PMT15-00667 C R H O
Architecture Interiors Planning
195 S.°C'Street,Suite 200
Tustin,CA 92780
714-832-1834
FAX 714-832-1910
July 14, 2015
City of Menifee
Building Department
29714 Haun Road
Menifee, CA 92584
Re: Buffalo Wild Wings
30123 Haun Road
Menifee, CA 92584
Permit No: PMT15-00667
We have incorporated the Building Department comments dated July 2, 2015 by Esgil
Corporation to our set of drawings. The changes are clouded and under Delta #4
Agency Revision 7-14-15..
The following is a response to the agency comments with a description of where the
changes occurred:
Buildine—Ali Sadres:
1. Please submit three revised...
We are resubmitting 5 complete set to building department.
2. Please see attached...
Acknowledged.
3. To speed up the process...
Acknowledged.
GENERAL & ARCH. PME ITEMS GLEN ADAMEK:
1. The K-sheets are not signed...
Acknowledged K-sheets signed.
2. The City building official...
See approval letter. Health Department approved set was turned into
Building Department.
4. The new Utility Plans...
a) See revised civil sheet loft. Site plans match.
City of Menifee
Building Department
Page 2 of 2
i
S. The response provided states...
We contact Tait Engineering and provided requested information on
sheet loft.
7. Correct the Reclaimed Water...
The Reclaimed water and domestic calculations revised relocated from
sheet P400 to sheet P301.
12, On the gas riser diagram...
Dirt legs on gas isometric fixed on sheet P302, gas leg isometric example
created for clarification.
Please don't hesitate to call me if you have any additional questions my telephone
number is (714) 832-1838 #28.
By:
Roberto Diaz
Project Manager
CRHO Architects, Inc.
Cc Dale Hartwig—Buffalo Wild Wings
2
RIVERSIDE COUNTY COMMUNITY HEALTH Ad`„IENCY
IDEPARTIIa9ENT OF ENVIRONMENTAL HEALTH
FOOD ESTABLISHMENT PLAN APPROVAL NOTICE
SR# 33172 Date 4/7/15
Project Name Buffalo Wild Wins Address 30123 Haun Rd., Menifee, CA
Plans Submitted by Roberto Diaz
Phone 714-832-1838 ext 28
Owner SAA Address 5500 Wayiata Blvd #1600 Minneapolis Phone 952-59_3_9943
The plans are now approved subject to the conditions listed below and the attached compliance
p nce sheet
.
1. Increase backup dry storage shelving from the indicated 37 linear to 48 linear feet. Note: Per Mr
Diaz additional wall shelving to be added. To be evaluated and a proved prior to final approval.
2. Ensure that bar equipment with drain lines drains indirectly to a floorsink . Drain lines must be
properly air gaped.
3. Interior walls and floor of dumpster area must be smooth finished and sealed with an approved
epoxy type cement/block sealer
4. Prior to final approval provide a copy of the Grease Interceptor sizing letter and Will Serve letter
from the local water and sewer agencies.
5. Prior to final approval provide an approved air balance report from a certified air balancer.
CONSTRUCTION INSPECTIONS: Contact the Plan Checker for a Preliminary Inspection when construction is
approximately 80% complete, with plumbing, rough ventilation, and rough equipment installed. Request for
inspection should be made at least five (5) working days in advance.
A FINAL INSPECTION MUST be made upon completion of ALL work including finished details. APPROVAL to
operate shall not be granted, or remodeled areas approved to operate, until the facility has passed the FINAL
INSPECTION, and "APPLICATION TO OPERATE" has been completed and PERMIT FEES have been paid.
Request for inspection should be made at least five (5) working days in advance.
PLANS CHECKED BY David Albietz#028
Phone 951-461-0245
1 acknowledge the corrections noted herein and as indicated on the plans and agree to incorporate them during
construction:
Signature Date
Company Name_
DEH-SAN-178(Rev 2/06)
2275 S.Main St Suite 204 800 S.Sanderson 47-950 Arabia St"A" 38740 Sky Canyon Dr 554 S.Pase60) o Dorotea 4065 County Cir
(951)273-9140 (951)766-2824 (760)863-8287 (951)461-0284
Fax(951)520-8319 Fax(951)766-7974 FtLY(760)863-8303 Fax(951)461-0245 Fax(760) 3320 1470 Fax�(951)35851) -5017
Department Web Site—www.riwoeh.org
2270 Trumble Rd., Perris CA 92570
EASTERN MUNICIPAL P•0, Box 8300 Perris CA 92572-8300
W A T E R o I S T R I C r .. Telephone (951) 928-3777
SINCE 1950
PLAN CHECK SUPPLEMENTAL PAGE
Date: 5/13/2015 PPI No. 20150000206 SC Site No.
Business Name: Buffalo Wild Wings
Site Address: 30123 Haun Road Menifee CA 92584
1. Waste Discharge Application dated 3/20/2015 is acceptable for Source Control issues.
2. Installation of 2500 gallon grease interceptor with sample box is acceptable. The
interceptor must be installed per SB-70. See attached.
3. The rough plumbing must be inspected prior to backfilling. Installation of interceptor
including connections must be inspected prior to backfilling. Please call (951) 928-
3777 ext. 6203 to schedule inspections 48 hours in advance. Failure to schedule
inspections may require dye test at an additional cost of$100.00 per hour.
4. If a water softener is installed currently or in the future, it must be of the type that does
not discharge brine to the sewer as per EMWD Ordinance 59.6 Article 3.6(A)(1):
"Prohibiting Users from discharging the regeneration cycle from any
water conditioning appliance, including but not limited to water softeners
or conditioners, to the POTW."
5. Waste Discharge Application fee of$225.00, plan check review/inspection fee of
$195.00, and all New Business fees must be paid before final Clearance will be
issued.
Inspector: Scarlett Draper �rolDivVision
Released for first to TS
For more information, please call EMWD Source C at (951) 928-3777 ext
6203.
J:\Source_control.821Penns-APPROVED ONLYI\Fonns-Plan ChecklPC Supplementals\FSE with new grease Interceptors.doc