PMT15-03410 City of Menifee Permit No.: PMT15-03410
29714 HAUN RD.
�CCEL/> MENIFEE, CA 92586 Type: Residential Electrical
MENIFEE Date Issued: 11106/2015
PERMIT
Site Address: 29052 GUAVA ST, MENIFEE, CA 92584 Parcel Number: 333-631-020
Construction Cost: $14,593.40
Existing Use: Proposed Use:
Description of SOLAR TR-31582-1 MENIFEE HILLS
Work: 3.71 KW 14 MODULES
LOT 30
Owner Contractor
LENNAR HOMES OF CA, INC LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR#302 25 ENTERPRISE
CORONA, CA 92879 ALISO VIEJO, CA 92656
Applicant Phone: 9493498269
JEREMIAH ACAYTURRI License Number:728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO, CA 92656
Fee Description City Amount!$1
Solar, Residential or Small Commercial 1 252.00
Building Permit Issuance 1 27.00
GREEN FEE 1 1.00
SMIP RESIDENTIAL 1 2.00
General Plan Maintenance Fee-Electrical 1 12.60
$294.60
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing builiding operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee.Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,orwhere the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA_Bldg_Permit_Template.rpt Page 1 of 1
BUILDING & SAFETY PERMIT/PLAN CHECK APPLICATION
Menifee
DATE 10/28/2015 PERMIT/PLAN CHECK NUMBER ? 1 t lS-"
TYPE: ❑COMMERCIAL ❑✓ RESIDENTIAL ❑MULTI-FAMILY ❑MOBILE HOME ❑POOL/5PA ❑SIGN
SUBTYPE: ❑✓ ADDITION ❑ALTERATION []DEMOLITION ❑ELECTRICAL [-]MECHANICAL
[]NEW ❑PLUMBING [:IRE-ROOF-NUMBEROFSOUARES
DESCRIPTION OF WORK SOLAR PERMIT-Plan 3105-3.71 kW/14 PCS
Master Solar Plan#PMT14-00706
PROJECT ADDRESS 29052 Guava St, Menifee,CA 92584
ASSESSOR'S PARCEL NUMBER 333-631-020 LOT 30 TRACT 31582-1
PROPERTY OWNER'S NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302
PHONE (951)817-3680 EMAIL leremiah.acayturri@lennar.com
APPLICANT NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302,Corona,CA 92879
PHONE (951)817-3680 EMAIL jeremiah.acayturri@lennar.com
CONTRACTOR'S NAME Lennar Homes of California, Inc. OWNER BUILDER? ❑✓ YES❑NO
BUSINESS NAME Lennar Homes of California, Inc.
ADDRESS 980 Montecito Dr.,Suite 302, Corona,CA 92879
PHONE (951)817-3680 EMAIL )eremiah.acayturri@lennar.com
CONTRACTOR'S STATE LIC NUMBER 728102 LICENSE CLASSIFICATION A&B
VALUATION$ $ 14,593.40 SO FT L SO FT
APPLICANT'S SIGNATURE DATE 10
CITY STAFF USE ONLY
DEPARTMENT DISTRIBUTION CITY OF MENIFEE BUSINESS LICENSE NUMBER
BUILDING PLANNING ENGINEERING FIRE GREEN I 1` SMIP
INVOICE �G46Q PAIDAMOUNT
AMOUNT -{ OCASH 0CHECK# 0CREDIT CARD VISA/MC
PLAN CHECK FEES PAIDAMOUNT 0CASH 0 CHECK# OCREDITCARD VISA/MC
OWNER BUILDER VERIFIED OYES C NO DL NUMBER NOTARIZED LETTER O YES O NO
City of Menifee Building&Safety Department 29714 Houn Rd. Menifee, CA 92586 951-672-6777
www.cityofinenifee.us Inspection Request Line 951-246-6213
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM 1 OTV MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
71 SYSTEM SIZE 3. KW LOCATIONS INDICATED BY THE ILLUSTRATION.
MODULE 1 14 PCS.1 HYUNDAI I HIS-S265RG(265W) BUYER:
INVERTER 1 14 PCS.1 ENPHASE I M215-60-2LL-S22-IG
ROOF TYPE I TILE W1 COMPOSITE SHINGLE UNDER ARRAY DATE:
SUB-ARRAY INFORMATION
ARRAY#1 ARRAY#2 ARRAY#3 City of W. f', I i' 3�AEN1 EE
MOD OTY 10 2 2 BUYER:
i
TILT 23° Building 23° 23° � r„
AZIMUTH ISI° 271° 91° DATE: LW Ii SA
NOV 0 4 a- PLAN APPROVAL
le
R e c e. ;t REVIEWED BY
'Approval of these plans s all not
22'-9"ARRAY approval of,any violation any pl
3' 23'-7'FLASHING
regulations and ordinances This s
———————— —- — jobsite until completion.
t
I
i
t
SOLADECK WIRE
TRANSITION BOX
(UNDER ARRAY)
r
i
u
I I
�LL —
PV-� DISCONNECT Q I EXTERIOR-GARAGE
UTILITY METER a 41111111111111111
-—' MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF N
PLAN 3105 ELEVATION C-REVERSE ® A.
ORIENTATION ----L5=9
ORIGINAL BY: DESIRES WILLIAMS I DATE:15.09.2L
MEN I FEE HILLS LENNAR:
980 MONTECITO DRIVE.#302 REVIEWED BY:TOM FIDDES DATE:15.09.24
CORONA,CA 92879 REV.# BY DATE DESCRIPTION
�Pniamcist*
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway S0ea1
INDIVIDUAL 29052 GUAVA STREET Bouldx,CO B03N
PLOT PLAN 1 1116'=1'-0' MENIFEE.CA 303.447.0300
SYSTEM LAYOUT
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT DETAIL ITEM NOTE/CALC UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(THAR) ASHRAE 2% °C 37 INV.MODEL INVERTER SPEC M2I5-60-2LL-S22-IG
TEMP,AMBIENT LOW(THIN) ASHRAE EXTR.MIN °C -2 INV.MAX POWER,(WAG MAX) INVERTER SPEC WATTS CAC) 225
TEMP.MODULE TEST(TESST) MODULE SPEC °C 25 INV. INPUT V.(Voc MAX) INVERTER SPEC VOLTS(GC) 48
TEMP,DELTA LOW(TDaTA) THIN-TTEST °C -27 INV.OUTPUT V.(VAc NOM) INVERTER SPEC VOLTS(AC) 240
MOD.MANUFACTURER MODULE SPEC HYUNDAI INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC 18S-S265RG INV.OUTPUT CURRENT.IAc INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS CDC) 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.POWER PTC MODULE SPEC WATTS(cc) 238 COMPLIANCE INVERTER SPEC UL1741/IEEE1547
MOD.OPERATING VOLTAGE(VMP) MODULE SPEC VOLTS(cc) 31.30 INV.GROUNDING INVERTER SPEC ISOLATED
MOD,OPEN CCT. VOLTAGE(VOC) MODULE SPEC VOLTS(0C) 38.10 INV.QTY.MAX/BRANCH CCT. NV_G C1 OTY 1 14
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC V/°C -0.114 BRANCH CCT. OUTPUT, IMAXBc (IAc°INV.GTYac) I AMPS(AO) 1 12.60
MOD. MAX VOLTAGE(VMAXMO9) (VOG+(T9°COEF)) VOLTS(cc) 41.18 INV.QUANTITY,TOTAL I INV.QTYT I QTY 1 14
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS CDC) 8.50 TOTAL SYSTEM OUTPUT.IMAXTS I(IAC-INV.QTYT) I AMPS(AG). 12.60
MOD.SHORT CCT.CURRENT(1st) MODULE SPEC AMPS(0c) 9.00
MOD. MAXIMUM CURRENT(IKAX) (15c• 1.25) AMPS(DC) 11.25 /
MIN.AMPACITY REO'D,PER NEC (IMAX-L25) AMPS(oc) 14.06 !/
SERIES FUSE RATING,MAX MODULE SPEC AMPS(cc) 15 51yd
ELECTRICAL EQUIPMENT SCHEDULE
KEY CITY MANUFACTURER MODEL NOTES TRADE
1 14 HYUNDAI HIS-S265RG(265W) PV MODULE SOLAR
2 14 ENPHASE M215-60-2LL-S22-IG PVINVERTER SOLAR
3 3 RSTC/SOLADECK 0786-3RS PV ROOF JUNCTION BOX,NEMA 3R SOLAR ( 05tFU(
4 1 CUTLER-HAMMER DG221URB PV AC DISCONNECT.NEMA 3R.24OV,30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR is On$Of
6 I TBD TBD 120V DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TBD TBD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR ) appro)
8 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS,I X ISA-IP(ENVOY) SOLAR
9 14OTF CI ITLFR-HAMMER TBD PV ORFAKFR,IX 20A-2P,LOCATE AT OPPOSITE END OF BUS FROM MAIN BRFAKER SOLAR
10 1 TBD TBD SERVICE PANEL,MIN. 125A BUS BLDR. ELEC.
11 I TBD TBD UTILITY METER,IPH.120/24OV.200A BLDR.ELEC.
12 TBD I TED I GROUNDING ELECTRODE UFER I BLDR. ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS
1)CONDITION OF USE(COU): (AMPACITY•TEMP.DERATE ° FILL DERATE) vs.REO'D(TMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS. vs.REQ'D.(IMAX ° 1.25) PANEL MFR. CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC' AMPACITY W/0 TEMP. FILL RESULT REO'D OCD BUS RATING AMPS 200
TYPE DERATES DERATE DERATE (A) W USED(A) MAIN DISCONNECT AMPS 200
A #12 CU THWN-2 COU 30 0.76 1.0 22.80 12.60 ALLOWED PV PER NEC AMPS 40
TERM 25 25 15.75 20 PV OCPD DEVICE USED AMPG 20
B #10 CU NM-B COU 40 0.91 1.0 36.40 12.60
TERM 35 35 15.75 20
C #10 CU NM-B COU 40 0.91 1.0 36.40 12.60
TERM 35 35 15.75 20
CONDUCTOR SCHEDULE
KEY 1 CONDUCTORS CU/AL TYPE LOCATION TRADE
A I-#12 ENGAGE CABLE,I-96G.FREE AIR CU TC-ER ARRAY SOLAR
B 3-#10.I-#10 EGC I CU I NM-B(ROMEX) INTERIOR I SOLAR
C 3410,I-#IO EGC I CU I NM-B(ROMEX) INTERIOR I SOLAR
D CATSE,ETHERNET CABLE I CU I CATSE I INTERIOR I SOLAR
5 6 II
7 • o o _
SEE NOTE 15 O O
0 WIO (SNIP
G O
� LAM
I I I
ROOF E RIOR-GARAGE
ELECTRICAL DIAGRAM 3.71 KW
LOT#30
LENNAR: ORIGINAL BY: DESIREE WILLIAMS I DATE:15.09.24
MENIFEE HILLS 980 MONTECITO DRIVE.#302 REVIEWED BY:TOM FIDDES DATE:15.09.24
CORONA CA 92879 REV.# BY DATE DESCRIPTION
namaste
SOLAR
DWG TITLE: PAGE#: SCALE: SITE LOCATION:
INDIVIDUAL 4Bo &o,COStreet
PLOT PLAN 2 NTS 29052 GUAVA STREET Boulder, 7. BD004
ELECTRICAL
MENIFEE,CA 303.447.030D
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
D ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 48'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE.
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3'ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3.PUB 140113-ICC.JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I-)SPACE BETWEEN PV MODULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2.)BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOUNT REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'. RTA
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL BE A MINIMUM OF 3'.
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL'TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION. IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT(11 OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE,DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE. COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO _
INSTALLATION.
e a pei
ederal,)
:ans mu
ELECTRICAL NOTES:
GENERAL -
U ALL PV EQUIPMENT WILL BE TESTED AND LISIEU FOR ITS USE BY A NA110NALLY RECOGNIZED TESIING LABORATORY(NRTL).
2)THE GROUNDING OF THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CEC.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90-C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE UL1703,IEC61646.IEC61730.
8)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W/ENPHASE MICRO-INVERTER SYSTEM.
11)MODULE AND ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SURFACE AND SHALL BE MANAGED IN A WORKMANLIKE MANNER.
12)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 250.122.
13)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING,OR MANUFACTURER'S RECOMMENDATIONS.
14)A PV AGGREGATION PANEL(SUB PANEL)WILL NOT BE INCLUDED FOR SYSTEMS WITH ONE BRANCH CIRCUIT.
15)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET(OR EQUIVALENT)FOR ENPHASE ENVOY MONITOR.
SIGNAGE-
16)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
17)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
18)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING. BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT t.
19)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MARKED'PHOTOVOLTAIC POWER SOURCE:OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 10'.
BUILDER ELECTRICAL AND SOLAR CONTRACTORS-
20)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
21)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26.
LE14NAR: ORIGINAL BY: DESIREE WILLIAMS I DATE:15.09.24
MEN I FEE HILLS 980 MONTECITO DRIVE.#302 REVIEWED BY: TOM FIDDES I DATE:15.09.24
CORONA,CA 92079 REV.# BY DATE DESCRIPTION If a n S A.
fetA
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bmadeay Street
INDIVIDUAL 29052 GUAVA STREET BONdw.CO 803N
PLOT PLAN 3 NTS MENIFEE.CA 303.447.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY THE
UTILITY AND A SOLAR PV SYSTEM. DISCONNECTS
ARE LOCATED AS SHOWN. NT
�► 4 /S
DATE
..NO WE 1.�a
igpNSrtlpN POM
(UNEP OPP1Y1 r city
y2pt 0 UI!
9- 21
gIaR-ceq<cE
-TEP n
.S CEPMEL
(4F 10BYPIIILMRI
0
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
I-877-SLR-POWR
PV POWER SOURCE - AC SPECS
AC OPERATING VOLTAGE: 240 V
AC OPERATING CURRENT: 12.6 A
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
ORIGINAL BY: DESIREE WILLIAMS DATE:15.09.24
MENIFEE HILLS LENNAR:
980 MDMIELITD DRIVE.#302 REVIEWED BY:TOM FIDDES DATE:15.09.24
CORONA.CA 92879 REV.# BY DATE DESCRIPTION
Vnamasr(5
{aL�!
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29052 GUAVA STREET Sadder.CO 80304
PLOT PLAN 4 NTS MENIFEE,CA 303.447.0300
PLACARDS