• 1.25) PANEL MFR, CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALL. AMPACITY W/O TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE DERATES OERATE DEBATE (A) (A) CD
CD MAIN DISCONNECT I AMPS 1 200
A #12 CU THWN-2 COU 30 0.7 II.0 22.80 9.00 ALLOWED PV PER NEC AMPS 40
TERM 25 25 11.25 20 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 0.91 I.0 36.40 9.00 ^
TERM 35 35 IL25 20 ...��\
C #10 CU NM-B COU 40 0.91 1.0 36.40 9.00 Mtke Dufault --
TERM 35 35 11.25 20 Sr VP Operations
CONDUCTOR SCHEDULE IJc#1001333 ClassB
KEY 1 CONDUCTORS CU/AL TYPE LOCATION TRADE
A I-#12 ENGAGE CABLE, 1-#6G,FREE AIR I CU I TC-ER ARRAY SOLAR
B I 3-#10,1-#10 EGC I CU I NM-B(ROMEX) INTERIOR I SOLAR
C 1 3410,1-NIO EGC I Cu I NM-B(ROMEX) INTERIOR I SOLAR
D I CAT5E,ETHERNET CABLE I Cu I CAT5E INTERIOR I SOLAR 5 6 II
(D o 0
M —
SEE NOTE 15 10
O
15AIIP
O O O
OM2P
3
'N
ROOF E TER10R-GARAGE
ELECTRICAL DIAGRAM 2.65 xW
LOT#110
CAMELLIA AT LENNAR: ORIGINAL BY: GREGWONG I DATE:16.04.12
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA I DATE:16.04.12
THE LAKES CORONA,CA 92879 REV.# BY DATE I DESCRIPTION le.S0
01 AN 16.04.18 CONREMD GARAGE MIENTATI N f amast;6
DWG TITLE: PAGE#: SCALE: SITE LOCATION: SOLAR
INDIVIDUAL 30I9L MUIRLANDS DRIVE 4571 Broadway Street
PLOT PLAN 2 NTS Bouldw,CO 8D304
ELECTRICAL MENIFEE,CA 303,447,0300
STRUCTURAL NOTES:
SOLAR CONTRACTOR- Mike Dufault
D ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C. Sr VP OperdNOns
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE. LIL#1DO1133 Class B
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATIO,N{�n/L
MANUAL,VERSION 227.3.PUB 140113-ICC,JANUARY 2014. THE
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(1')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE `LEPA
OF THE PV ARRAY/SUB-ARRAY.
B)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
D DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 00 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK
)w4t..4
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SMALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
rrued to be a permit
of the fed!ral,stat(
'qroved p:ai s must b
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SMALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250J22.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: GREG WONG DATE:16.04.12
CAMELLIA AT REVIEWED BY:SHAUN MARUNA DATE:16.04.12
9B0 NA,CA I92 DRIVE,%302
THE LAKES CORONA,GA 92879 REV.# BY DATE DESCRIPTION
01 All 16.04.18 ORgRECSEO GARAGE ONIEMATGN f-�21ncirricist*
uR
DWG TITLE: PAGE#: SCALE: �c
SITE LOCATION: 4371&o CO8Street
INDIVIDUAL 30194 MUIRLANDS DRIVE Boulder,
C08030/
PLOT PLAN 3 NITS MENIFEE,CA
NOTES 303.447.0300
Ik��
Mike Duhult
Sr VP Operations
Uc#1001133 Class B
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
DATE
or an
A on the
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER B
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 9.o A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: GREG WONG DATE:16,04.12
CAMELLIA AT LENNAR:
980 MONTELITO DRIVE.#302 REVIEWED BY:SHAUN MARUNA DATE:16.04.12
THE LAKES CORONA,CA 92B79 REV.# BY DATE DESCRIPTION
OI All 16.04.1a [U IMUEO GARAGE ORIENGTION (lanlasb@
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: GoEAe
INDIVIDUAL 4677 B=dway Street
PLOT PLAN L NTS 30194 MUIRLANDS DRIVE BMW&.CO B03
PLACARDS MENIFEE,CA 303.447.0300