PMT16-01951 City of Menifee Permit No.: PMT16-01951
29714 HAUN RD. Type: Residential Electrical
<ACCELA. MENIFEE,CA 92586
MENIFEE Date Issued: 0712 2/2 01 6
PERMIT
Site Address: 29669 ARGYLE CIR,MENIFEE,CA 92584 Parcel Number: 364-360-034
Construction Cost: $8,331.40
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 12 MODULES 3.18KW
LOT 125
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ALISO VIEJO,CA 92656
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO,CA 92656
Fee Description O0t Amount(Sl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpt Page 1 of 1
BUILDING & SAFETY • . . P •
`Menifee
DATE 06/15/2016 PERMIT/PLAN CHECK NUMBER
TYPE: []COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA []SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION ❑DEMOLITION ❑ELECTRICAL ❑MECHANICAL
[_]NEW [—]PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2785-3.18 kW/12 PCS
Master Solar Permit: PMT14-02630
PROJECT ADDRESS 29669 Argyle Circle., Menifee, CA 92584
ASSESSOR'S PARCEL NUMBER 36 q-3gn -03y LOT 125 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lerner Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona, CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION $ $8.331.40 SO FT I FT
APPLICANT'S SIGNATURE DATE 0 611 5/2 01 6
DEPARTMENT*DISTRIBUTION 0p CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PG FIRE GREEN $tCASH
INVOICEpAID AMOUNTAMOUNT CHECKp O CREDIT CARD VISA/MC
PLAN PAID AMOUNT CHECK# O CREDIT CARD VISA/MC
OWNER BUILDER VERIFIED O YES O NO DLNUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-5777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.18 KW I I LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 12 PCS.I HYUNDAI I HIS-3265RG(265W) I BUYER:
INVERTER 12 PCS.1 ENPHASE I M215-60-2LL-S22-I6
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
L
ARRAV#I 1 ARRAY#2 1 ARRAV#3 �• �- YJLI
MOD OTY 12 1 NA I NA BUYER: , I YIItY ATILT 23° NA• NA•
AZIMUTH 180° NA- NA- DATE:
City of Menifee
Building Dept
JUN2
Received In,l Of thes 2 plans
+I 'wal of,aryv latior
"g`;ations and or financi
01'3:teuntilcom I
1 ARRAY p hon.
20'-7'-T FLASHING a.-I'
I
I
p
� I -
I I
SOLADECK WIRE
TRANSITION BOX ,
(UNDER ARRAY)
I � �
I I
PV AC DISCONNECT `
EXTERIOR-GARAGE
UTILITY METER e
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
N
PLAN 2785 ELEVATION 8
ORIENTA ION 3 LO #in
CAMELLIA AT LENNAR: ORIGINAL BY: DESIREE WILLIAMS I DATE:I6.4.IL
980 MONTECITO DRIVE,.#302 REVIEWED BY:SHAUN MARUNA DATE:16.4.14
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTIONDWG 'd namasb�
104A!
TITLE: PAGE#: SCALE: SITE LOCATION:
IND] DUUAA
4571&oadway SVeet
29669 ARGYLE CIRCLE Boulder,CO 80304
PLOT PLAN 1 1/16'= 1'-0' MENIFEE,CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC I UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% •C 37 INV.MODEL INVERTER SPEC 11215-60-2LL-S22-I13
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN •C -2 INV. MAX POWER,(WAD MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEGT) MODULE SPEC •C 25 INV. INPUT V.(Vo[MAX) INVERTER SPEC VOLTS(DC) 4B
TEMP,DELTA LOW(TEELTA) TnIN-TEEST °C -27 INV.OUTPUT V.(VAC NOM) INVERTER SPEC VOLTS(AC) 240
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD,PART NUMBER MODIRE SPEC HIS-S265RG INV.OUTPUT CURRENT,IA[ INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(oc) 265 INV.PHASE OUANTITV INVERTER SPEC PHASE I '
MOD.POWER PTC MODULE SPEC WATTS(00 238 COMPLIANCE INVERTER SPEC UL1741/IEEE15,4
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(oc) 31.30 INV.GROUNDING INVERTER SPEC ISOLATED i° DI
MOD.OPEN CCT.VOLTAGE(VOC) MODULE SPEC VOLTS(OD) 38.10 INV,CITY,MAX t BRANCH CCT. INV.OTYec OTY 12
MOD.COEFF.VOLT/TEMP(COEF) MODULES V/•C -0.114 BRANCH CCT.OUTPUT,Inazec (IAC•INV.QTYec) AMPS(AC) 10.80
MOD.MAX VOLTAGE(VMAXMOD) (VOC+(TO•CDEF)) VOLTS(oU 4LO INV.QUANTITY,TOTAL INV.OTYNV.QTYT)T OTY 12
MOD. OPERATING CURRENT(IMP) MODULE SPEC AMPS(00) 8.50 TOTAL SYSTEM OUTPUT,IM (IA AZTS C•I AMPS(AC) 10.80
MOD.SHORT CCT.CURRENT Usc) MODULE SPEC AMPS Toe) 9.00
MOD.MAXIMUM CURRENT(IMAX) (ISC• 1.25) AMPS(DQ 11.25
MIN.AMPACITY REO'D.PER NEC (IMAX• 1.25) AMPS(DC) 14.06
SERIES FUSE RATING,--MAX MODULE SPEC AMPS(m) 15 _
ELECTRICAL EQUIPMENT SCHEDULE
KEY OTY I MANUFACTURER MODEL I NOTES TRADE
1 12 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR
2 12 ENPHASE M215-60-2LL-S22-IG PVINVERTER SOLAR no',be cc nstrue,
3 1 1 RSTC/SOLAOECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R.24OV,30A SOLAR 'nr prOvlsl ins of t
5 I ENPHASE ENVOY PV DATA MONITOR,120V SOLAR his set of pprOV1
6 I TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 I TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS;I X 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL,MIN. 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER.IPH.120/24OV,200A BLDR.ELEC.
12 1 TBD 1 TOD I GROUNDING ELECTRODE LIFER BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
U CONDITION OF USE(COU): I (AMPACITY•TEMP.DERATE•FILL DERATE) Vim.,REQ'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS. VS.REO'D.(Im"• 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE OERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 1200
A #12 CU THWN-2 I COU 1 30 1 0.76 1.0 1 72.An I 10.80 I ALLOWED PV PER NEC AMPS 140
TERM 25 25 13.50 20 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 0.91 1.0 1 36.40 1
I0.80
TERM 35 35 13.50 20
C #10 CU NM-B COU 40 10.91 11.0 1 36.40 110.80
TERM 1 35 1 1 1 35 113.50 1 20
CONDUCTOR SCHEDULE
KEY I CONDUCTORS i CU/AL I TYPE I LOCATION I TRADE
A -#12 ENGAGE GABLE.I-#6G.FREE AIR CU TC-ER ARRAY SOLAR
B 3-#10. -#10 EGC LU NM-8
(ROMEX) INTERIOR SOLAR
C 3-#10.1-#10 EGC CU NM-B(ROMEX) INTERIOR I SOLAR
D I CATSE,ETHERNET CABLE LU LATSE INTERIOR ISOLAR
7 R o a
5 6 II
M —
SEE NOTE 15 10
iO
O
0 'N
3
G' G�
A B C =12
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 318 XW
LOT#125
LENNAR: ORIGINAL BY: DESIREE WILLIAMS DATE:
CAMELLIA AT 16.4.1E
98D MONTECITO DRIVE.#302 REVIEWED BY:SHAUN MARUNA DATE:16.4.14
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namasbe
DWG TITLE: PAGE*: SCALE: SOLAR
SITE LOCATION:
treet
INDIVIDUAL 29669 ARGYLE CIRCLE 45711der.0 8 304
PLOT PLAN 2 NTS BOOIEeF,C080304
ELECTRICAL MENIFEE.CA 303.447.0300
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
S ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLAOECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'5 INSTRUCTIONS. IT WILL BE FLASHED AMID SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL.VERSION 227.3,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH 0")SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(29 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY. (�
8)UNIRAC SOLARMOLNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'. 1 7ME
ROOFING CONTRACTOR-
D DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION, IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(10 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
)e Permit f(
-del it,state c
Ins TiustbeI
ELECTRICAL NOTES:
GENERAL-
O ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN ACONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH, PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703. IEC61646.IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRG-INVERTER SYSTEM.
10 MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS. WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY: DESIREE WILLIAMS DATE:I .4.14
CAMELLIA AT LENNAR: REVIEWED BY: SHAUN MARUNA DATE:16.4.14
CORONA CA 92
THE LAKES 980MONTECI DRIVE,#302
879 REV.# BY DATE DESCRIPTION
namaste
sovAv
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Broadxay Sheet
INDIVIDUAL 29669 ARGYLE CIRCLE Boulder,CO 80304
PLOT PLAN 3 NTS MENIFEE,CA
NOTES 303.447.0300
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
i
wa
DATE
ran
y
SOI-ADECon the
WIRE
TRRANSITIOANSITIO N BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 6
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 10.8 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: DESIREE WILLIAMS DATE:16.4.14
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARUNA DATE:16.4.14
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
o namasbe
>i4lAII
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Broaftay Street
INDIVIDUAL 29669 ARGYLE CIRCLE Boulder.CO W304
PLOT PLAN 4 NTS MENIFEE,CA
303.447.0300
PLACARDS