PMT16-01955 City of Menifee Permit No.: PMT16-01955
29714 HAUN RD. Type: Residential Electrical
-1►CCEL/? MENIFEE,CA 92586
`."Wk.- MENIFEE Date Issued: 0 7/2 212 01 6
PERMIT
Site Address: 30182 MUIRLANDS DR, MENIFEE, CA Parcel Number: 364-370-020
92584 Construction Cost: $8,331.60
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 12 MODULES 3.18KW
LOT 109
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ALISO VIEJO,CA 92656
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO,CA 92656
Fee Description ON Amount
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bidg_Permit_Template.rpt Page 1 of 1
APPLICATIONBUILDING & SAFETY PERMIT/PLAN CHECK
'.2;Menifee
DATE 0 6/1 512 0 1 6 PERMIT/PLAN CHECK NUMBER MT(cO---O i -
155
TYPE: [:]COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA []SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION []DEMOLITION [:]ELECTRICAL [-]MECHANICAL
[]NEW [-]PLUMBING [:IRE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2785-3.18 kW/12 PCS
PMTW- 02G30
PROJECT ADDRESS 3D162 Muirlands Dr., Menifee, CA 925B4
ASSESSOR'S PARCEL NUMBER 364-370-020 LOT 109 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 9B0 Montecito Dr.,Suite 302, Corona, CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 960 Montecito Dr.,Suite 302, Corona, CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION $ $8,331.60 SO FT L SQ FT
APPLICANT'S SIGNATURE DATE 0 611 5/2 01 6
CITYSTAFF USE ONLY
DEPARTMENT DISTRIBUTION lC W CITYOFMENIFEEB BER USINESSLICENSENUM
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE G PAID AMOUNT
AMOUNT q l OCASH 0CHECK# 0CREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT O CASH O CHECKa O CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED O YES 0 NO DL NUMBER NOTARIZED LETTER O YES 0 NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-572-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.18 RW I LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 12 PCS. HYUNDAI I HiS-S265RG(265W) BUYER:
INVERTER 12 PCS. ENPHASE I M215-60-ZLL-S22-IG
ROOF TYPE TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3
MOD OTY 12 NA NA BUYER:
TILT 23' NA' NA'
AZIMUTH 90- NA' NA' DATE:
City of Menifee
Building Dept M�ik)eoDteDic MFE
Sr V P OperatloasA N D
JUN 2 3 2016 LkR 1001133 Class B
l
Received
29'-8'ARRAY
30'-6'FLASHING
' . . xe^.Ian$Steal
, �loiatinnof;
— - - ---� :� ;Icrdinantes. '
i. Emletion.
I I
I I
I p I I
I
I
SOLAOECK WIRE
——— TRANSITION BOX
(UNDER ARRAY)
I PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER B
I I MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
I I I
i - --------�
9
NOTE: DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2785 ELEVATION A-REVERSE z
ORIENTATION 2 # 10
ORIGINAL BY: GREG WO DATE:16.04.12
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE, #302 REVIEWED BY:SHAUN MARUNA DATE:16.04.12
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION •�
to namast;e
soiAc
DWG TITLE: PAGE#: SCALE:
517E LOCATION:. 4571 Broadway Street
INDIVIDUAL 30182 MUIRLANDS DRIVE Boulder,CO 80304
PLOT PLAN I I/16'= I'-0'SYSTEM LAY MENIFEE,CA 303.447.0300
OUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE /CALL UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE, CA INV. MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(THAR) ASHRAE 2% °C 37 INV. MODEL INVERTER SPEC M215-60-21-L-S22-I13
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV. MAX POWER, (WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VOC MAX) INVERTER SPEC VOLTS(DC) 48
TEMP,DELTA LOW(TDELTA) THIN-TTEGT °C -27 INV. OUTPUT V.(Vac NOM) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV. OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD. PART NUMBER MODULE SPEC HIS-S265RG INV. OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AC) 0.9
MOD. POWER STC(P) MODULE SPEC WATTS CDC) 265 1 INV. PHASE QUANTITY INVERTER SPEC PHASE I
MOD. POWER PTC MODULE SPEC WATTS CDC) 25B COMPLIANCE INVERTER SPEC ULI741/IEEE1547
MOD. OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS CDC) 1 31.30 INV. GROUNDING 1 INVERTER SPEC ISOLATED
MOD. OPEN CCT. VOLTAGE(VOC) MODULE SPEC VOLTS(DC) 38.10 INV. CITY,MAX/BRANCH CCT. INV.QTYB9 QTY 12
MOD. COEFF. VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT. OUTPUT, IHAXBC CIAC-INV.QTYBU AMPS(AC) 10.80
MOD. MAX VOLTAGE(VMAXMOD) (Voc+ (TD-COEF)) VOLTS(Dc) 41.18 INV. QUANTITY,TOTAL INV.QTYT CITY 12
MOD. OPERATING CURRENT (IMP) MODULE SPEC AMPS CDC) 8.50 TOTAL SYSTEM OUTPUT, IMAXTS CIAO.1NV.OTYT) AMPS(Ac) 10.80 ^I� I
MOD. SHORT CCT. CURRENT(ISC) MODULE SPEC AMPS CDC) 9.00 �.
MOD. MAXIMUM CURRENT(IMAK) (Isc• 1.25) AMPS (OC) 11.25
MIN. AMPACITY REQ'D, PER NEC (IMAX- 1.25) AMPS(DC) 14.06
SERIES FUSE RATING, MAX MODULE SPEC AMPS(DC) 15
ELECTRICAL EQUIPMENT SCHEDULE
KEY CITY MANUFACTURER MODEL NOTES TRADE
1 12 HYUNDAI HIS-S265RG (265W) PV MODULE SOLAR
2 12 ENPHASE M215-60-2LL-S22-IG PVINVERTER SOLAR
3 1 RSTC /SOLADECK 0786-3R5 PV ROOF JUNCTION BOX, NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT, NEMA 3R,24OV,30A SOLAR
5. 1 ENPHASE ENVOY PV DATA MONITOR, 120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR I:nn;truer t(
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR ,!<_i0;18 Of j te
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I x ISA-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER, I X 20A-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR J apprOV d
10 TBD TBD SERVICE PANEL,MIN. 125A BUS BLDR. ELEC.
II I TBD I TBD I UTILITY METER, IPH, 120/24OV,200A I BLDR. ELEC.
12 1 I 1 TBD I TBD I GROUNDING ELECTRODE UFER I BLDR. ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COU): I (AMPACITY'TEMP. DERATE - FILL DERATE)V5. REO'D(IMAX) ITEM I UNIT I PANEL
2)TERMINALS(TERM): I AMPACITY AT TERMINALS. vs. REQ'D, (IMAX' 1,25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC, AMPACITY W/0 TEMP. FILL RESULT REp'D OLD BUS RATING I AMPS 1 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT I AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 10.80 ALLOWED PV PER NEC I AMPS 40
TERM 25 25 13.50 20 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 10.80 /T
TERM 35 35 1 .50 20
C #10 CU NM-8 TCOUER 40 0.91 L0 36.40 1 .
TERM 35 35 130.50 50 20 Mlke Dufault
CONDUCTOR SCHEDULE Sr VPOperations
Lick 1D01133 Class 8
KEY CONDUCTORS CU/AL TYPE LOCATION TRADE
A I-#12 ENGAGE CABLE, I-#6G, FREE AIR CU I TC-ER JARRAY SOLAR
B 3-#10, 1-#10 EGC CU NM-B (ROMEX) INTERIOR SOLAR
C 3-#10, 1410 EGC CU NM-S (ROMEX) I INTERIOR SOLAR
D CAT5E,ETHERNET CABLE CU CATSE I INTERIOR SOLAR 5 6 11
7 e o u O
SEE NOTE 15IL2F
co
yO
O O O
♦N
G G G
A B T_ 12
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 3.IBKW
LOT#109
CAMELLIA AT LENNAR: ORIGINAL BY: GREG WO DATE:16.04.IZ
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA I DATE:16.04.12
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION .�
�tanamast6
DWG TITLE: PAGE#: SCALE: SSOLAR
ITE LOCATION:
INDIVIDUAL 4571 Broadway Street
PLOT PLAN 2 NTS 30182 MUIRLANOS DRIVE Boulder,CO 80304
ELECTRICAL I
MENIFEE,CA 303.447.0300
STRUCTURAL NOTES
SOLAR CONTRACTOR-- Mike DUfaUlt
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C. Sr VP Operations
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE. LICO 1001133 Class B
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3, PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I')SPACE BETWEEN PV MODULES. SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21)BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
B)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
ANCE
ETWEEN ARRAY EDGE AN TRANSITIN FLASHING (COMPOSITION TO TILE)
BE A
LL
IMUM
2)26 GAUGE TBINTERLOCKING FLASHING DSI EWALLOTO BE INSTALLED ALONG THE LENGTH IOF THE VINARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE THE 41
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 09 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE. PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE. BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
,per t fa
)al,st to c
ELECTRICAL NOTES: i musl be l
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646, IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS. WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING, OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
I6)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING /PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING /PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY: GREG WONG DATE:16.04.12
CAMELLIA AT LENNAR: REVIEWED BY:SHAUN MARUNA DATE:16.04.12
CORON9130 A,CEAI98791VE,#302 REV.# BY DATE DESCRIPTION •'
THE LAKES tMCISr;e
sasee
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
treet
INDIVIDUAL 45T1 Ber,CO 8 304
PLOT PLAN 3 NTS MENI MUIRLANOS DRIVE BONtleq 7. 30304
NOTES MENIFEE,CA 303.447.0300
Mike Dufault
Sr VP Operations
Licit ID01133 Class B
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
1> 'ATE
an
SOLADECK WIRE '(
1> TRANSITION BOX
(UNDER ARRAY) it,the
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 10.8 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: GREG WONG I DATE:16.04.12
CAMELLIA AT LENNAR: REVIEWED BY:SHAUN MARUNA DATE:16.04.12
CORONA,CA I9 B791VE,#302 REV.# BY DATE DESCRIPTION •�
THE LAKES lanamasbe
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
treet
INDIVIDUAL 4377lder,C Broadway 304
PLOT PLAN L NTS MENI MUIRLANDS DRIVE Boulder, 7. 30304
PLACARDS MENIFEE.CA 303.447.0300