PMT15-03896 City of Menifee Permit No.: PMT16-03896
29714 HAUN RD. Type: Residential Electrical
'[;KCCEL/-> MENIFEE, CA92586
o,'tS.M.'" MENIFEE Date Issued: 12/23/2015
PERMIT
Site Address: 29699 GLENNEYRE WAY, MENIFEE,CA Parcel Number:
92584 Construction Cost: $7,650.40
Existing Use: Proposed Use:
Description of SOLAR TR 30422-3 CAMELLIA
Work: 11 MODULES
LOT 90
Owner Contractor
LENNAR HOMES OF CA LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA,CA 92879 ALISO VIEJO, CA 92656
Applicant Phone:9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO, CA 92656
Fee Description gtv Amount ISI
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE _ 1 1.00
SMIP RESIDENTIAL 1 1.00
General Plan Maintenance Fee-Electrical 1 12.60
$293.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being monied on thereunder when In violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Pennit_Terrplate.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN . • •
-Wenifee
DATE 12/15/2015 PERMIT/PLAN CHECK NUMBER
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA []SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION [—]DEMOLITION ❑ELECTRICAL []MECHANICAL
❑NEW ❑PLUMBING El RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2399-2.92 kW/11 PCS
Master Solar Permit No. PMT14-02630
PROJECTADDRESS 29699 Glenneyre Way, Menifee,CA92584
ASSESSOR'S PARCEL NUMBER LOT 90 TRACT 30422-3
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona,CA
PHONE (951)817-3680 EMAIL jeremiah.acaytuni@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $7,650.40 SQ rT L SO FT
APPLICANT'S SIGNATURE DATE 12/15/2015
CITY STAFF USE ONLY _Afimffp"�
DEPARTMENT DISTRIBUTION Jp I� CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE �/"7 PAID AMOUNT „
AMOUNT J� 0CASH CHECK# OCREDITCARD VISA/MC
PLAN CHECK FEES PAID AMOUNT O CASH O CHECK# O CREDITCARD VISA/MC
OWNER BUILDER VERIFIED 3 YES O NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Haun Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTY MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 1 2.92KW LOCATIONS INDICATED BY THE ILLUSTRATION.
OD MULE 11 PCS.1 HYUNDAI I HIS-S265RG(265W) BUYER: ME IFE
INVERTER IIPCS. ENPHASE M215-60-2LL-S22-IG CITY OF
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION BUILDING A ND
MOD OTY ARRAY NA A V#1 ARRAY#2 RA ARY#3 BUYER: PLAN AI A
TILT 7. NA- NA-
AZIMUTH
VAI
AZIMUTH 180° NA' I NA- DATE:
City of Menifee
REVIEWED
Building Dept
DEC 2 1 [Uib "Approval of these pli nsshal
approval of,any viola on of a
regulations and ordin nces, 1
Received jobsite until completi n.
29'-3'ARRAY
T-10' 30'-I'FLASHING
b
SOLADECK WIRE i
TRANSITION BOX
(UNDER ARRAY) +
PV DISCONNECT
EXTERIOR-GARAGE
---___
I METER 8
MAIN S
MAIN SERVICE PANEL
L_________. (VERIFIED BY BUILDER) V
o
•�I
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 2399 ELEVATION A REVERSE
ORIENTATION 3 LOT#90 N
CAMELLIA AT LENNAR: ORIGINAL BY: BRI MORRIS DATE:15.10.05
980 MONTECITO DRIVE.#502 REVIEWED BY:JIMMY METER I DATE:15.10-05
THE LAKES CORONA.CA 92879 REV.# BY DATE DESCRIPTION •O ,I
nann=a
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29699 GLENNEYRE WAY Boulder,CO 80304
PLOT PLAN 1 1/16'= 1'-0' MENIFEE,CA 303A47.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALL UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(THU) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M215-60-2LL-S22-IG
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER.(WAC MAX) INVERTER SPEC WATTS(AC) 225
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VDC MAX) INVERTER SPEC VOLTS(DC) 48
TEMP,DELTA LOW(TDELTA) THIN-TTEST °C -27 INV.OUTPUT V.(VAC NON) INVERTER SPEC VOLTS(AC) 240 �/ /
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60 1 r
MOD. PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AC) 0.9
MOD. POWER STC(P) MODULE SPEC WATTS(DC) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD. POWER PTC MODULE SPEC WATTS(DO 238 COMPLIANCE INVERTER SPEC UL174I/IEEEIS47
MOD. OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(DC) 31.30 INV.GROUNDING INVERTER SPEC ISOLATED
MOD. OPEN CCT.VOLTAGE(VOO MODULE SPEC VOLTS(DC) 38.10 INV.OTY,MAX/BRANCH CCT. INV.GTYBC CITY 11
MOD. COEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT.OUTPUT, IMAXBC (IAC'INV.QTYBC) I AMPS(Ac) 1 9.90 1
MOD, MAX VOLTAGE(VMAXMOD) (VOC+(TD'COEF)) VOLTS(DC) 41.18 INV.QUANTITY,TOTAL I INV.OTYT I CITY 1 11
MOD. OPERATING CURRENT(IMP) MODULE SPEC AMPS(DC) 8.50 TOTAL SYSTEM OUTPUT.IMAM OAC-INV.QTYT) I AMPS(AC) 1 9.90
MOD. SHORT CCT. CURRENT(ISC) MODULE SPEC AMPS(DC) 9.00
MOD. MAXIMUM CURRENT(]MAX) (Isc•1.25) AMPS(DC) 11.25
MIN.AMPACITY REQ'D.PER NEC (IMAX•1.25) AMPS(DC) 14.06
SERIES FUSE RATING,MAX MODULE SPEC AMPS(DC) 15 t .COnstr
ELECTRICAL EQUIPMENT SCHEDULE VisionsI
KEY CITY MANUFACTURER MODEL NOTES TRADE
1 II HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR Ie ofappr
2 11 ENPHASE M215-60-2LL-S22-IC PV INVERTER SOLAR
3 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT,NEMA 3R,240V.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR, 120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I x 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I x 2DA-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 I TBD TBO SERVICE PANEL.MIN. 125A BUS BLDR.ELEC.
II I TBD TBD UTILITY METER.IPH.120/24OV,2DOA BLDR.ELEQ.
12 I TBD TBD GROUNDING ELECTRODE UFER BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY°TEMP. DERATE- FILL DERATE)V .REO'D(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): I AMPACITY AT TERMINALS. us. REO'D,(IMAX•1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALL. AMPACITY W/0 TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 t35
9.90 ALLOWED PV PER NEC AMPS 40
TERM 25 12.38 20 PV OCPD DEVICE USED AMPS 20
B *10 CU NM-B COU 40 0.91 1.0 9.90
TERM 35 12.38 20
C #10 CU NM-S COU 40 0.91 1.0 9.90
TERM 35 12.38 20
CONDUCTOR SCHEDULE
KEY 1 CONDUCTORS CLVAL TYPE LOCATION TRADE
A 1-#12 ENGAGE CABLE.I-#6G.FREE AIR I CU I TC-ER I ARRAY SOLAR
B 1 3-910,1-#10 EGG I CU I NM-B(ROMEX) I INTERIOR SOLAR
C 3410,1-#10 EGG I CU I NM-B(ROMEX) I INTERIOR I SOLAR
D CAT5E.ETHERNET CABLE I CU I CAT5E I INTERIOR I SOLAR 5 6 11
7 • o O_
SEE NOTE 15 10
IsO
9
I � O zOP
3
IN
G G 1
A D C le
I I I
ROOF EXTERIOR-GARAGE
ELECTRICAL DIAGRAM 2.92 KW
LOT#90
LENNAR: ORIGINAL BY: BRI MORRIS DATE:I5.10.05
CAMELLIA AT 980 MONTECITO DRIVE,#302 REVIEWED BY:JIMMY METER I DATE:15.10,05
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namast6
soLev
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broad ay Street
INDIVIDUAL 29699 GLENNEYRE WAY Boulder,GO 80304
PLOT PLAN 2 NTS MENIFEE,CA 303.447.03DO
ELECTRICAL
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
O ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS.TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS.IT WILL BE FLASHED AND SEALED. . M111A RTl
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3.PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(1')SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
B)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
D DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF Y.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(I')OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS. ''.a pi
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION. 'decal,
vans m
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL),
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED T0.PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
IU MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
IB)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT;WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LENNAR: ORIGINAL BY: BRI MORRIS DATE:15.10.05
CAMELLIA AT 980 MONTECITO DRIVE,9302 REVIEWED BY:JIMMY METER DATE:15.10.05
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namast(3
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
4574 Bmadvay Street
INDIVIDUAL 29699 GLENNEYRE WAY BoWd"..CO 80304
PLOT PLAN 3 NTS
NOTES MENIFEE.CA 303.447.0300
CAUTION: ENT
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN.
in
rl
te
9LGGELR WIRE
,R.T"80R
'LRSSA 69RAY)
PV AC 0L9C0WffCT
45
EIIiEAIOR-GCRP4E
ur�un nErEn e
MCN y P6VEL
ryERWl.IEO BY BIIILpER)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT; SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 9.9 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: BRI MORRIS DATE:15.10.05
CAMELLIA AT LENNAR:
980 MONTECITO DRIVE.#302 REVIEWED BY:JIMMY MET ER I DATE:15.10.05
THE LAKES CORONA,CA 92879 REV.# BY DATE DESCRIPTION
namasbe
30UR
DWG TITLE: 7PAGE#: CALE: SITE LOCATION: 4571 Broadway StreetINDIVIDUAL 29699 GLENNEYRE WAY Boulder,GO 80304
PLOT PLAN TS MENIFEE.CA 303.447.0300
PLACARDS