PMT15-03580 City of Menifee Permit No.: PMT15-03580
29714 HAUN RD. Type: Residential Electrical
<ACCELA—> MENIFEE,CA 92586
NA- MENIFEE Date Issued: 12/1512015
PERMIT
Site Address: 29203 SWEETBRIAR CT, MENIFEE, CA Parcel Number: 333-640-008
92584 Construction Cost: $10,689.60
Existing Use: Proposed Use:
Description of SOLAR TR 31582-1 MENIFEE HILLS
Work: 14 MODULES 3.71 KW
LOT 94
Owner Contractor
LENNAR HOMES OF CA, INC LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ALISO VIEJO, CA 92656
Applicant Phone: 9493498269
JEREMIAH ACAYTURRI License Number.728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO, CA 92656
Fee Description ON Amount ISl
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1, 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permil_Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
Menifee
DATE 11/05/2015 PERMIT/PLAN CHECK NUMBER MTIS 0v_F-.>8O
TYPE: ❑COMMERCIAL 2 RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/SPA ❑SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION [-]DEMOLITION []ELECTRICAL [-]MECHANICAL
[-]NEW ❑PLUMBING ❑RE-ROOF-NUMBER OF SQUARES
DESCRIPTION OF WORK Solar Permit-Plan 2809-3.71 kW l 14 PCS
Master Solar Plan No.: PMT14-00706
PROJECTADDRESS 29203 Sweetbriar Ct, Menifee,CA 92584
ASSESSOR'S PARCEL NUMBER 333-640-008 LOT 94 TRACT 31582-1
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr., Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
APPLICANT NAME Jeremiah Acayturri
ADDRESS 980 Montecito Dr.,Suite 302
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? AYES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $ 10,689.60 ESQ FT
APPLICANT'S SIGNATURE DATE 11/05/2015
CITY STA_FFVSEONLY
DEPARTMENT DISTRIBUTION I()C �� CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN SMIP
INVOICE PAID AMOUNT n
AMOUNT CASH OCHECKq GCREDIT CARD VISA/MC
PLAN CHECK FEES PAID AMOUNT OCASH --CHECK# 0 CREDIT CARD VIWMC
OWNER BUILDER VERIFIED 0 YES 0 NO DL NUMBER NOTARIZED LETTER 0 YES 0 NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM 1 OTY MFR. 1 MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
SYSTEM SIZE 3.71 KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 1 14PCS. HYUNDAI I HIS-S265RG(265W) BUYER: • `rV OF M NIF
INVERTER 14 PCS. ENPHASE M215-60-2LL-S22-IG
ROOF TYPE I TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE: �`„` NG ND
SUB-ARRAY INFORMATION
MOD OTY ARRAY#I ARRAY
NA#2 ARRNA#3 BUYER: PIP
APP OVi
TILT 23° NA- I NA'
AZIMUTH ISO- I NA' I NA' City of MemteE DATE:
Building Dep,
NOV 13
REVIEWED BY,
��;�
RPi`s •Aoaroval of then plans
approval of,any vii lation
regulations and on linano
22'-9'ARRAY jobsite until compl tion.
23'-7'FLASHING 9'-V
t —
it
I
e t
—, SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
PV DISCONNECT
EXTERIOR-GARAGE
UTILITY METER 6
MAIN SERVICE PANEL
L (VERIFIED BY BUILDER)
Ir
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF
PLAN 3 ELEVATION B-R
ORIENTATION 3 LO #94 N
ORIGINAL BY: ERIK MAY I DATE:15.11.03
MENIFEE HILLS LENNAR: REVIEWED BY:JIMMY METER DATE:I5.I1.03
CO NA,CA I92 DRIVE,#302
CORONA,CA 92879 REV.# BY DATE DESCRIPTION
;PmamasrA
SOLAR
DWG TITLE: PAGE #: SCALE: SITE LOCATION: _ _. — ---4571 Bmadway Sweat
INDIVIDUAL 29203 SWEETBRIER COURT Boulder,CO 80304
PLOT PLAN 1 1/16'=1'-0' MENIFEE,CA 303. 47.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE,CA INV. MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(TMAX) ASHRAE 2% °C 37 INV. MODEL INVERTER SPEC M215-60-2LL-SZ2-I
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER,(WAC MAX) INVERTER SPEC WATTS(AC) 225 L
TEMP,MODULE TEST(TTEST) MODULE SPEC °C 25 INV. INPUT V.(VDC MAX) INVERTER SPEC VOLTS(DC) 48
TEMP,DELTA LOW(TEELTA) THIN-TTEST °C -27 INV.OUTPUT V.(VAC NOM) INVERTER SPEC VOLTS(AC) 240 Er
MOD. MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC HIS-S265RG INV.OUTPUT CURRENT,IAC INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(DC) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(DC) 238 COMPLIANCE INVERTER SPEC ULI741/IEEE1547 °
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(OC) 31.30 INV. GROUNDING INVERTER SPEC ISOLATED
MOD.OPEN CCT. VOLTAGE NOD) MODULE SPEC VOLTS(DC) 38.10 INV.CITY,MAX/BRANCH CCT. 21 OTY'C QTY 14
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT. OUTPUT,IMAXBC (IAC•INV.OTYSC) AMPS(AC) 12.60
MOD. MAX VOLTAGE(VMAXMOD) (VOC♦(TD°COEF)) VOLTS(DC) 41.18 INV. QUANTITY.TOTAL INV.OTYT OTY 14
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS(DC) 8.50 TOTAL SYSTEM OUTPUT,IMAXTS (IAC'INV.QTYT) IAMPS(AC) 12.60
MOD.SHORT CCT.CURRENT(IBC) MODULE SPEC AMPS(DC) 9.00
MOD.MAXIMUM CURRENT(IMAX) (ISC ° 1,25) AMPS(DC) 11.25
MIN.AMPACITY REQ'D,PER NEC (IMAX° 1.25) AMPS(DC) 14.06 'I ni t be c0
SERIES FUSE RATING.MAX MODULE SPEC AMPS(DC) I IS
ELECTRICAL EQUIPMENT SCHEDULE any arovish
KEY OTY MANUFACTURER MODEL NOTES TRADE Thl set of
1 14 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR
2 14 ENPHASE M215-60-2LL-S22-IG PV INVERTER SOLAR
3. 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221URS PV AL DISCONNECT,NEMA 3R,24OV,30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR.120V SOLAR
6 1 TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
8 NOTE CUTLER-HAMMER TBO PV BRANCH CIRCUIT BREAKERS: I X 15A-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I x 2OA-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL.MIN. 125A BUS BLDR.ELEC.
II TBD TBD UTILITY METER, IPH,120/24OV,200A BLOB.ELEC.
12 1 TBD TBD GROUNDING ELECTRODE LIFER BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY°TEMP. DERATE °FILL DEBATE)us.REDID(IMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS.yB.REQ'D.(IMAX° 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CA.C. AMPACITY W/O TEMP. FILL RESULT REQ'D OCD BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 12.60 ALLOWED PV PER NEC AMPS 40
TERM 25 25 15.75 20 PV OCPD DEVICE USED AMPS 20
B #10 Cu NM-B COU 40 0.91 1.0 36.40 12.60
TERM 35 35 15.75 20
C #10 Cu NM-B COU 40 0.91 1.0 36.40 12.60
TERM 35 35 15.75 20
CONDUCTOR SCHEDULE
KEY CONDUCTORS 1 CU/AL 1 TYPE LOCATION TRADE
A I-#12 ENGAGE CABLE.I-#6G.FREE AIR CU TC-ER ARRAY SOLAR O
B 3-#10,I-#10 EGL I CU I NM-B(ROMEX) I INTERIOR SOLAR 5 fi II
C 3-#10.1-#10 EGL I CU I NM-S(ROMEX) I INTERIOR I SOLAR 7SEENOTE
C= 0
D CAT5E,ETHERNET CABLE CU CAT5E INTERIOR SOLAR I M
15 10 O
ISAIIP
O O O O 20A/2P
3 IL_
N
G G G-�
I -
ROOF GARAGE
ELECTRICAL DIAGRAM 3.71 KW
LOT#94
MENIFEE HILLS LENNAR: ORIGINAL BY: ERIK MAY DATE:15.11.03
980 MONTECITO DRIVE,#302 REVIEWED BY:JIMMY METER I DATE:15.11.03
CORONA,CA 92879 REV.# BY DATE DESCRIPTION •,
namasbe
3o1A9
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
--INDIVIDUAL - - _ - 9571 BraaAvdY Street
PLOT PLAN 2 NTS 29203 SWEETBRIER COURT Boulder.CO 80304
ELECTRICAL MENIFEE.CA 303.447.0300
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
D ALL PV ROOF ATTACHMENTS WILL BE.SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT. AP9Y�
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3,PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH 01 SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(21 BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40%
ROOFING CONTRACTOR-
U DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION.IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT 00 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE,COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE. JEE Ix�p
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIROSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE. BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO 1 bdm
INSTALLATION.
{ plamII
ELECTRICAL NOTES:
GENERAL-
U ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING.NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703, IEC61646,IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER.AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING.OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SMALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT 1-.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
ORIGINAL BY: ERIK MAY DATE:I .11.
LENNAR: 03
MENIFEE HILLS REVIEWED BY:JIMMY METER DATE:15.11.03
980 MONTECITO DRIVE.#3D2
CORONA,CA 92879 REV.# BY DATE DESCRIPTION
ti namasGe
f OLAr
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: 4571 Broadway Street
-- INDIVIDUAL - 29203 SWEETBRIER COURT — - Boulder,CO 803D4
PLOT PLAN 3 NTS MENIFEE,CA 303.447.0300
NOTES
CAUTION: :NT
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN. ' e
DATE
iit for,or an
ate or city
t be kept on the
sDLarEcrc vnaE
1pAV R BOA
6wDER apanvl
Pv a D•EDM@CT
1 EZTEpI¢G 6NLLtE
U�ILfTSMEtEq!
ERVI[E PYIEL
(VEpiIED BY p1YZ0ER)
d�
�TJJI
II
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 12.6 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: ERIK MAY DATE:15.11.03
MENIFEE HILLS LENNAR:
980 MONTECITO DRIVE,#302 REVIEWED BY:JIMMY METER I DATE:15.11.03
CORONA.CA 92879 REV.# BY DATE DESCRIPTION
t9namast;d
SOLAR
DWG TITLE: PAGE#: I SCALE: SITE LOCATION: _ _ 4571 Broadmdy Street
INDIVIDUAL 29203 SWEETBRIER COURT BOWdu.CO 80304
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS