PMT16-01948 City of Menifee Permit No.: PMT16-01948
29714 HAUN RD.
SnCCEL/-> MENIFEE,CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 0 7/2 212 01 6
PERMIT
Site Address: 29705 ARGYLE CIR,MENIFEE,CA 92584 Parcel Number: 364-360-031
Construction Cost: $7,650.40
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 11 MODULES 2.92KW
LOT 122
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ALISO VIEJO, CA 92656
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number.728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO, CA 92656
Fee Description Ply Amount fE1
Solar,Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carded on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit Template.rpt Page 1 of 1
BUILDING • SAFETY PERMIT/PLANAPPLICATION
h:
,&Menifee
DATE 06/15/2016 PERMIT/PLAN CHECK NUMBER
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILEHOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑✓ ADDITION []ALTERATION ❑DEMOLITION ❑ELECTRICAL []MECHANICAL
❑NEW []PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2399-2.92 kW/11 PCS
Master Solar Permit: PMT14-02630
PROJECT ADDRESS 29705 Argyle Circle., Menifee,CA 92584
ASSESSOR'S PARCEL NUMBER 36q - 360 -031 LOT 122 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona, CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION $ $7,650.40 S L SO FT
APPLICANT'S SIGNATURE DATE 06/15/2016
DEPARTMENT DISTRIBUTION VO I CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN (00 SMIP
INVOICE �� PAIDAMOUNT
AMOUNT O�"��! OCASH OCHECK# :'CREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT ^CASH O CHECK# O CREDITCARD VISA/MC
OWNER BUILDER VERIFIED O YES NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM DTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 2.92 8W I LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE II PCS.I HYUNDAI HIS-S265RG (265W) BUYER:
INVERTER II PCS.j ENPHASE I M2I5-50-2LL-S22-IG
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#I 1 ARRAY#2 ARRAY#3 i.l I Y OF MENIF E
MOD OTY II NA NA BUYER:
TILT NA• I NA' DATE: FUILDINGAN SAF
AZIMUTH 155'55° NA' NA-
City of Menifee
Building Dept i'LAN APPROV L
JUN 2 3
REVIEWED B
R e c e I
=lpproval of these plans s iall not
approval of,any violation if any p
r igulations and ordinance 4 This:
19'-9'ARRAY jubsite until completion.
6'-W 20'-7'FLAR =
r i
i
� I
-> RANSI WIRE
T
TRANSITION BOX
(UNDER ARRAY)
f — PV AC DISCONNECT
I
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
L
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2399 ELEVATION B-REVERSE
0 N A ION LO
CAMELLIA AT LENNAR: ORIGINAL BY: DESIREE WILLIAMS I DATE:16.4.14
980 MONTECITO DRIVE,#302 REVIEWED 8Y:SHAUN MARUMA I DATE:I6.4.14
THE LAKES CORONA,CA 92079 REV.# BY DATE DESCRIPTION
Pnornast;6
DWG TITLE: PAGE#: SCALE: SOLAR
SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29705 ARGYLE CIRCLE Boulder.CO 80304
PLOT PLAN I I116'= I'-0' MENIFEE.CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC 11215-60-21-L-S22-IG
TEMP.AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER,(WAC MAX) INVERTER SPEC WATTS(Ac) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VOC MAX) INVERTER SPEC VOLTS 00 48
TEMP.DELTA LOW(ToELTA) THIN-TTEST °C -27 INV.OUTPUT V,(VAc NON) INVERTER SPEC VOLTS(AC) 240
MOO.MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,AC INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(oe) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I PAS
MOD.POWER PTC MODULE SPEC WATTS(00 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(DC) 31.30 INV.GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT.VOLTAGE(VOO) MODULE SPEC VOLTS(130 38.10 INV. OTY.MAX/BRANCH CCT. INTOTYsc1 GTY II
MOD.COEFF,VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT.OUTPUT.IMAXBc I(IAC'INV.QTYac) I AMPS(AC) 9.90
MOD.MAX VOLTAGE(VMAXMOO) (Voc+(TO'COEF)) VOLTS We) 41.18 INV. QUANTITY, TOTAL I INV.QTYT I OTY 11
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS We) 8.50 TOTAL SYSTEM OUTPUT,IMAXTs I OAC'INV.QTYT) I AMPS(AC) 9.90
MOD.SHORT CCT. CURRENT(Ise) MODULE SPEC AMPS(00 9.00
MOD.MAXIMUM CURRENT(IMAX) (Ise•1.25) AMPS(oU 11.25
MIN.AMPACITY REO'D.PER NEC (IMAX' 1.25) AMPS(00 14.06
SERIES FUSE RATING.MAX MODULE SPEC AMPS(130 IS 46
ELECTRICAL EQUIPMENT SCHEDULE I
KEY OTY MANUFACTURER MODEL NOTES TRADE ^HStr ed t0 YI
1 11 HYUNDAI MIS-S265RG(265W) PV MODULE SOLAR
2 11 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR ,IONS thefe(
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V.30A SOLAR If appn ived pla
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS;I X 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 20A-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL.MIN.125A BUS BLDR.ELEC.
II TBO TBD UTILITY METER,IPH.120/24OV,200A BLDR.ELEC,
12 1 1 1 TBD TBD I GROUNDING ELECTRODE UFER BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
D CONDITION OF USE(COU): (AMPACITY•TEMP.DERATE•FILL DEBATE) Vs.REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS. Vs.REQ'D,(IMAX' 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALL' AMPACITY W/O TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 9.90 ALLOWED PV PER NEC AMPS 40
TERM 25 25 12.38 20 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 9.90
TERM 35 35 12.38 1 20
C #10 CU NM-B COU 40 0.91 1.0 36.40 9.90
TERM 35 35 12.38 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS 1 CU/AL TYPE 1 LOCATION I TRADE
A 1-#12 ENGAGE CABLE.1-#6G,FREE AIR CU TC-ER ARRAY SOLAR
B 3-#Q.1-#10 EGC I CU I NM-B(ROMEX) I INTERIOR SOLAR
C 1 3-#10.1-#10 EGC I CU NM-B(ROMEX) I INTERIOR I SOLAR
D I CAT5E,ETHERNET CABLE I CU CATSE INTERIOR I SOLAR
5 6 II
7 • c u
I M -
SEE NOTE 15 I IO
0 0
0
Hliliffliliffl
'N
GJ
A B C =I2
ROOF I EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.92 KW
LOT#122
ORIGINAL BY: DESIREE WILLIAMS DATE:Ifi.4.14
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:SHAUN MARL24A I DATE:16.4.14
THE LAKES CORONA CA 92879 REV.# BY DATE I DESCRIPTION
namaste
sou•
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
0.Bo Broadway,COStreet
INDIVIDUAL 29705 ARGYLE GIRLIE Boulder, 80009
PLOT PLAN 2 NTS
ELECTRICAL MENIFEE.CA 03.417.0300
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
U ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 40'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMGUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(1')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE (�
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR.-
U DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF
21 26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 00 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE. '
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
)2rR)It
TIUSt b
ELECTRICAL NOTES:
GENERAL-
1)ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTU.
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING.NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646.IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER.CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: DESIREE WILLIAMS DATE:16.4.14
CAMELLIA AT 980 MONTECITO DRIVE.#302 REVIEWED BY: SHAM MARUNA DATE:16.4.14
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION tmmasbd
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29705 ARGYLE CIRCLE Boulder.CO 80304
PLOT PLAN 3 NITS MENIFEE,CA 303.447.030Q
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
DATE
or an
ity
of on the
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV AC DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE — AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 9.9 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: DESIREE WILLIAMS DATE:16.4.1E
CAMELLIA AT LENMAR:
980 MONTELITD DRIVE,#302 REVIEWED BY:SHAUN MARUNA DATE:16.4.14
THE LAKES CORONA.CA 92879 REV.# BY DATE DESCRIPTION
Vniamost(3
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bmdwey Slreel
INDIVIDUAL 29705 ARGYLE CIRCLE BoWder,CO SON
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS