PMT14-00928 City of Menifee Permit No.: PMT14-00928
MENIFEE, CA 92586 29714 HAUN RD.
4W6cm Type: Residential Electrical
f�k
MENIFEE Date Issued: 0 511 2/2 01 4
PERMIT
Site Address: 29093 NECTARINE ST, MENIFEE, CA Parcel Number: 333-631-006
92584 Construction Cost: $9,353.40
Existing Use: Proposed Use:
Description of INSTALL RESIDENTIAL ROOF MOUNTED SOLAR PV SYSTEM
Work: 14 MODULES 14 MICROINVERTERS 3.57KW
MASTER PLAN CHECK PMT14-00706
Owner Contractor
LENNAR HOMES OF CA, INC LENNAR HOMES OF CALIFORNIA INC
980 MONTECITO DR STE 302 25 ENTERPRISE
CORONA, CA 92879 ALISO VIEJO, CA 92656
Applicant Phone: 9493498000
AMY WILLIAMS License Number: 728102
LENNAR HOMES OF CALIFORNIA INC
25 ENTERPRISE
ALISO VIEJO, CA 92656
Fee Description ON Amount 131
'� ^SJaR r t ^Yw�•a s. =+s r?'-f a^e 1* .t re sm ,-gyp- a nos& FR""2a a
Solae,�Res-lde��lal�malsL�CoTmmeraal �rt�.���, ,a��zzs� _, , °rN -� �m252Q'�.
Building Permit Issuance 1 27.00
'ems• :�� "i.� � "� � T:sr rrr,+ cfi-"�a�` e �, i r
SMIP RESIDENTIAL 1 1.00
$281.00
The issuance of this permit shall not prevent the building official from thereafter requiring the correction of errors in the plans and
specifications or from preventing building operations being carried on thereunder when in violation of the Building Code or of any other
ordinance of City of Menifee. Except as otherwise stated,a permit for construction under which no work is commenced within six
months after issuance,or where the work commenced is suspended or abandoned for six months,shall expire,and fees paid shall be
forfeited.
AA Bldg Permit_Template.rpt Page 1 of 1
' i
CITY OF MJENIFElE PLCK No:
29714 Haun Road Data: Cat : a4
Menifee, CA 92586
Phone: (951)672-6777 Amoun: Amounl;�U G1
Fax:(951)679-3843 Ck#: Ck#:
Building Combination Permit
7o Be completed �yAppllcant
Lega Description: Menifee Hills/El Dorado I Planning Case:
Property Address: / 9��9 As s or's Parcel Numb
T31582-1 Lot—L�—N/
Pro ecV'fenant Na Unit#: a Floor P.
"'P31852-1 El Dorado
Name: PhoneNo951.207.3045 Fax No.
Letmar Homes of California,Inc.
Property Address: Ulnit Number ZIP Code
Owner 980 Montecito Drive,Suite 302 Corona 92879
Email Address:
Name: Phone No.951.207.3045 Fax No.
Amy Williams
Applicant Address:Same as above Unit Number Zip Coda
Email Address: amy.williams@lennar.Com
Name: Phone No. Fax No.
Contractor Address: City State I Zip Code
Contractors City Business License No. Contractor CZry State of California License No. Classification: B
Number of Squares;
Square Footage
of work,R- ?�
Description of Work:
Applicant's Signature Data'
To as Completed By City Staff Only
I rdi caia As R-Received or N/A-Not Applicable
5 Completes sels of fully dimensioned,drawn to sale plans which include: i set of documents which Include i
❑ Tile Sheet ❑ Elevations ❑;Mectricaln ❑W
olls Report(on cd only)lan ❑ rgy(on E y,x 11) I
❑ Plol!SitePlan ❑ Roof Plan ❑ alculations❑ diagram for elec.services overJ
❑ Foundation Plan ❑ Cross Section ❑ nFloor Plan ❑ Structural Framing Plan&Details ❑ ❑ ort-ResidentialClass Code: Indicate New ConstrmctonAlteration' ddition* Means/MetWorkType: Repair' - Retrofit' vislonto EAsling Permit'Required?
Proposed Building Use(s): Existing Building Use(s):
#Buildings: #Units: .tl Stories: Will the Building Have a Basement? Y of N
Bldg.Code Occupancy Group Indicate it Indicate all Geo-tech.Haz.Zane
At Project Indicate Spdnklered YES or NO that apply: Coastal Zone
Construction Noise Zone
Completion: Type(s): Colo YES or NO
Faquired7 Listed on Historic Resources Inventory
CITY PLANNING STAFF ONLY
APPROVALS: Costal Commiss Arch.Review Board Landmark Comm. Planning Comm.Zoning Administrator
Cil Pro ecl Elec.Vehicle Char er Landmark Seismic Retrofit aa'of case:tit g.
Fee Exempt: y 1 g ornnaIA royal
Expedite Protecl(s): Child Care Cily Protect Green Building Landmark Affordable Hauling
For Staff Use Only
aulltlinglsalely PenoilSpecalsl I City Planning Civ Engineering EPW - min Transportation MgmL Renl Control
THANK YOU FOR HELPING US CREATE ABETTER COMMUNITY
SYSTEM INFORMATION BUYER ACKNOWLEDGES THAT THE SOLAR MODULES TO BE INSTALLED
ITEM OTV MFR. MODEL ON THE ROOF OF THE HOME WILL BE SUBSTANTIALLY IN THE
LOCATIONS INDICATED BY THE ILLUSTRATION,
SYSTEM S12E i 3.579W
MODULE I It,PCS. I RENESOLA JC255S-24180-0 BUYER:—--------_-----------------
INVERTER 14 PCS. I ENPHASE M215-A0-2LL-S22-IO
ROOF TYPE d TILE W/COMPOSITE SHINGLE UNDER ARRAY DATE:_-__---_—___-----------------------
SUB-ARRAY INFORMATION
ARRAY#I ARRAY#2 ARRAY#3
MID OTY 14 NA NA BUYER:________-----------------
TILT 1 23° MA. I NA° DATE-
A2IMUYH 1 187° NA' I NA'
II--�
UTILITY METER 8 .1
MAIN SERVICE PANEL ul
(VERIFIED BY BUILDER) ff
-_
� gyp/
TV AC DISCONNECT --
EXTERIOR-GARAGE /���J
I �
I I I I
I
I I
I I
� I
I
-- - - 9--3Y--ARRAYCITY OF MENIFE Q
SOLADECK WIRE TRANSITION BOX 9'-3 Y- 23•-3Y,-ARRAY 8'40}-FLASHING
(UNDER ARRAY) 24'-I Y_--FLASHING UILDING AND AFETY C
PLAN APPROVAL
REVIEWED BY -
NOTE:DIMENSIONS ARE SHOWN IN PLANE OF ROOF "Approval of these plans shal not he constn
approval of,any viokbm of a iy provisions c
ION A-R
PLAN 2INELEVAT LOT#fi rernlatinns and o ces. is set of appn
ORIENTATION 3
ORIGINAL BY: STACEY MCKINNEY I DATE A
ENNAR:
MERIDIAN AT REVIEWED BY:TOM fI00ES 1 DATE:14.3.20
980 MONTECITO DRIVE REV.# BY DATE DESCRIPTION
MENIFEE HILLS CORONA,CA92789 �namasb6
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 Bra -,ay Ste l
INDIVIDUAL 79093 NECTARINE ST. Boulder,CO 80304
PLOT PLAN I/16"=1'-0' MENIFEE•CA 303.447.D300
SYSTEM LAYOUT
i
i
K,
PLAN 2809 ELEVATION A-R
ORIENTATION 3 LOT# G
LENNAR: ORIGINAL BY: TOR FI MCIONNEV DATE:14.3.28
MERIDIAN AT REVIEWED BY:TOM ODEB DATE 14.3.20
980 MONTECITO DRIVE REV.k BY GATE DESCRIPTION !"
MENIEEE HILLS CORONA.Cd921B9 unamasud
SOLAR
DWG TITLE: PAGE e: SCALE: SITE LOCATION: 4571 Broadway Street
INDIVIDUAL 29093 NECTARINE ST. Boulder,GO 80304
PLOT PLAN 2 /G4'=1-0 MENIPEE.CA 303.447.0300
SITE PLAN
MODULE SPECS AND CALCULATIONS INVERTER SPECS AND CALCULATIONS
ITEM NOTE/CALC UNIT I DETAIL ITEM NOTE/LALC UNIT DETAIL
LOCATION MENIFEE,CA INV.MAKE INVERTER SPEC ENPHASE
TEMP,AMBIENT HIGH(Fli ASHRAE 2% 'C 37 INV.MODEL INVERTER SPEC M215-60-21LS22-I15
TEMP,AMBIENT LOW(TMIM) ASHRAE EXTR.MIN 'C -2 INV.MAX POWER,(WAC MAX) INVERTER SPEC WATTS(Ad 225
TEMP.MODULE TEST(TTEST) MODULE SPEC 'C 25 INV.INPUT V.(Vuc MAX) INVERTER SPEC VOLTS(DO 48
TEMP,DELTA LOW FVELTN THIN-TTEST 'C -2] INV.OUTPUT V.(Vac NOM) INVERTER SPEC VOLTS(AU 240
NOD.MANUFACTURER MODULE SPEC RENESOLA INV.OUTPUT FREQUENCY INVERTER SPEC HERTZ 60
MOD.PART NUMBER MODULE SPEC JC255S-24/B0-D INV.OUTPUT CURRENT,Inc INVERTER SPEC AMPS(AC) 0.9
MOD.POWER STC(P) MODULE SPEC WATTS(DO 265 INV.PHASE QUANTITY INVERTER SPEC PHASE I
MOD.OPERATING VOLTAGE(Vnr) MODULE SPEC VOLTS(DU 30.20 COMPLIANCE INVERTER SPEC UL17LIll EE1547
MOD.OPEN CCT.VOLTAGE WOO MODULE SPEC VOLTS(DC 37.60 INV.GROUNDING INVERTER SPEC ISOLATED
MOD.COEFF.VOLT/TEMP(COEF) MODULE SPEC VPC -0.117 INV.OTY.MAX/BRANCH CCT. INV9TYac OTV 14
MOD.MAX VOLTAGE(VMAXM M) (VOG ((WCOEF)) VOLTS(oc7 40.76 BRANCH CCT.OUTPUT,Inaxec (IAC'INV.GTYec) AMPS(AU 12.60
MOD.OPERATING CURRENT(IMP) MODULE SPEC AMPS()d 0.44 INV.QUANTITY,TOTAL INV.QTYi I OTY M
MOD.SHORT CCT.CURRENT(ISO MODULE SPEC AMPS(00 8.99 TOTAL SYSTEM OUTPUT,IMAXIS I(IAC'IN0.0TYt) I AMPG(Ac) 12.60
MOD.11AXIMUM CURRENT(8uX) Bsc-1.25) AMPS(0c) 11.24
MIN.AMPACITY REGO.PER NEC OMA}'1.25) AMPS CDC) 14.05
SERIES FIRE RATING.MAX MODULE SPEC AMPS(DC) 20
ELECTRICAL EQUIPMENT SCHEDULE
KEY 1 OTY MANUFACTURER MODEL MOTES TRADE
IL RENESOLA JC255S-24/68-8 PV MODULE SOLAR
2 1 14 1 ENPHASE M21540-21LL-S224G PV INVERTER SOLAR li
3 I 1 RSTC/SOLADECK 0786-3R5 PV ROOF JUNCTION BOX,NEMA 3R SOLAR
4 1 CUTLER-HAMMER DG221LRB PV AC DISCONNECT,NEMA 3R.24OV.30A SOLAR
5 1 ENPHASE ENVOY PV DATA MONITOR,120V SOLAR
6 1 TRO TBD IZOV DEDICATED RECEPTACLE FOR ENVOY PV DATA MONITOR SOLAR
7 1 TOD TOD CATS PORT FOR SOLAR PV INTERNET CONNECTION TO HOME NETWORK BOX SOLAR
0 NOTE CUTLER-HAMMER TBD PV BRANCH CIRCUIT BREAKERS:I x ISA-IP(ENVOY) SOLAR
9 NOTE CUTLER-HAMMER TBD PV BREAKER,I X 2OA-2P.LOCATE AT OPPOSITE END OF BUS FROM MAIN BREAKER SOLAR
10 1 TBD TBD SERVICE PANEL MIN. 125A BUS R.ELEC.
it I TBD TBD UTILITY METER,IPH,120/24OV.200A BLDR.ELEC
12 1 TRO TRD GROUNDING ELECTRODE UFER BLDR.ELEC.
CONDUCTOR SIZING CALCULATIONS INTERCONNECTION CALCULATIONS !,
1)CONDITION OF USE(COU): (AMPACITY'TEMP.DEBATE-FILL DEBATE) vs.REO'D OMAX) ITEM UNIT PANEL
2)TERMINALS(TERM): AMPACITY AT TERMINALS. .REO'D.UMAX-1.25) PANEL MFR. if I CUTLER-HAMMER
KEY SIZE CU/AL INSULATION CALC. AMPACITY W/0 TEMP. FILL R SULT REO'D OCD BUS RATING NIPS 200
TYPE DERATES DERATE DERATE (A) (A) USED(A) MAIN DISCONNECT AMPS 200
A W12 CU THWN-2 COU 30 .76 1.0 22.801 12.60 ALLOWED PV PER NEC AMPS 40
TERM 25 25 I5.75 20 PV OCPD DEVICE USED AMPS 20
B #10 CU NM-B COU 40 .91 L0 36.40 12.60
TERM 1 35 1 1 115.75 1 20
C 910 CU NM-B COU 40 .91 I.0 36,0 12.60
TERM 35 3 115.15 1 20
CONDUCTOR SCHEDULE
KEY I CONDUCTORS 1CU/AL TYPE LOCATION TRADE
A -#12 ENGAGE LABLE. -#6G.FREE AIR CU TC-ER ARRAY SOLAR
B 3-#10.I-#10 EGC LU MM o(ROMEX) INTERIOR SOLAR
C 3-#10,I-#10 EGC CU NM (ROMEX) INTERIOR I SOLAR
D CAT5E.ETHERNET CABLE I CU I CATSE INTERIOR SOLAR
6 5 0
o � 7
SEE EFL RTMEN
N NOTE 20
sO i Q
c
e a
o=
EXTERIOR-GARAGE ROOF
d to b a pamit f01 .
the fe MI,sate ni
ELECTRICAL DIAGRAM 3.57sW
LOT#6 'I?d must be
ORIGINAL BY: STACEY MCKINNE
LENNAR: Y DATE.14.3.20
MERIDIAN AT REVIEWED BY:TOM FIDDES DATE:IL_3.28tu
980 MONTECITO DRIVE REV.# BY DATE DESCRIPTIONMENIFEE HILLS CORONA,CA92789 namast6
oue
DWG TITLE: PAGE#: SCALE: SITE LOCATION: 4571 BIODtlmey Slreel
INDIVIDUAL 29093 NECTARINE ST. RDN0e4 GO 60304
PLOT PLAN 3 NTS MENIFEE,CA 303.447.0WO
ELECTRICAL
it
STRUCTURAL NOTES:
SOLAR CONTRACTOR-
S ALL PV ROOF ATTACHMENTS WILL BE SPACED ALONG MODULE RACKING RAILS AT NOT GREATER THAN 4B'O.C.
2)ALL PV ROOF ATTACHMENTS WILL BE STAGGERED BY ROW AMONGST THE ROOF FRAMING MEMBERS,TO MAXIMUM EXTENT POSSIBLE,
3)ROOF PENETRATIONS ASSOCIATED WITH SOLAR RACKING WILL BE SEALED WITH AN APPROVED SEALANT.
4)SOLADECK WIRE TRANSITION BOX WILL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. IT WILL BE FLASHED AND SEALED.
5)PV ARRAY WILL BE A MINIMUM OF 3-ABOVE THE COMPOSITE SHINGLE ROOF SURFACE.
6)THE UNIRAC SOLARMOUNT RACKING SYSTEM AND SOLAR PV ARRAY WILL BE INSTALLED ACCORDING TO THE UNIRAC SOLARMOUNT CODE-COMPLIANT INSTALLATION
MANUAL,VERSION 227.3.PUB 140113-ICC,JANUARY 2014.
7)UNIRAC TOP CLAMPS REQUIRE A ONE INCH(I')SPACE BETWEEN PV MCIDULES.SOLARMOUNT RAILS MUST EXTEND A MINIMUM OF TWO INCHES(2-)BEYOND THE EDGE
OF THE PV ARRAY/SUB-ARRAY.
8)UNIRAC SOLARMOL94T REQUIRES THAT A THERMAL EXPANSION GAP BE INSTALLED FOR ANY RAIL LENGTH OF GREATER THAN 40'.
ROOFING CONTRACTOR-
1)DISTANCE BETWEEN ARRAY EDGE AND TRANSITION FLASHING(COMPOSITION TO TILE)WILL RE A MINIMUM OF 3%
2)26 GAUGE INTERLOCKING FLASHING'SIDEWALL-TO BE INSTALLED ALONG THE LENGTH OF THE PV ARRAY AT ROOFING MATERIAL TRANSITION.IT SHALL BE
APROVED PRIOR TO PV SYSTEM INSTALLATION.
3)PEEL-N-STICK BASE TO BE INSTALLED ONE FOOT O)OR MORE BEYOND THE EDGE OF THE COMPOSITION SHINGLE.DOWN TO THE ROOF EAVE.PEEL-N-STICK BASE TO
BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS.
4)AREAS UNDER EACH PV ARRAY SHALL BE ROOFED WITH COMPOSITION SHINGLE.COMPOSITION SHINGLE SHALL RUN FROM ABOVE THE PV ARRAY TO THE ROOF EAVE.
5)TILE INSTALLED BELOW THE ARRAY TO BE INSTALLED ABOVE THE COMPOSITION ROOF PER ROOFER SPECIFICATIONS.
6)BIRDSTOP WILL BE INSTALLED AT THE UPPERMOST TRANSITION FROM TILE TO COMPOSITION SHINGLE.BIRDSTOP TO BE SPECIFIED BY ROOFER PRIOR TO
INSTALLATION.
ELECTRICAL NOTE&
GENERAL-
S ALL PV EQUIPMENT WILL BE TESTED AND LISTED FOR ITS USE BY A NATIONALLY RECOGNIZED TESTING LABORATORY(NRTU.
2)THE GROUNDING BE THE PHOTOVOLTAIC SYSTEM SHALL COMPLY WITH THE APPLICABLE VERSION OF THE NEC/CE[.
3)ALL GROUNDING ELECTRODE CONDUCTORS WILL BE INSTALLED IN A CONTINUOUS LENGTH EXCEPT WHERE SPLICED BY AN IRREVERSIBLE CONNECTOR OR EXOTHERMIC
WELD.
4)NON-CURRENT CARRYING METAL PARTS SMALL BE CHECKED FOR PROPER GROUNDING,NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE
MAY BE ELECTRICALLY INSULATED BECAUSE OF PAINT/FINISH. PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.
5)ROOF PENETRATIONS WILL BE COMPLETED AND SEALED PER APPLICABLE CODE.
6)ALL CONDUCTORS WILL HAVE A 90°C RATING TO ENSURE CODE COMPLIANCE.
SOLAR CONTRACTOR-
7)MODULE CERTIFICATIONS WILL INCLUDE ULI703,IEC61646,IEC6I730.
B)CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS.
9)RACEWAY POINT OF PENETRATION FROM EXTERIOR TO INTERIOR WILL BE SEALED TO PREVENT INGRESS OF WATER AND INSECTS.
10)DC WIRING IS LIMITED TO PV ARRAY FOOTPRINT W)ENPHASE MICRO-INVERTER SYSTEM.
ID MODULE AM ENPHASE WIRING SHALL BE LOCATED AND SECURED UNDER THE ARRAY USING SUITABLE WIRING CLIPS.WIRING SHALL NOT MAKE CONTACT WITH THE
ROOF SLRFACE AND SHALL BE MANAGED IN A WORKMAN-LIKE MANNER.
SIGNAGE-
12)PV SYSTEMS SHALL BE CLEARLY MARKED IN ACCORDANCE WITH NEC ARTICLE 690 AND OTHER APPLICABLE STATE AND LOCAL CODES.
13)ALL SAFETY MARKING/PLACARDS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE OR OTHER MECHANICAL MEANS.
14)MARKING/PLACARDS WILL BE METAL OR PLASTIC WITH ENGRAVED OR MACHINE PRINTED LETTERING.BACKGROUND WILL BE RED WITH WHITE CAPITAL LETTERING OF
MINIMUM HEIGHT e.
15)ALL WIRING/RACEWAYS/JUNCTION BOXES WILL BE MAIMED'PHOTOVOLTAIC POWER SOURCE;OR EQUIVALENT:WIRING/RACEWAYS SHALL BE MARKED EVERY 101.
BUILDER ELECTRICAL CONTRACTOR-
16)INSTALLATION SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER.
17)SPACE REQUIREMENTS FOR ALL ELECTRICAL EQUIPMENT WILL COMPLY WITH NEC ARTICLE 110.26-
18)EQUIPMENT GROUNDING CONDUCTORS WILL BE SIZED IN ACCORDANCE WITH NEC TABLE 25L122.
19)CONDUCTOR TERMINATIONS WILL BE TORQUED PER DEVICE LISTING.OR MANUFACTURER'S RECOMMENDATIONS.
20)A DEDICATED 120V BRANCH CIRCUIT IS REQUIRED IN MASTER CLOSET FOR ENPHASE ENVOY MONITOR.
ORIGINAL BY: STACEY MCKINNEY I DATE:I
LENNPR: L.3.28
MERIDIAN AT REVIEWED BY:TOM FIODES DATE:14.3.28
980 MONTECITO DRIVE REV.# BY DATE DESCRIPTION
MENIFEE HILLS CORONA.CA92789 �anamast6
aRre.
DWG TITLE: PAGE M: SCALE: SITE LOCATION: 4571 BroaUay Street
INDIVIDUAL 1 29093 NECTARINE ST. Boulder,CO WON
PLOT PLAN 4 NTS MENIFEE.CA 303.447.0300
NOTES
CAUTION:
POWER TO THIS BUILDING IS SUPPLIED BY
THE UTILITY AND A SOLAR PV SYSTEM.
DISCONNECTS ARE LOCATED AS SHOWN.
UTILITY METER 8
MAIN SERVICE PANEL
(VERIFIED BY BUILDER)
PV AC DISCONNECT
EXTERIOR-GARAGE
SOLADECK WIRE TRANSITION BOX
(UNDER ARRAY)
SERVICE BY QUALIFIED PERSONNEL ONLY
CONTACT: SUNSTREET ENERGY GROUP
1-877-SLR-POWR
NOTE: SEE MASTER SET FOR ADDITIONAL PLACARD INFORMATION
LENNAR: ORIGINAL BY:STACEY MCKINNEY DATE:14.3.2E
MERIDIAN AT REVIEWEDBY:TOM FIDOES DATE:14.3.28
980 MONTECITO DRIVE REV.R BY DATE DESCRIPTION
MENIFEE HILLS CORONA,CA92789 ViaamasGB
sb6
DWG TITLE: PAGE h: SCALE: SITE LOCATION: 4571 B 8A9.y 5129t
INDIVIDUAL 2909S NECTARINE ST. Baultl ,CC80304
PLOT PLAN 5 NTS MENIFEE,CA 303.447.0300
PLACARDS